10
4. CLOSING
4.1. IN GENERAL
IO90.195.120.K3.WDC
IO90.195.060.K9.WDC
IO90.195.060.L8.WDC
The doors are permanently self-closing.
The cabinets feature a cylinder lock with closing status indicator.
They can be integrated into a master key system.
IO90.078.059.057.U9.S
The drawer is not permanently self-closing. The cabinet has a cylinder
lock with a locking status indicator.
The drawer has a thermal release and closes automatically in the event
of a fire.
ATTENTION:
The owner/user must ensure that all doors are kept closed whenever the contents of the cabinet are
not being accessed. In general, it must be noted that the cabinets do not possess an emergency unlocking
facility. This means that persons trapped inside the cabinet cannot free themselves!
5. INTERIOR FITTINGS
5.1. BOTTOM COLLECTING SUMP
11
22
According to EN 14470-1:
A bottom collecting sump must be
installed below the lowest storage level. The bottom collecting sump
must be able to hold a minimum volume of 10 %of all the containers
stored in the cabinet
[1]
or at least 110 % of the volume of the largest
single container
[2]
, whichever of these volumes is larger.
Leaks:
• Liquid in the sump is to be collected using suitable means.
• The choice of means is your own responsibility.
IO90.195.120.K3.WDC
IO90.195.060.K9.WDC
IO90.195.060.L8.WDC
1
2
3
IO90.078.059.057.U9.S
1
2
3