P/N PM000158A • Rev. 2 • ISS 19JUN2018

1 of 3

© 2018 Ascom, Inc.

External Input Module Installation Sheet

Model NUMI2-HE

Description

The NUMI2-HE External Input module resides on the active 
room bus. The module has two Ascom SafeConnect 
sockets on the front face and two RGB LEDs (one above 
each socket).

Module Connectors

The module includes two RJ-45 jacks for room bus 
connections and DIP switches for room bus addressing. 
Figure 1 shows the jacks and DIP switches on the back of 
the module.

Figure 1: Module connections

Legend

(1) 2x RJ-45 connections to room bus
(2) DIP switches for bus addressing

Setting the Room Bus Address

The room bus address is a unique number assigned to a room 
module when modules of the same type are attached to the 
room bus.

If you do not use DIP switches to set the room bus address, 
be sure all the DIP switches are in the OFF position on the 
back of the module.

To set the DIP switches:

1.  Set the DIP switches for the correct room bus address 

(0...7), as shown in Figure 1, item 1. 

2. Using a small screwdriver, gently slide the switch up for 

“ON” or slide it down for “OFF.”

Installation

Note: 

Before beginning the installation, ensure all the 

necessary cables are available and are properly terminated. 
RJ-45 connectors should be terminated in accordance with 
the T568B or EIA 568B connection standard. 

The module can mount to a backbox, or to a wall using a 
surface-mounting spacer (NUSP1-HE).

To mount the module on a backbox or spacer:

1. When using a backbox, loosen the screws on the backbox 

so that approximately 5mm extend out from the backbox 
and the heads of the screws can pass through the keyhole 
slots of the adapter plate.
-or-

When using a spacer, ensure it is properly mounted to the 
wall and that the adapter screws are available.

2. Place the adapter (with the arrow facing up) over the 

backbox and ensure that it is level.