background image

P.A.: The access procedure for “hidden” parameters allows the
“PP” parameter to be checked and changed, and is useful therefore
if the password set  has been forgotten.

2.5 - ACTIVE SET POINT SELECTION

The instrument allows up to 4 different regulation Set points to be
pre-set (

“SP”

“S2”

,

 “S3”

,

 “S4”

) and then to choose which one to

make active.
This function can be used if it is necessary to switch different
function temperatures (e.g. day and night or positive and negative
etc). 
The active set point can be selected:
- Using the parameter “SA”
- using the key U if the parameter "UF" = 3.
- Using the key DOWN/AUX if the parameter "Fb" = 3.
- Using the digital input 1 if the parameter. “FI” = 8 or 14 or the
digital input 2 if the parameter “FI” = 12 or 13 (between “SP” and
“S2”).
- Using the digital inputs 1and 2 if the parameter. “FI” = 11
(between “SP”, “S2”, “S3” and “S4”).
The Set points can be set with a value between the programmed
value in parameter.

 “LS”

  and the programmed value in parameter

“HS”.

Note:

 in the examples that follow, the Set point is generally

indicated as "SP", how when operating the instrument will work
according to the Set point selected as active.

2.6 - ON / STAND-BY

 

FUNCTION

The instrument, once powered up, can assume 2 different
conditions:
- ON : means that the controller uses the control functions.
- STAND-BY : means that the controller does not use any control
function and the display is turned off except for the  Stand-by led.
If there is no power, and then power returns, the system always
sets itself in the condition it was in before the  black-out.
The ON/Stand-by function can be selected: 
- Using the key U if the parameter "UF" = 4.
- Using the key DOWN/AUX if the parameter "Fb" = 4.
- using the digital input if the parameter  “FI” = 10

2.7 - KEYBOARD LOCK FUNCTION

On the instrument  it’s possibile to lock completely the keyboard. 
This function is particularly useful when the regulator is reachable
by the users and it’s desired to avoid any modification.
To activate the keyboard lock it’s enough program the par. 

“Lo”

 to

a different value to oF. 
The value program to this parameter it is the time of inactivity of the
keys afterwhich the keyboard will be locked.
Insofar not pressing  any key for the time "Lo" the instrument
automatically disable the normal functions of the keys.
When the keyboard is lock, if any of the key is pushed, on the
display will appear  

“Ln” 

to indicate the active lock.

To unlock the keyboard it’s enough to contemporarily push  key P
and UP and keep them pushed for 5 sec., afterwhich the label 

“LF”

will appear on the display and all the keys functions will be availab-
le again .

3 - INFORMATION ON INSTALLATION AND USE

3.1 - PERMITTED USE

The instrument has been projected and
manufactured as a measuring and control device to
be used according to EN60730-1 for the altitudes
operation until 2000 ms.

 

The use of the instrument

for applications not expressly permitted by the

above mentioned rule must adopt all the necessary protective
measures. The instrument CANNOT be used in dangerous
environments (flammable or explosive) without adequate
protection. The installer must ensure that EMC rules are respected,
also after the instrument installation, if necessary using proper
filters. Whenever a failure or a malfunction of the device may cause
dangerous situations for persons, thing or animals, please

remember that the plant has to be equipped with additional devices
which will guarantee safety.

3.2 - MECHANICAL MOUNTING

The instrument TLB55, in case 135 x 97 mm, is designed for
flush-in panel mounting. Make a hole 124 x 85 mm and insert the
instrument, fixing it with the provided special brackets. 
We recommend that the gasket is mounted in order to obtain the
front protection degree as declared. The BSL unit is designed for
mounting inside enclosure by 2 screws. Avoid placing the BSL unit
and internal side of TLB55 in environments with very high humidity
levels or dirt that may create condensation or introduction of
conductive substances into the instrument. Ensure adequate
ventilation to the instruments and avoid installation in containers
that house devices which may overheat or which may cause the
instrument to function at a higher temperature than the one
permitted and declared.  Connect the instruments as far away as
possible from sources of electromagnetic disturbances such as
motors, power relays, relays, solenoid valves, etc.

3.3 - ELECTRICAL CONNECTION

Carry out the electrical wiring by connecting only one wire to each
terminal, according to the following diagram, checking that the
power supply is the same as that indicated on the instrument and
that the load current absorption is no higher than the maximum
electricity current permitted. As the instrument is built-in equipment
with permanent connection inside housing, it is not equipped with
either switches or internal devices to protect against overload of
current: the installation will include an overload protection and a
two-phase circuit-breaker, placed as near as possible to the
instrument, and located in a position that can easily be reached by
the user and marked as instrument disconnecting device which
interrupts the power supply to the equipment. It is also
recommended that the supply of all the electrical circuits connected
to the instrument must be protect properly, using devices (ex.
fuses) proportionate to the circulating currents. It is strongly
recommended that cables with proper insulation, according to the
working voltages and  temperatures, be used. Furthermore, the
input cable of the probe has to be kept separate from line voltage
wiring. If the input cable of the probe is screened, it has to be
connected to the ground with only one side. We recommend that a
check should be made that the parameters are those desired and
that the application functions correctly before connecting the
outputs to the actuators so as to avoid malfunctioning that may
cause irregularities in the plant that could cause damage to people,
things or animals.

3.4 - ELECTRICAL WIRING DIAGRAM

CONNECTOR

SLAVE

TLB55

Out2

C

Out3

100..240 VAC

SUPPLY

1

4

Out1

2

5

3

6

BSLB4

Pin 1 (com.)

TLBCA

CABLE

Out4

EN

6 (4) A

4 (4) A

1 (1) A

Out2:

Out3,4:

Out1:

10 A Res.

2 A Gen.Use

30 LRA

UL

12 A Res.

10E5 cycles, 0 T 60 °C

(SELV, Limited Energy)

12A MAX.

5 FLA

60730

Dig2

Dig1

Pr2

Pr1

8

7

10

9

13

11 12

ASCON TECNOLOGIC - TLB55

 

- OPERATING INSTRUCTIONS - Vr. 04 - 02/12 - ISTR-MTLB55ENG04 - PAG. 3

Summary of Contents for TLB 55

Page 1: ...NS 4 9 EVAPORATOR FANS CONTROL 4 8 MANUAL DEFROST 4 7 DEFROST CONTROL 4 6 COMPRESSOR PROTECTION FUNCTION AND DELAY AT POWER ON 4 5 CONTINUOUS CYCLE FUNCTION 4 4 TEMPERATURE CONTROL 4 3 OUTPUTS CONFIGU...

Page 2: ...been selected press the P and the code that identifies the first parameter in the selected group will be visualised Again using the UP and DOWN keys the desired parameter can be selected and pressing...

Page 3: ...rules are respected also after the instrument installation if necessary using proper filters Whenever a failure or a malfunction of the device may cause dangerous situations for persons thing or anima...

Page 4: ...a contact that is normally closed and open when the alarm sounds An to control an alarm with a memory function through a contact that is normally closed and open when the alarm sounds see alarm memor...

Page 5: ...n cycle is set by the parameter dE If instead the evaporator probe is used parameter EP on the defrosting takes place when the temperature measured by the probe exceeds the temperature set in the para...

Page 6: ...output to be activated in alarm status and that they remain activated even when the alarm has ceased see par 4 9 5 Disablement recognition of memorised alarm can only be carried out manually by press...

Page 7: ...is active see selecting active set point 9 Signalling of external alarm with disablement of all the control outputs with contact normally open on closing the digital input 1 and after the ti time all...

Page 8: ...ters available on the instrument Some of them may not be present because depend on the model type of instrument Gruppo SP parametri relativi al Set Point 99 LS 99 Maximum Set Point HS 7 50 58 HS Minim...

Page 9: ...rature alarms Type Ab Absolute dE Relative to Set Ay 46 Note Def Range Description Par 3 oF 99 min Alarm delay with open door oA 54 oF oF 99 hrs Temperature alarms delay after continuous cycle cA 53 6...

Page 10: ...t be shipped to ASCONTECNOLOGIC with a detailed description of the faults found without any fees or charge for ASCONTECNOLOGIC except in the event of alternative agreements 7 TECHNICAL DATA 7 1 ELECTR...

Page 11: ...2 9 Approvals ENEC Lic n 00161 C UL file n E212227 7 5 INSTRUMENT ORDERING CODE DISPLAY AND CONTROL UNIT TLB55 standard instrument TLB55S instrument with Sensitive Touch keyboard a b c d e f g h ii jj...

Reviews: