Ascon Tecnologic - Z31V - OPERATING INSTRUCTIONS - PAG. 4

Moreover, 

before connecting the outputs to the ac-

tuators

, check that the parameters set are the desired 

ones and the application works correctly in order to 
avoid malfunctions in the plant that could cause dam-
age to people, things or animals.

4.3.1 

Electrical wiring diagram

Z31V

Inputs

Power supply

Out1

SPDT

SPST-NO

Out1: 

 16 A-AC1 (6 A-AC3)/250 VAC; 1 HP 250 VAC, 1/2 HP 125 VAC

Common:

 12 A max. for models with removable terminal blocks

Probe

NC

C

NO

C

NO

Internal

Buzzer

5.  FUNCTIONS

5.1 

Measure and display configuration

Using the parameter 

i.SE

 it is possible select the type of 

probe is connected to the instrument:

Pt

 

Thermistor PTC KTY81-121,

nt

 

Thermistor NTC 103AT-2.

Instead, with the 

i.uP

 parameter it is possible to select the 

temperature engineering unit and the desired measure reso-
lution (

C0

 = °C/1°; 

C1 

= °C/0.1°; 

F0

 = °F/1°; 

F1

 = °F/0.1°).

The instrument allows the measurement calibration, which 
can be used to recalibrate the instrument according to appli-
cation needs, the calibration is made by using parameter 

i.C1

.

Using 

i.Ft

 parameter it is possible to set a software filter 

for the measuring the input values in order to decrease the 
sensibility to rapid temperature changes (increasing the time).  
The instrument normally displays the temperature measure-
ment, but it is possible see the maximum and minimum peak 
measurement using the 

 key.  Pressing and releasing the 

 key the display alternately shows the code that identifies 

the variable (see below) and its value.  The variables are:

Lt

 

Minimum stored temperature;

Ht

 

Maximum stored temperature;

Pr1

  Current temperature measured by probe Pr1.

Minimum and maximum peak values are not retained when 
the power is removed and can be reset by pressing the 

 

key for 3 s while the peak value is displayed.  After 3 sec-
onds the display shows “

---

” for an instant to indicate the 

peak value has been erased and takes as peak temperature 
the one measured at that moment.
The variables display mode is automatically abandoned after 
about 15 seconds from the last pressure of the 

 key

5.2 

Alarm functions

The alarm conditions of the instrument are:

 

Probe errors 

E1

 and 

-E1

;

 

Temperature alarms 

Hi

 and 

Lo

.

The alarm functions act on the   LED, the internal buzzer, if 
present and configured by the parameter 

o.bu

 and the relay 

output if present.
The parameter 

o.bu

 allows the configuration of the internal 

buzzer as follows:

oF

 

Buzzer disabled

1

 

Buzzer activated only to signal alarms;

2

 

Buzzer activated briefly only to signal the keys pres-
sures (does not signal alarms);

3

 

Buzzer is activated to signal both alarms and key 
pressures.

Any active alarm condition is signaled  with the   LED 
switched on while the  silent  alarm condition is signaled with 
the flashing   LED.
The buzzer (if any) can be configured to signal alarms  by 
programming the parameter 

o.bu

 = 1 or 3 and always oper-

ates as a tacit alarm signal.  This means that, when activat-
ed, it can be silenced by a short pressure of any key.
The relay output, if present, will be activated when an alarm is 
triggered to deactivate when there are no alarms in progress.

5.3 

Temperature alarms

The temperature alarm function acts according to the meas-
urement of the probe, the alarm thresholds set at parameters 

A.HA

 (maximum alarm) and 

A.LA

 (minimum alarm) and the 

A.Ad

 

differential.
By means of some parameters it is also possible to delay 
the enabling and the intervention of these alarms.  These 
parameters are:

A.PA

  Temperature alarm exclusion time when powering ON 

the instrument if, when switched ON, it is in alarm con-
dition.  If at power ON the instrument is not in alarm 
conditions, the 

A.PA

 time is not considered;

A.At

  Temperature alarm delay activation time.  The temper-

ature alarm is enabled at the end of exclusion time and 
is triggered after the 

A.At

 time, when the temperature 

measured by the probe rises above or falls below the 
respective maximum and minimum alarm thresholds.

AL

A.LA

A.HA

Temp.

A.Ad

A.Ad

time

off

off

off

ON

ON

Hi

Lo

Maximum and minimum temperature alarms can be disabled 
by setting their relevant parameters 

A.HA

 and 

A.LA

 = 

oF

.

Summary of Contents for Z31V

Page 1: ...o be equipped with additional electromechanical devices which will guarantee safety 1 INSTRUMENT DESCRIPTION 1 1 General description The Z31V is a digital electronic microprocessor thermometer equipped with functions for temperature alarms The instrument has 1 input for PTC or NTC temperature probes and can be equipped with either an internal buzzer or a relay output for alarm signaling The Z31SV ...

Page 2: ...ord that can be personalised through t PP parameter To protect the parameters set the desired password number at t PP parameter When the protection is active press the key to access the parameters and keep it pressed for about 5 s after which the display shows r P Press the key again the display will show 0 at this point using the and keys set the programmed password number and press the key again...

Page 3: ... Panel cut out 29 0 6 71 0 6 mm RECOMMENDED PANEL CUTOUT min 12 mm min 15 mm 4 2 3 Mounting mm Type 2 gasket max 12 mm Type 1 gasket 29 mm max 34 43 Type 2 Type 1 Butterfly type brackets Screw type bracket 86 4 3 Electrical connections Carry out the electrical wiring by connecting only one wire to each terminal according to the following diagram checking that the power supply is the same as that i...

Page 4: ...ured at that moment The variables display mode is automatically abandoned after about 15 seconds from the last pressure of the key 5 2 Alarm functions The alarm conditions of the instrument are Probe errors E1 and E1 Temperature alarms Hi and Lo The alarm functions act on the LED the internal buzzer if present and configured by the parameter o bu and the relay output if present The parameter o bu ...

Page 5: ...m may not be present either due to the fact they depend on the type of instrument or be cause they are automatically disabled as unnecessary i Measuring inputs parameters Parameter Description Range Default Note 1 i se Probe type Pt PTC thermistor nt NTC thermistor nt 2 i uP Unit of measurement and resolution decimal point C0 C resolution 1 F0 F resolution 1 C1 C resolution 0 1 F1 F resolution 0 1...

Page 6: ...0 AC frequency 50 60 Hz Power consumption About 4 VA Inputs 1 input for temperature probes NTC 103AT 2 10 kW 25 C or PTC KTY 81 121 990 Ω 25 C Output 1 relay output SPDT or SPST NO 16A AC1 6A AC3 250 VAC 1 HP 250 VAC 1 2HP 125 VAC 12 A max for the common pole of removable terminal block model Relay output electrical life SPST NO 100000 operations SPDT 50000 operations VDE omologation Action type T...

Page 7: ...t Relay SPST NA 16A AC1 resistive load S Out Relay SPDT 16A AC1 resistive load d Terminal block Screw terminals standard E Removable screw terminal block complete N Removable screw terminal block the fixed part only e Display Red B Blue c Buzzer Not present B With Buzzer c a b d e f g h f h Reserved codes ii jj Special codes ii jj g Packaging Bracket type AT package Butterfly brackets std V AT pac...

Page 8: ...Ascon Tecnologic Z31V OPERATING INSTRUCTIONS PAG 8 ...

Reviews: