![Asentria Teleboss 850 User Manual Download Page 30](http://html.mh-extra.com/html/asentria/teleboss-850/teleboss-850_user-manual_2981745030.webp)
TeleBoss 850 2.06.280_STD User Manual
Page 24
Include Time in Filename
is an ON/OFF toggle to enable the addition of the file transfer time to the name of each
transferred file of data. Default setting is OFF.
Include Sequence #s in Filename
is an ON/OFF toggle to enable the addition of a unique sequence number to the
beginning of the name of each transferred file of data. This ensures that no two transfers will have the same file
name. Default setting is OFF.
Data File
n
/ Events File
are text-entry fields where the name each data file will have on the remote server (not
including any date, time, or sequence numbers) can be configured.
Note:
There is no menu option to set “FTP Auto-delete”, a setting that will cause all data in the file to be deleted
when polled via the FTP ‘get’ function. To enable FTP Auto-delete, set
net.ftp.autodel
=ON
.
Once FTP Push has been configured, entering the
PUSHTEST
command will test the connectivity to the FTP server
and write a “log in” and “log out” entry to the Status File in the directory you configured. No data is pushed with this
command. Connection data displayed on the terminal screen is useful if the connection fails.
An immediate push of data can be done using the
PUSHNOW
command.
PPP Settings
TeleBoss 850 - PPP Settings
A) PPP Dialout Settings
B) PPP Hosting Settings
C) IP Routing
D) Route Test Settings
displays settings pertaining to making outbound PPP network connections.
displays settings for hosting a PPP connection.
displays settings for routing of IP packets between PPP connections and the LAN a T850 is connected to.
displays settings for network monitoring/PPP backup connection settings. This menu allows
you to configure up to three IP addresses to ping on a regular basis. If any of the configured addresses are up then
the unit will assume Ethernet is a reliable way of sending SNMP traps. If all configured addresses are down then the
unit will fall back to PPP dialout in order to maintain reliable network connectivity for sending SNMP traps.
PPP Dialout Settings
TeleBoss 850 - PPP Dialout Settings
A) PPP Dialout Enabled [OFF]
B) Telephone Number []
C) User Name []
D) Password [********]
E) Idle Connection Disconnect (sec) [60]
F) Maximum Retries [3]
G) Carrier Detect Timeout (sec) [60]
H) Login Sequence Timeout (sec) [30]
I) Dialout Modem Init String []
J) IP Address to Suggest [0.0.0.0]
PPP Dialout Enabled
is an ON/OFF toggle to enable PPP dialout. Default setting is OFF.
Telephone Number
sets the phone number of the PPP host the T850 is to dial into. (Max length 48 chars)
User Name / Password
sets the login credentials that are used to log into the PPP host. (Max length for each is 64
chars)