Ascon Tecnologic - Y39H Line - Operating Instructions - Pag. 6

Through the 

i.dS

 parameter is possible to set the variable 

normally displayed:

Pt

 

Measure of the 

temperature

 Probe;

Ph

 

Measure of the 

humidity

 Probe;

St

 

Set Point of the temperature control;

Sh

 

Set Point of the humidity control;

th

 

The temperature and humidity measures alternated 
every 10 s;

tt

 

The temperature and the 

t.of

 timer decreasing count-

ing alternated every 10 s;

3U

 

The temperature, humidity and the 

t.of

 timer decreas-

ing counting alternated every 10 s;

of

 

Numerical display switched OFF.

The normally displayed value is established by parameter 

i.dS

, but, repeatedly pressing and releasing   key, it is 

possible to sequentially display all the measurement and 
operating variables.  The display alternately shows the code 
that identifies the variable and its value.  The variables that 
can be displayed are:

t

 

Temperature probe measurement;

h

 

Humidity probe measurement;

t.of 

Countdown to the next activation of the auxiliary output 
configured as 

o.Fo

 = 

2

 (only if the timer is enabled);

Lt

 

Minimum stored Pr1 temperature;

Ht

 

Maximum stored Pr1 temperature.

The system exits the variable display mode after 15 s from 
the last   key pressure.

5.3 

Digital Input Configuration

The digital input function is defined using the 

i.Fi

 parameter 

and the action is delayed for the time programmed with pa-
rameter 

i.ti

.  The 

i.Fi

 parameter can be configured for the 

following functions:

Digital Input not active;

External alarm signalling via NO contact: closing the digi-
tal input (and after the 

i.ti

 time) the alarm is activated 

and the instrument alternately shows on the display the 
label 

AL

 and the variable set at parameter 

i.dS

;

External alarm signalling with deactivation of all control 
outputs via NO contact: closing the digital input (and after 
the 

i.ti

 time) all the control outputs are disabled, the alarm 

is activated and the instrument alternately shows on the 
display the label 

AL

 and the variable set at parameter 

i.dS

;

Instrument Switch ON/OFF (ON/Stand-by) of instrument  
via NO contact: closing the digital input (and after the 

i.ti

 

time) the instrument is switched 

ON

 while it is placed in 

Stand-by

 when the digital input is open;

4  AUX

 auxiliary output remote control with NO contact: 

when the input is closed (and after the 

i.ti

 time), the 

auxiliary output is activated as described in the operating 
modes of the auxiliary output;

Door opening signalling via NO contact: when the input 
closes (and after the 

i.ti

 time) the instrument alternately 

displays 

oP

 and the variable established with 

i.dS

.  With this 

operating mode, the action of the digital input also activates 
the time that can be set in parameter 

A.oA

 after which the 

alarm is activated to signal that the door has remained open;

-1

-2

-3

-4

-5

 

These functions are like those just described, but work 
with a reversed logic as the contact is NC.

5.4 

Outputs and Buzzer Configuration

The instrument outputs can be configured by the relative pa-
rameters 

o.o1

 , 

o.o2

 and 

o.o3

.  The outputs can be configured 

for the following functions:

ot

 

To manage the temperature control device.  In the 
case of neutral zone control (

r.HC

 = 

nr

) for the control 

of the cooling control device;

rh

 

To manage the humidity control device.  In the case of 
neutral zone control (

r.ud

 = 

nr

) for the control of the 

dehumidification control device;

HE

 

To manage the heating control device in case of neu-
tral zone control (

r.HC

 = 

nr

);

hu

 

To manage the humidification control device in case of 
neutral zone control (

r.ud

 = 

nr

);

Au

 

To control the auxiliary device;

At

 

To control a silenceable alarm device through a con-
tact that is NA and closed when the alarm sounds;

AL

 

To control an alarm that cannot be silenced through a 
contact that is NA and closed when the alarm sounds;

-t

 

To control a silenceable alarm device through a con-
tact that is NC and open when the alarm sounds;

-L

 

To control an alarm that cannot be silenced through a 
contact that is NC and open when the alarm sounds;

on

 

Output ON when the instrument is in ON state.  The 
output is active when the instrument in ON and not 
active when the instrument is in Stand-by mode.  This 
mode can be used to control shop lights, non-misting 
resistances or other utilities;

L1

 

To manage a light device through the keys  /  or  /

Aux

 when correctly configured (

t.UF

 or 

t.Fb

 = 4).   

This output can be activated and deactivated even 
when the instrument is placed in Stand-by;

of

 

Disabled output.

The function carried by for 

Aux

 output ( 

o.o1

 , 

o.o2

o.o3

 = 

Au

is defined by the parameter 

o.Fo

 and the function is condi-

tioned by the time set with parameters 

o.tn

 and 

o.tf

.

Using the 

o.tu

 parameter is possible to establish whether the 

scale of the 

o.tF

 parameter should be in 

hours and minutes

 

(

H

) or in 

minutes and seconds

 (

n

).

o.Fo

 can be configured for the following functions:

of

 No function;

1. 

Activation by the key  / ,  /

Aux

 or by Digital Input with 

contact NO: the output is activated pressing a key  

/  or  /

Aux

 suitably configured (

t.UF

 or 

t.Fb

 = 

1

) or 

via the digital input (

i.Fi

 = 

4

).  These commands have 

a bi-stable function (toggle), which means that when 
first pressed, the output is activated while the second is 
disabled.  In this mode, the 

Aux

 output can be turned 

OFF automatically after a certain time that can be set ON 
the parameter 

o.tn

.  With 

o.tn

 = 

of

 the output is activated 

and deactivated only manually, using a key  ,  , or via 
the digital input.  When 

o.tn

 = 

time

, once activated the 

output is turned OFF automatically after the 

o.tn

 time;

2. 

Independent twin timer.  The 

Aux

 output is activated 

when the instrument is turned ON for the time 

o.tn

 then 

it is deactivated for the time 

o.tF

 and so on.  The 

o.Fo

 = 

2

 mode also provides a timer enabling/disabling function.  

This function allows the user to manually disable/enable 
the timer by pressing the  /

Tm

 key for 5 s.  The flashing 

Tm

 LED indicates thet the timer is enabled.  If 

o.Fo

 = 

2

the first time the timer is switched ON, it is always enabled 
and can be disabled/re-enabled using the  /

Tm

 key.  

When the instrument is turned OFF and the next time it is 

Summary of Contents for Y39H

Page 1: ...oling application with ON OFF control and humidity control humidification and deumidification with ON OFF control the instrument integrates an asymmetrical oscillator timer whitch can be used for spec...

Page 2: ...lashing 12 LED Stand By When the instrument is in Stand by mode is the only lit LED 13 LED Tm Time When flashes points out that the twin timer which operates on the Auxiliay output is enabled 2 Progra...

Page 3: ...ly entering the password is protected if the SET LED is steady ON the parameter is programmable without password not protected To change the parameter visibility press the key and keep ing it pressed...

Page 4: ...insert the instrument fixing it with the provided special brackets In order to obtain the declared front protection degree IP65 use the screw type bracket optional Avoid placing the instrument in env...

Page 5: ...obe Out2 Out1 Out3 TRH03 5 Functions 5 1 ON STAND BY Function Once powered the instrument can assume 2 different conditions ON The controller uses the control functions STAND BY The controller uses no...

Page 6: ...uration The instrument outputs can be configured by the relative pa rameters o o1 o o2 and o o3 The outputs can be configured for the following functions ot To manage the temperature control device In...

Page 7: ...ith neu tral zone r HC nr When r HC nr the output configured as ot operates with a cooling action like r HC C while the output configured as HE can be used to operate with a heating action The r d dif...

Page 8: ...the actuator motor or water injec tion solenoid valve 5 7 Compressor Protection Function and Delay at Power ON The compressor protection functions performed by the in strument are studied to avoid fre...

Page 9: ...AL A Lt A Ht A dt A dt time off off off ON ON Hit Lot Temp Pt or assume the values SP A Ht and SP A Lt if the alarms are relative A yt 2 AL A Lt SPt A Ht Temp Pt A dt A dt time off off off ON ON Hit L...

Page 10: ...uts are disabled at digital input intervention 5 8 4 Open Door Alarm The instrument can notify an Open door alarm activated by the digital input with the function programmed as i Fi 5 When the digital...

Page 11: ...PC USB Enter PWS 12 V A B C TTL USB to PC USB For additional info please look at the A01 instruction manual 6 2 RS 485 Serial Interface by ARS1 Through the ARS1 device TTL RS485 interface and the ap p...

Page 12: ...th Humidity and Tempearture measurements alterna ted every 10 s tt Tempearture and countdown t of measurements alternated every 10 s 3U Humidity Tempearture and countdown t of mea surements alternated...

Page 13: ...h 0 0 30 0 RH 1 0 43 A th Humidity alarm delay A Hh and A Lh oF 0 01 9 59 min s 99 5 min s x 10 oF 44 A PA Temperature and Hunidity Alarms delay at power ON oF 0 01 9 59 h min 99 5 h min x 10 2 00 45...

Page 14: ...ithout any fees or charge for Ascon Tecnologic except in the event of alterna tive agreements 10 Technical Data 10 1 Electrical Data Power supply 12 VAC DC 12 24 VAC DC 100 240 VAC 10 AC Frequency 50...

Page 15: ...EN61000 4 5 supply 2 kV com mode 1 kV diff mode EN61000 4 6 3 V 11 How to order MODEL Y39H Instrument with mechanical keyboard a POWER SUPPLY H 100 240 VAC G 12 24 VAC VDC F 12 VAC VDC b OUT1 OUTPUT...

Page 16: ...Ascon Tecnologic Y39H Line Operating Instructions Pag 16...

Reviews: