AC
3
- Installation Manual
24
3-6
Analogue Output Connections
(connectors X9 and X10)
3-6-1
AO1... AO4 Current Analogue Output Connections
• Respect the polarity shown;
• Type: 0/4... 20 mA;
• Load: < 500
Ω
;
• Resolution: 12 bit;
• Accuracy: 0.1%;
• Isolation: 800V between the Analogue Ouputs and the
Main Electronics.
3-6-2
AO1... AO4 Voltage Analogue Output Connections
• Respect the polarity shown;
• Type: 0/1... 5 V, 0/2... 10 V;
• Load: > 1 k
Ω
;
• Resolution: 12 bit;
• Accuracy: 0.1%;
• Isolation: 800V between the Analogue Ouputs and the
Main Electronics.
3-7
Digital Output Connections
3-7-1
DO1... DO
8
(PNP) Source Type Digital Output
(connector X6)
• The Digital Outputs number of the terminals are:
D01... D08
• The 8 output loads should not exceed 0.7 A each;
• In the drowing are connected only 2 loads as an example;
• Isolation: 800 V between the Digital Outputs and the
Main Electronics.
Note:
For proper electrical connection, refer to Power supply for Digital Channels
(connectors X5 and X7).
Load
+
mA
Load
+
mA
GND
Load
+
mA
Load
+
mA
GND
Lower side
Front
0/4... 20 mA Analogue Outputs
X9
X10
AO1
AO2
AO3
AO4
Lower side
Front
Load
+
V
Load
+
V
GND
X9
X10
0... 10 V Analogue Outputs
Load
+
V
Load
+
V
GND
AO1
AO2
AO3
AO4
Upper side
Front
Digital Outputs D01... D08
LOAD
LOAD
24 Vdc
+
-
Summary of Contents for AC3nP