asecos EN 14470-1 User Manual Download Page 6

6

6

1. NOTES • GUIDELINES • GUARANTEE

1.1.  GENERAL SAFETY NOTES

• Observe applicable statutes and regulations, and the notes in these operating instructions, when 

handling hazardous materials.

• Work on the electrical system is to be carried out only with the power turned off and only by 

qualified electricians – refer here to the regulations of the local electricity supply company.

• The on-site installation conditions are to be observed (e.g. bolting the cabinets to the building).

• The instructions of the supervisory engineering department must be followed.

• Observe accident prevention regulations and workplace ordinance.

• Ensure that the necessary safety checks are only carried out by authorised staff using original spare 

parts.

• Only use the cabinet after having been properly instructed; access is to be forbidden to  

unauthorised persons.

• The pivoting area of the doors is to be kept free at all times; doors/drawers are to be kept closed.

• By assigning trained/authorised technical personnel you can prevent the malfunctions, damage 

and corrosion damage that result from inappropriate transport.

• Observe the upper limits for stored quantities, loading etc.

• Containers with a volume larger than that of the spill containment sump may not be placed 

inside the cabinet; spilt hazardous materials are to be collected immediately and removed.

• Vessels containing aggressive chemicals (acids/alkalis) are to be kept in special cabinets for acids and 

alkalis or on shelves for acids and alkalis as well as in cabinets with metal-free interior equipment.

• Sufficient technical ventilation must be ensured , pay attention to the notices on connection to 

an extraction system under point 9.1!

• Before storing such materials, check that the cabinet's surface is resistant to the chemicals.

• The storage of corrosive liquids or gases can affect the function of the shut-off equipment for the 

air supply and exhaust.

• Before the initial commissioning, the safety storage cabinet is to be examined by the user for 

possible damage. 

(See point 3.2)

Set-up requirements

 

   

   

0–35 °C

  

30–70 %

1.2.  GUARANTEE

The guarantee for this product is agreed between you (the customer) and your dealer  

(the seller). As the manufacturer, asecos guarantees the products listed in the operating instruc-

tions for a period of 24 months from the date of delivery.

All model safety equipment are subject to a compulsory annual inspection by specialised staff 

authorised by the manufacturer. Otherwise the customer’s guarantee claim against the  

manufacturer expires.

1.3.  CABINET DETAILS

A complete overview of the models can be found at the start of the operating instructions. 

Cabinet data

  

  Logbook (included with the cabinet)

Technical drawing 

 

Appenidix 1

Technical data

  

 

Table in Appendix 2

 

S-LINE • Q-LINE • UB-LINE • XL-LINE • K-LINE

These models are tested, certified and marked according to requirements of BS EN 14470-1. 

They are intended for the storage of combustible liquids in work rooms in accordance with the 

valid national regulations.

G-CLASSIC-30 • G-ULTIMATE-90

These models are tested, certified and marked according to requirements of BS EN 14470-2. 

They are intended for the storage and emptying of gas cylinders in buildings in accordance with 

the valid national regulations.

Summary of Contents for EN 14470-1

Page 1: ...tariff with a fixed term of 5 years you will get a war ranty extension for a maximum of 5 years for your safety storage cabinet Weitere Informationen zu unseren Garantieleistungen finden Sie unter ww...

Page 2: ...CR S90 129 120 WDAC S90 129 060 WDAC S90 129 060 WDACR S PHOENIX 30 S90 197 120 FDAS S90 197 060 FDAS S90 197 060 FDASR S PHOENIX 90 S90 196 120 FDAS S90 196 120 MV FDAS S90 196 090 FDAS S90 196 060 F...

Page 3: ...060 110 050 2S UB90 060 110 050 S UB90 060 110 2S UB90 060 110 2S 0103 UB90 060 110 PZ 2S UB90 060 110 S UB90 060 110 S 0103 UB90 060 140 050 2S UB90 060 140 2S UB90 060 140 2S 0103 UB90 060 140 PZ 2...

Page 4: ...t freundlichen Gr en asecos GmbH YOUR PERSONAL DOCUMENTATION TO THE asecos SAFETY CABINET Dear Customer you have made a decisive investment in safety for your company by purchasing this asecos safety...

Page 5: ...NG FUNCTION 8 3 1 Alignment of the cabinets 8 3 2 Commissioning 10 3 3 Anti tilt device 10 4 CLOSING MECHANISMS 10 4 1 Types of closing 10 4 2 Automatic door closing system TSA 11 4 3 Locking 12 5 INT...

Page 6: ...tal free interior equipment Sufficient technical ventilation must be ensured pay attention to the notices on connection to an extraction system under point 9 1 Before storing such materials check that...

Page 7: ...ally trained staff Tilting the cabinet may only be done without jolts Dismantling of the transport packaging 1 4 2 8 3 4 5 6 In plant transport is also possible without transport locks inserted as sta...

Page 8: ...e given immediatly 8 3 4 5 6 7 5 CAUTION Afterwards lower the cabinet slowly and without jolts in order to prevent damage Remove the transport locks from the door joints after erection 3 ERECTION COMM...

Page 9: ...d for this can be obtained on enquiry from asecos service 1 1 Unlock the cabinet and open it manually 2 Remove the power cable from the interior 3 Align the cabinet 4 Allow the cabinet to close automa...

Page 10: ...re IEC power cable including earthed mains plug 3 3 ANTI TILT DEVICE x x CAUTION If these model groups are equipped with drawers they must be fastened to the wall using the anti tilt device supplied A...

Page 11: ...060 MV MH FDAS 3 3 3 3 3 3 3 3 3 3 K PHOENIX Vol 2 90 3 3 3 3 3 K UB 90 3 3 UB LINE UB30 060 110 2TAS 3 3 ALL MODELS 3 XL LINE ALL MODELS 3 3 3 G LINE G CLASSIC 30 G ULTIMATE 90 3 Q CLASSIC 15 30 90 U...

Page 12: ...ely mechanically and only with the very low forces of the closing spring Reaching inside the cabinet during the closing process is therefore harmless and the risk of injury is ruled out 4 3 LOCKING CA...

Page 13: ...CONTAINMENT SUMP 1 2 According to EN 14470 1 A spill containment sump must be installed below the lowest storage level The spill containment sump must be able to hold a minimum volume of 10 of all th...

Page 14: ...ULTIMATE 90 6 1 MOUNTING RAILS for fittings for pressurised gases height adjustable 6 2 CYLINDER RETAINER a permanently mounted on the rear wall b tension belts for securing the gas cylinders c adjus...

Page 15: ...he cabinet wall must be properly sealed with suitable fire protection putty ROKU 1000 order no 6520 over the full area and the complete wall thickness It is recommendable to manufacture the pipes from...

Page 16: ...y and exhaust Each container placed inside reduces the minimum containment volume demanded in section 5 1 in relation to the total stored quantity The total volume of the stored gas cylinders must not...

Page 17: ...1 GENERAL FACTS NOTICES The fire protection valves near the supply and extraction air connections are safety and maintenance relevant components In order to check the correct operation or to replace a...

Page 18: ...e cabinet and must be screwed to the openings on the top section 9 3 G CLASSIC 30 G ULTIMATE 90 CAUTION In the case of gas cylinder cabinets that are connected to a technical exhaust system the minimu...

Page 19: ...your warranty claims in the case of fire only by an authorised asecos employee refer also to our service brochure regarding this In addition we recommend that you carry out a daily and monthly functi...

Page 20: ...2020...

Page 21: ...0 195 116 Q30 195 086 Q30 195 086 R Q90 195 120 Q90 195 120 WDAC Q90 195 120 FD Q90 195 090 Q90 195 090 WDAC Q90 195 060 Q90 195 060 WDAC Q90 195 060 R Q90 195 060 WDACR Q LINE S LINE 843 160 160 620...

Page 22: ...LINE S PHOENIX 30 S CL ASSIC 90 S PEGASUS 90 S30 197 120 FDAS S90 196 090 WDAS WDAC WDEU 230 8 9 708 333 150 616 406 333 Zuluft Abluft 75 Erdungsm glichkeit Draufsicht 1202 1004 98 952 338 598 88 Zul...

Page 23: ...0 060 110 050 2T UB90 060 110 ST UB90 060 110 050 ST UB90 080 110 060 2S UB90 080 110 075 2T XL CL ASSIC 90 XL CL ASSIC 90 XL90 222 155 WDAS XL90 222 110 WDAS UB LINE XL LINE 512 532 2360 125 1404 403...

Page 24: ...334 36x 40 40 84 181 157 21 m a x 1 8 0 Abluft 75 Erdungsm glichkeit Zuluft 75 Draufsicht 230 184 406 96 m a x 1 8 0 1135 325 82 150 Draufsicht Abluft 75 Zuluft 75 Erdungsm glichkeit Rohrdurchf hrungs...

Page 25: ...bei 10fachem Luftwechsel Air flow and Pressure Loss at 10times Air change volume en drukverlies bij 10 voudige luchtverversing volume et perte de pression avec un taux de renouvellement de l air de 10...

Page 26: ...FDACR 600 615 1968 450 520 1740 90 310 S90 196 090 FWAS 900 615 1968 750 520 1740 90 310 XL90 222 155 WDAS 1105 1015 2225 935 850 2030 90 855 XL90 222 110 WDAS 1555 1015 2225 1385 850 2030 90 1150 UB...

Page 27: ...5 6 5 5 1 5 600 626 75 60 25 19 22 73 20 6 8 5 1000 686 75 235 213 64 23 9 15 1000 833 75 230 209 09 16 1 15 300 246 2 50 2 8 7 2 1 1 300 246 50 17 5 16 2 2 1 300 246 30 25 22 2 2 1 300 205 50 13 5 8...

Page 28: ...et sich aus der Breite des Schrankes multipliziert mit der Tiefe Summe aus Tiefe des Schrankes und 1000mm Aktionsraum davor BEISPIEL Q90 195 120 Schrankgewicht 424 kg Beladung 600 kg Einzugsfl che 120...

Page 29: ...2 529 kg m2 Il peso specifico si ottiene dal peso totale dell armadio armadio vuoto carico compreso diviso per la sua superficie utile Questa si calcola moltiplicando la larghezza dell armadio per la...

Page 30: ...3030...

Page 31: ...31 31...

Page 32: ...asecos GmbH Abt Kundendienst Weiherfeldsiedlung 16 18 D 63584 Gr ndau Fax 49 60 51 92 20 10 www asecos com Ihr Fachh ndler Your partner Uw partner Votre partenaire Su distribuidor su richiesta...

Reviews: