3.3 

Connections

General notes on electrical connections

•  The probe cables must be kept separated from high 

power voltage wiring;

•  If shielded cables are used, the protection shield must be 

connected to ground at one side only.

3.3.1 

Electrical wiring

Colour

Connection

Red

Power supply - Positive pole

Green

Power supply - Negative pole

Yellow

Terminal A+ RS485

Blue

Terminal B- RS485

3.4 

Communication protocol

The product uses the standard RS485 MODBUS-RTU proto-
col format, all operating and response commands are made 
up of hexadecimal data.
When the sensor is shipped, the RS485 communication set-
tings are:

•  Modbus Address: 1;
•  Baud rate: 9600
•  Data bits: 8;
•  Parity: n (no parity);
•  Bit di stop: 1.

3.4.1 

Variables Map

Address

Descrizione

no. of 

decimals

R/W

Dec. Hex.

0

00 Measured Temperature

2

R

1

01 Measured Humidity

2

R

102

066 Modbus Address

0

R/W

103

067

Baud rate
1 2400
2 4800
3 9600
4 19200
5 38400
6 115200

0

R/W

107 06B Temperature offset (-10 ÷ +10)

2

R/W

108 06C Humidity offset (-10 ÷ +10)

2

R/W

4.  PROBLEMS AND MAINTENANCE

4.1 

Cleaning

We recommend to clean the instrument with a slightly wet 
cloth using water and not abrasive cleaners or solvents only.
Should it be necessary to remove the sensor, avoid to me-
chanical stress it and in particular avoid touching the humid-
ity sensor.

4.2 

Disposal

The appliance (or the product) must be 
disposed of separately in compliance 
with the local standards in force on 
waste disposal.

5.  WARRANTY AND REPAIRS

The instrument is under warranty against manufacturing 
flaws or faulty material, that are found within 18 months from 
delivery date.  The warranty is limited to repairs or to the 
replacement of the instrument.
The eventual opening of the housing, the violation of the instru-
ment or the improper use and installation of the product will 
bring about the immediate withdrawal of the warranty effects.
In the event of a faulty instrument, either within the period of 
warranty, or further to its expiry, please contact our sales de-
partment to obtain authorisation for sending the instrument 
to our company.
The faulty product must be shipped to Ascon Tecnologic with 
a detailed description of the faults found, without any fees or 
charge for Ascon Tecnologic, except in the event of alterna-
tive agreements.

6.  TEHNICAL DATA

6.1 

Technical characteristics

Temperature range:

 -30 ÷ 80°C;

Temperature accuracy:

 ±0.5°C @ 25°C;

Humidity range:

 0 ÷ 100% RH;

Humidity accuracy:

 ±3% RH @ 25°C;

Communication interface:

 RS 485;

Default data format:

 9600, 8, n, 1;

Power supply:

 6 ÷ 24 VDC;

Operating temperature

 -40 ÷ 80°C;

Operating Humidity

 5 ÷ 90% RH;

Standard connection cable length:

 1 m.