2.3 - ELECTRICAL CONNECTIONS 

To access the terminal block remove the cover by unscrewing the 
two screws on it. 
Avoid touching any electronic components and carry out the 
electrical wiring connecting one wire only for each terminal, 
according to the following diagrams, checking that the power supply 
is the same as indicated on the instrument. 
Use the cable gland to make the cable exit and check the correct 
grip of the same and of the cover box 

 

to obtain the declared 

protection degree. 
Check then if the measure instrument is equipped with a voltage 
output 9... 30 VDC able to supply at least 20 mA, otherwise 
connecting the probe with an external voltage supply 9... 30 VDC 
able to supply the necessary current as previously described and 
connecting it following the wiring diagrams. 
It's strongly recommended to use cables with proper insulation, 
according to the working voltages and  temperatures.  
Furthermore, the cable of the probe has to be kept separate from line 
voltage wiring in order to avoid electromagnetic noises infiltration.  
If the input cable of the probe is screened, it advisable to connect it 
on the ground with one side only.  

Ascon Tecnologic S.r.l.

 

and its legal representatives are not 

responsible for any eventual damages to people, things or animals 
deriving from the instrument violation, not proper or wrong use or 
in any case not in accordance with the instrument features. 
 
2.4 - ELECTRICAL CONNECTION DRAWING 

 

Wiring diagram with instrument supply :

 

 

Wiring diagram with external supply :

 

 

 

3 - OPERATING MODE

 

 
The instrument to which the probe has to be connected has to be 
provided with a current input 4... 20 mA type.  
To have a correct measure indication is necessary to set the lower 
and upper input limits.  
These limits are the corresponding value to 4 mA (lower limit or 
beginning of scale) and 20 mA (upper limit or ending of scale) which 
have to be displayed.  
See on the operating instructions of the measure instrument the 
setting mode of these limits. 

The set values for TRH 11 probe are:

 

Lower limit (4 mA): 0 
Upper limit (20 mA): 100 
 

4 - PROBLEMS, MAINTENANCE AND WARRANTY

 

 
4.1 - MEASURE ERRORS

 

Reading errors can occur if settling time is too short, or be caused by 
steam, sprayed water, air drafts, direct exposure to sunlight, or 
presence of condensate on the sensor. 
To obtain accurate measurements the sensor should be left to settle 
in the existing atmosphere for some time.  
To reduced the possibility of condensation on the humidity sensor 
place the probe in ventilated position and where there is not a quick 
and elevation variation of temperature (from cold to warm) 

 
4.2 - CLEANING

 

It is recommended to clean the box only with a cloth welted with 
water or with a detergent neither abrasive nor containing solvents. 
Should be necessary to remove the protective cap, do not cause any 
mechanical stress to the sensors and absolutely avoid touching the 
humidity sensor. 

 
4.3 - WARRANTY AND REPAIRS 

The instrument is under warranty against construction vices or defected 
material, noticed within 12 months from delivery date.  The warranty is 
limited to the repairs or to the substitution of the instrument. 
The eventual violation of the instrument or the wrong use and 
installation of the product means the automatic decay of the warranty. 
In case of defected instrument, noticed in warranty period or out of 
warranty, do contact our sales department to obtain the shipment 
authorisation. 
The defected product must be shipped to Ascon Tecnologic with the 
detailed description of the failures found  and without any fees or 
charge for Ascon Tecnologic, safe different agreements. 
 

5 - TECHNICAL DATA

 

 

5.1 - ELECTRICAL DATA

 

Power supply: 9... 30 VDC 
Power consumption: 20 mA max. 
Humidity sensor type: Capacitive 
External load: 250 

Ω

 max. 

Output signal : 4...20 mA (0... 100%RH) 
Protection class against electric shock: Class III 
 

5.2 - MECHANICAL DATA

 

Housing: plastic 
Dimensions: 80 x 80 mm, depth 52 mm 
Weight: 125 g approx. 
Mounting: Wall mounting  
Connections: 2.5 mm

screw terminal block 

Recommended connection cable: 2 x 0.75 or 2x1 mm

2

 

Box protection : IP 65 
Air filter: Polyethylene 
Operating temperature: -30... 70 °C 
Operating humidity: 0... 100 RH% 
Storage temperature: -30... 80 °C 
Maximum workplace pollutant concentration: 

Acetone (CH3COCH3) 

1000 ppm 

2400 mg/m

3

Ammonia (NH3) 

25 ppm 

18 mg/m

3

 

Petrol 

300 ppm 

1200 mg/m

3

Chlorine (Cl2) 

1 ppm 

1.5 mg/m

3

 

Acetic Acid (CH3COOH) 

10 ppm 

25 mg/m

3

 

Ethyl Acetate (CH3COOC2H5) 

400 ppm 

1400 mg/m

3

Ethanol (C2H5OH) 

1000 ppm 

1900 mg/m

3

Ethylene Glycol (HOCH2CH2OH) 

100 ppm 

260 mg/m

3

 

Formaldehyde (HCHO) 

1 ppm 

1.2 mg/m

3

 

Isopropanol ((CH3)2CHOH) 

400 ppm 

980 mg/m

3

 

2-Butanone (C2H5COCH3) 

200 ppm 

590 mg/m

3

 

Hydrochloric Acid (HCl) 

5 ppm 

7 mg/m

3

 

Sulphur Dioxide (SO2) 

5 ppm 

13 mg/m

3

 

Hydrogen Sulphide (H2S) 

10 ppm 

15 mg/m

3

 

Nitrogen Oxides (NOx) 

5 ppm 

9 mg/m

3

 

Toluene/Xylene (C6H5CH3) 

100 ppm 

380 mg/m

3

 

Ascon Tecnologic - TRH 11

 

- OPERATING INSTRUCTIONS - Vr. 02 - PAG. 2

 