ASCON TECNOLOGIC - TLK33 - OPERATING INSTRUCTIONS - 

PAG. 2

E

 : Thermistors PTC and NTC, Thermocouples temperature probes 

(J,K,S and ZIS Infrared sensors), mV signals (0..50/60 mV, 12..60 
mV),. 

I

 : normalized analogue signals 0/4..20 mA 

V

 : normalized analogue signals 0..1 V, 0/1..5 V, 0/2..10 V 

Other important available functions are: reaching of the Set Point at 
controlled  speed,  ramps and dwell function, parameters protection 
on different levels, configuration of parameters via the A01 device. 

1.2

 - 

FRONT PANEL DESCRIPTION

1  -  Key  P

  :  This  is  used  to  access  the  programming  parameters 

and to confirm selection. 

2 - Key DOWN

 : This is used to decrease the values to be set and 

to select the parameters. If the key is held down, the user returns to 
the  previous  programming  level  until  he  exits  the  programming 
mode.   

3 - Key UP

  :  This  is  used  to  increase  the  values  to  be  set  and  to 

select  the  parameters.  If  the  key  is held down, the user returns to 
the  previous  programming  level  until  he  exits  the  programming 
mode.  Outside  the  programming  mode  it  permits  visualisation  of 
the output control power.  

4  -  Key  U

  :  This  is  a  key  with  a  function  programmable  by  par. 

“USrb”.  It  can  be  set  to  :  Activate  Auto-tuning  and  Self-tuning 
functions, swap the instrument to manual control, silence the alarm, 
change the active Set Point, deactivate control.  

5 - Led Heat 

: indicates the HEAT mode

 

6 - Led Cool 

: indicates the COOL mode 

7 - Led AL1 

: indicates the state of output AL1 

8 - Led AL2 

: indicates the state of output AL2 

9 - Led AT/ST 

:  indicates that the Self-tuning function is activated 

(light on) or that Auto-tuning (flashing ) is in progress.

 

10  -  Led  SET 

:  when  flashing,  it  indicates  access  to  the 

programming mode.

 

11  -  Led  –  Shift  index: 

indicates  that  the  process  value  is  lower 

than the one programmed on par. “AdE”. 

12  -  Led  =  Shift  index:

  indicates  that  the  process  value  is  within 

the range [SP+AdE ... SP-AdE] 

13 - Led + Shift index:

  indicates  that  the  process value is higher 

than the one set on par. “AdE”. 

2 -  PROGRAMMING 

2.1 - FAST PROGRAMMING OF THE SET POINT

 

This  procedure  permits  rapid  programming  of  the  active  Set  Point 
and possibly the alarm thresholds (see par 2.3) 
Push key “P”, then release it and the display will visualise 

“SP n”

 

(where  n  is  the  number  of  the  Set  Point  active  at  that  moment) 
alternatively to the programmed value. 
To  modify  the  value, press “UP” key to increase it or the “DOWN” 
key to decrease it. 
These  keys  change  the  value  one  digit  at  a  time  but  if  they  are 
pressed  for  more  than  one  second,  the  value  increases  or 
decreases rapidly and, after two seconds in the same condition, the 
changing speed increases in order to allow the desired value to be 
reached rapidly. 
Once  the  desired  value  has  been  reached,  by  pushing  key  P  it  is 
possible  to  exit  by  the  fast  programming  mode  or  it  is  possible  to 
visualise the alarm thresholds (see par. 2.3). 
To  exit  the  fast  Set  programming  it  is  necessary  to  push  key  P, 
after the visualisation of the last Set Point, or alternatively, if no key 

is pressed for approx. 15 seconds, the display will return to normal 
functioning automatically.

 

2.2 - SELECTION OF THE CONTROL STATE AND PARAMETER 
PROGRAMMING

 

By  pushing  key  "P"  and  holding  it  down  for  approx.  2  sec.  it  is 
possible to enter into the main selection menu. 
Using the "UP" or DOWN” keys, it is then possible to roll over the 
selections: 

"OPEr"

 

 to enter into the operating parameters menu 

"ConF"

 

 to enter into the configuration parameters menu 

"OFF"

 

 to swap the regulator into the OFF state 

"rEG"

 

 to  swap  the  regulator  into  the  automatic  control 
state 

"tunE"

 

 to activate the  Auto-tuning or Self-tuning function 

"OPLO"

 

 to  swap  the  regulator  to  the  manual  control  state 
and  therefore  to  program  the % control value using 
the “UP” and “DOWN” keys 

Once the desired item has been selected, push key “P” to confirm. 
Selecting  "OPEr"  and  "ConF"  gives  the  possibility  of  accessing 
other menus containing additional parameters and more precisely : 

"OPEr"  -

  Operating  parameters  Menu:  this  normally  contains  the 

Set Point parameters but it can contain all the desired parameters 
(see par. 2.3). 

"ConF"  -

  Configuration  parameters  Menu:  this  contains  all  the 

operating parameters and the functioning configuration parameters 
(alarm configuration, control, input, etc.) 

S E LF T U N IN G

A U T O T U N IN G

A T
S T

2 sec.

H old for

"O F F "

"rE G "

"O P LO "

To enter the menu 

“ConF”

 select the option “ConF”, press the key 

“P” and the display will show “0”. 
At  this  request,  enter,  using  keys  “UP”  and  “DOWN”,  the  number 
reported on the last page of this manual and push key “P”. 
If  an  incorrect  password  is  entered,  the  instrument  exit  from 
programming mode. 
If  the  password  is  correct,  the  display  will  visualise  the  code 
identifying the first group of parameters (“ 

]

SP 

“) and with keys “UP”

and  “DOWN”  it  will  be  possible  to  select  the  desired  group  of 
parameters. 
Once the desired group of parameters has been selected, the code 
identifying  the  first  parameter  of  the  selected  group  will  be 
visualised by pushing the “P” key. 
Again using the “UP” and “DOWN” keys, it is possible to select the 
desired  parameter  and,  if  the  key  “P”  is  pressed,  the  display  will 

AT

9

ST

TLK33

4

U

3

-20.5.

2

P

1

Heat Cool

AL1 AL2

10

5

6 11 12 13

7 8

Summary of Contents for TLK 33

Page 1: ...PUTS 4 8 RS 485 SERIAL INTERFACE 4 9 PARAMETERS CONFIGURATION BY A01 5 PROGRAMMABLE PARAMETERS TABLE 6 PROBLEMS MAINTENANCE AND GUARANTEE 6 1 ERROR SIGNALLING 6 2 CLEANING 6 3 GUARANTEE AND REPAIRS 7...

Page 2: ...an one second the value increases or decreases rapidly and after two seconds in the same condition the changing speed increases in order to allow the desired value to be reached rapidly Once the desir...

Page 3: ...electing the desired state from the main selection menu suing the keyboard By using the key U on the keyboard suitably programming par USrb USrb tunE USrb OPLO USrb OFF it is possible to pass from rEG...

Page 4: ...upply for each instrument as there is no isolation between the power supply and input We recommend that a check should be made that the parameters are those desired and that the application functions...

Page 5: ...is possible to obtain a heating effect polarizing in one direction and a cooling effect when polarizing in the other direction The Double Action PID control works on the output depending on the active...

Page 6: ...Point SP2 after a set time thus obtaining a simple automatic process cycle These functions are available for all the programmable controls PID single and double action ON OFF and Neutral Zone ON OFF...

Page 7: ...onditions and then back in alarm conditions P V 1 0 t i m e A L 1 O N O N O N o f f o f f o f f o f f A b 1 exemple with absolute low alarm ALARM DELAY the alarm output may behave in two different way...

Page 8: ...485 GND B HOST PC PLC 120 ohm Rt 10 8 9 10 8 9 If the instrument is equipped with a serial interface the parameters to be programmed are the following all present in the parameters group SEr Add Addre...

Page 9: ...9 9999 0 16 rot Rotation of the measuring straight line 0 000 2 000 1 000 17 InE OPE functioning in case of measuring error Our Or Ur OUr 18 OPE Output power in case of measuring error 100 100 0 19 dI...

Page 10: ...the correct functioning of the probe uuuu The measured variable is under the probe s limits under range oooo The measured variable is over the probe s limits over range ErAt Auto tuning not possible b...

Page 11: ...34 MAX 12 mm 7 4 FUNCTIONAL FEATURES Control PID double action Measurement range according to the used probe see range table Display resolution according to the probe used 1 0 1 0 01 0 001 Overall acc...

Page 12: ...a b c d e f g hh i a POWER SUPPLY G 12 24 VDC b INPUT D thermoresistances Pt100 thermocouples J K S I R mV E thermistors PTC NTC thermocouples J K S I R mV I normalized signals 0 4 20 mA V normalized...