background image

Ascon Tecnologic - Y39 Line - Operating Instructions - Pag. 8

Third control (parameter 

P.P3

) inhibits the activation of the 

ot

 

output by a time delay (

P.P3

) that starts when the output was 

turned ON last time (delay between switching-ONs).

SP

Out

ot

off

off

off

ON

ON

ON

time

P.P3

P.P3

P.P3

r.d

Pr1

Temp. 

During the output inhibition the LED 

OUT

 (Cool

 

 or Heat

 

blinks.  It is also possible to prevent activation of all the outputs 
after the instrument is turned ON, for the time set with param-
eter 

P.od

.

During the power ON delay phase, the display shows the 
indication 

od

 alternated with the normal visualization.

All these functions are disabled if the relative parameters are 
set to 

OFF

 (

oF

).

5.8 

Defrost Control

The defrost control acts on the outputs configured as 

ot

 and 

dF

.

The type of defrost that the instrument must carry out is set 
with parameter 

d.dt

 that can be programmed as:

EL

 With 

electrical heating

 (or by 

stopping compres-

sor

): during defrost, the output 

ot

 is deactivated while 

the output 

dF

 is enabled.  The defrost will be made by 

Stopping compressor when 

dF

 output is not used;

in

 With 

hot gas

 or 

inversion of cycle

: during defrost the 

outputs 

ot

 and 

dF

 are enabled;

no

 

Without compressor output conditioning

: during 

defrost, the output 

ot

 continues operating in order to 

control the temperature while 

df

 output is enabled.

Et

 

With 

electrical heating

 and 

defrost temperature 

control

: during defrost, the 

ot

 output is deactive while 

df

 

output operates as evaporator temperature control.

With this selection, the defrost end is always timed (time 

d.dE

).  

During defrost 

dF

 output behaves as an heating action tem-

perature control with Set Point = 

d.tE

, fixed differential at 1°C 

and operates using as reference the reading of the evaporator 
temperature probe (

EP

).

5.8.1  Automatic Defrosts Start

The automatic control of defrost occours by interval times.
The automatic defrost is therefore obtained by setting, with 

d.di

 parameter, the time that must elapse between the end 

of a defrost and the beginning of the next one.
The first defrost after Power ON can be set with parameter 

d.Sd

.  This allows to perform the first defrost at a different 

interval from 

d.di

 time.

To force the instrument to perform a defrost cycle at each 
power ON (as long as the conditions set with parameters 

d.tS

 and 

d.tE

 are satisfied) set parameter 

d.Sd

 = 

oF

.

This allows the evaporator to be permanently defrosted, 
even when frequent power supply interruptions occur that 
may stop several defrost cycles.
If, on the other hand, all defrosts must be executed at the 
same interval time, set 

d.Sd

 = 

d.di

.

Setting 

d.di

 = 

oF

 interval defrosts are disabled (including 

the first one, regardless of the time set at 

d.Sd

 parameter).

Counting mode interval and automatic defrost start modes 
are set with parameter 

d.dC

:

rt

 

At real-time power-ON intervals.  

d.di

 interval is count-

ed referring to the total time the instrument is switched 

ON.  Mode currently used in the refrigerators systems.

ct

 

At time intervals of the compressor operation (output 

ot

 switched ON).  Mode typically used in the posi-

tive temperature refrigerators systems with defrost by 
stopping compressor.

cS

 

Defrost cycle at each compressor stop (i.e. at each 
deactivation of the output 

ot

) or however at defrost 

interval end with counts the total working time (instru-
ment ON).  If 

d.di

 = 

oF

 the defrost happens only at 

compressor stops.  This mode is used only on particu-
lar refrigerator systems in which is needed to have the 
evaporator at the maximum efficiency conditions at all 
compressor cycles.

St

 

Defrost due to evaporator temperature.  The instru-
ment starts a defrost cycle when the temperature 
evaporator (

EP

 probe) goes below the 

d.tS

 pro-

grammed temperature or however at defrost interval 
end as for the 

rt

 mode (instrument 

ON

).  If 

d.di

 = 

oF

 

the defrost happens only when the evaporator tem-
perature goes below the one set at 

d.tS

.  This metod 

can be used in heat pump defrost systems (in this 
case the defrost intervals are usually disabled) or to 
guarantee a defrost if the evaporator reaches very 
low temperatures that normally result symptomatic of 
a bad thermal exchange in comparison to the normal 
working conditions.

dd

 

Dynamic defrost intervals system.  This mode allows 
to dynamically reduce the defrost interval counting in 
progress (

d.di

 or 

d.Sd

 if it is the first defrost), anticipat-

ing the execution of a defrost when necessary, follow-
ing an algorithm that allows to notice a performance 
decreasing of refrigerator thermal exchange.  Besides 
it maintains active the mode 

St

 that allows a further 

control of the defrost in order to notice a performance 
decreasing of refrigerator thermal exchange.
The algorithm allows to esteem a reduction of thermal 
exchange in base to the increase of the difference of 
temperature between 

Pr1

 (controlled temperature) 

and evaporator (

EP

 probe) that is stored by the instru-

ment in proximity of the Set Point.
The advantage of the “

Dynamic Defrost Interval

” is the 

possibility to program a defrost interval time longer 
than normal.  The instrument has the possibility to 
anticipate the defrost when necessary or to start the 
cycle after the programmed time.
If the 

DDI

 is correctly set many un-necessary defrost cy-

cles can be avoided (obtaining an energy saving) which 
instead can happen, in the normal operation when, to 
guarantee with greater certainty the system efficiency, 
the defrost interval is programmed at a too low time.

Phase

off

off

ON

ON

0

1

2

3

Temp.

time

d.di/d.Sd

time to defrost Phases 0, 1

Defrost

ON

ON

off

off

DT0

d.tE

d.tS

Cool

(ot)

dF

SP 

+ r.d

SP

PR1

r.d

EP

DT1

DT2

DT3

time to defrost Phase 2

time to defrost Phase 3

Summary of Contents for Y39

Page 1: ...rature probes and a digital input alterna tive to a temperature input in addition can be equipped with an internal buzzer that is the sound system for alarms The 3 outputs can be can all be configured for controlling the compressor or the temperature control device the defrosting device the evaporation fan or alternatively any of the previ ous functions using an auxiliary device or an alarm The 3 ...

Page 2: ...atus ON ON OFF OFF or inhibited flashing 12 LED Stand By When the instrument is in Stand by mode is the only lit LED 2 PROGRAMMING 2 1 Fast Set Point Programming The normal mode to program the setpoint is done by mo mentarily pressing the key the display shows SP or SP2 alternated to the programmed value To change it press the key to increase the value or to decrease it These keys increase or decr...

Page 3: ...e protected parameters Previous Parameter Next Parameter SET PARAMETER Increase Value Decrease Value 35 0 25 5 NOT Protected PARAMETERS NORMAL MODE Hold for 2 s Hold for 5 s PARAMETERS PROGRAM MODE INS CORRECT PASSWORD Increase Value Decrease Value 0 R P PASSWORD REQUEST S LS a HA 2 5 Reset Parameters to Default Value The instrument allows the reset of the parameters to those values programmed in ...

Page 4: ...er must ensure that EMC rules are respected also after instrument installation if necessary using proper filters 4 INSTALLATION WARNINGS 4 1 Mechanical Mounting The instrument in case 78 x 35 mm is designed for flush in panel mounting Make a hole 71 x 29 mm and insert the instrument fixing it with the provided special brackets In order to obtain the declared front protection degree use the screw t...

Page 5: ...nction and the display is turned OFF except for the Stand by LED The transition between Standby and ON status is equivalent to power ON the instrument providing the electrical power In case of power failure the system always sets itself in the condition it was in before the black out The ON Stand by function can be selected Pressing the key for at least 1 s if t UF 4 Pressing the key Aux for at le...

Page 6: ...after the i ti time all the control outputs are disabled the alarm is activated and the instrument alternately shows ON the display the label AL and the variable set at para meter i dS 10 Instrument Switch ON OFF ON Stand by of instrument via NO contact closing the digital input and after the i ti time the instrument is switched ON while it is placed in Stand by when the digital input is open 11 A...

Page 7: ...OUT ot off off ON ON ON time Pr1 Temp Pr1 In the event of probe error it is possible to set the instrument so that the output continues working in cycles according to the times programmed with parameters r t1 activation time and r t2 deactivation time If a probe error occurs the instrument activates the output for the r t1 time then deactivates it for the r t2 time and so on whilst the error remai...

Page 8: ...nterval and automatic defrost start modes are set with parameter d dC rt At real time power ON intervals d di interval is count ed referring to the total time the instrument is switched ON Mode currently used in the refrigerators systems ct At time intervals of the compressor operation output ot switched ON Mode typically used in the posi tive temperature refrigerators systems with defrost by stop...

Page 9: ... A ends because the d tE temperature has been reached defrost B ends when d dE time has elapsed as temperature d tE has NOT been reached defrost C does not take place as the evaporator temperature is higher than d tS d tE d ts dF off off off off d di dSd ON ON ON time d di Defrost d de 1 Temp EP Example of electric defrost with evaporator temperature control The defrost ends when d dE time has ela...

Page 10: ...ion similar to AL but with inverse logic function output active in normal conditions disabled in alarm n Function is similar to An but with inverse logic function output active in normal conditions disabled in alarm The instrument is equipped with the alarm memory function which can be activated via the A tA parameter A tA values are oF The instrument disables the alarm signal when the alarm statu...

Page 11: ...t is possible to enable disable the auxiliary output if configured as o Fo 2 2 Pressing the key for at least 1 s it is possible to enable disable a continuous cycle 3 Pressing the key for at least 1 s it is possible to select one of the 2 stored Set Point in rotation Once the selection has been made the display shows flashing the active Set Point code for about 1 s SP SP2 4 Pressing the key for at...

Page 12: ...upplied by the instrument Supply TLCNV Cable 7 8 9 6 5 4 ON TX RX TTL TLCNV B GND A RS 485 3 2 1 For additional info please consult the TLCNV instruction manual 7 PROGRAMMABLE PARAMETERS TABLE Here below is a description of all the parameters available on the instrument Some of them may not be present because depend on the model type of instrument S Set Point parameters Parameter Description Range...

Page 13: ...essor output conditioning Et Electrical heating with evaporator temperature control EL 24 d di Defrosting interval oF 0 01 9 59 h min 99 5 h min x 10 6 00 25 d Sd 1st defrost delay at power oF Defrost at power on 0 01 9 59 h min 99 5 h min x 10 6 00 26 d dE Length max of defrost cycle oF 0 01 9 59 min s 99 5 min s x 10 20 0 27 d tE Defrost stop temperature 99 9 999 C F 8 0 28 d tS Defrost enable t...

Page 14: ... and continuous cycle and unlock display delay after defrost oF 0 01 9 59 h min 99 5 h min x 10 1 00 52 A oA Alarm delay with door open oF 0 01 9 59 min s 99 5 min s x 10 3 00 o Outputs and buzzer configuration parameters Parameter Description Range Default 53 o o1 OUT1 function oF No function ot Temp Control compressor dF Defrosting Fn Fan Au Auxiliary At Silenceable alarm AL Not silenceable Alar...

Page 15: ...be shipped to Ascon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of alterna tive agreements 10 TECHNICAL DATA 10 1 Electrical Data Power supply 12 VAC DC 12 24 VAC DC 100 240 VAC 10 AC Frequency 50 60 Hz Power consumption 4 VA approx Input s 3 inputs for temperature probes PTC KTY 81 121 990W 25 C or NTC 103AT 2 10kW...

Page 16: ...e 2006 95 CE EN 60730 1 EN 60730 2 9 Regulation 37 2005 CE EN13485 air S A 2 50 C 90 C with probe NTC 103AT11 11 HOW TO ORDER MODEL Y39 Instrument with mechanical keyboard Y39S Instrument with Sensitive Touch keyboard a POWER SUPPLY H 100 240 VAC G 12 24 VAC VDC F 12 VAC VDC b OUT1 OUTPUT R Out1 Relay SPST NO 16A for resistive loads d OUT3 OUTPUT R Out3 Relay SPST NO 5A for resistive loads Not pre...

Reviews: