Installation & Maintenance Instructions

Form No.V8700R1

HYDRAMOTOR

r

 PUSH-TYPE LINEAR ACTUATORS

AH2D

HYDRAMOTOR

r

ACTUATOR

SERIES

WARNING

To prevent the possibility of death, serious injury or

property damage, the Hydramotor

r

 Actuator must be

installed  and  serviced  only  by  a  qualified  service

technician avoiding the following hazards:

S

Electrical  hazard.    Turn  off  all  electrical  power  to

Hydramotor

r

 Actuator.  More than one circuit may

exist.

S

Pressure  hazard.    Depressurize  valve  and  vent

hazardous or combustible fluid to a safe area before

inspection or removing the actuator or valve from

service.

S

Explosion,Ă fire or toxic Ăgas Ăhazards.  Extinguish all

open flames  and  avoid  any type of sparking or

ignition during leakage testing.

NOTICE:    See  separate  valve  installation  and  maintenance

instructions  for  information  on:  Operation,  Positioning,

Mounting,  Piping,  Strainer  or  Filter  Requirements,  Flow

Controls,  Preventive  Maintenance,  and  Cause  of  Improper

Operation.

DESCRIPTION

AH2D  Hydramotors

r

  are  self-contained  linear,  push-type

actuators  which  extend  when  powered  and  retract  by  spring

force upon power interruption.
The  AH  actuator  is  typically  used  for  control  of  gas-fired

heating  equipment,  commonly  to  open  and  close  a  valve or

both  a  valve  and  damper.    AH2D  actuators  position  V710

Series gas valve assemblies.

OPERATION

Application  of  electrical  power  simultaneously  drives  an

electric  pump  and  closes  a  normally-open  dump  valve,

resulting in up to 250 pounds of force on the actuator stem. This

extends the actuator stem and attached valve poppet, to open

the valve and/or damper.
Upon reaching the fully extended position, a travel limit switch

interrupts power to the electric motor while maintaining power

to the dump valve, thus stabilizing hydraulic pressure to hold

shaft position.  Position indicators on both sides of the actuator

show the actual position of the valve stem.
Upon  power  interruption,  the  dump  valve  opens  releasing

hydraulic  pressure,  allowing  the  return  spring  to  retract  the

stem and close the valve fully.  Closing time is one second or

less.

OPTIONAL FEATURES

S

Damper Shaft & Arm

 

 

Shaft with all components to mount

damper arm on either side of actuator.  Available with or

without return spring.

S

Auxiliary  Switch

   

One  or  two  integral  SPDT  switches,

field adjustable to actuate at any position of stroke.

S

Overtravel Proof-of-Closure Switch

  A single factory set

non-field adjustable SPDT switch to be used in conjunction

with V710 Series Gas Valves with overtravel seal (V22 or

V25 suffix in catalog number).

Figure 1.  AH2D Actuator (shown mounted

 on V710 series gas valve)

ACTUATOR

ASSEMBLY

COVER

COVER

SCREW

CONDUIT

KNOCKOUT

STEM POSITION

INDICATOR

DAMPER

ARM

DOWNSTREAM

PRESSURE TAP

UPSTREAM

PRESSURE TAP

(OPTIONAL)

AH2D

ELECTRICAL

VALVE

ASSEMBLY

(2)

NAMEPLATE/

Figure 2.  Cutaway schematic

(de-energized position)

OIL FILL PLUG

MOUNTING

PISTON

ACTUATOR STEM

HYDRAULIC

FLUID LEVEL

INTERNAL

RESERVOIR

SPRING

SET SCREW (2)

TRAVEL LIMIT

SWITCH

HOLE IS SHOWN 90

_

 OUT OF

TRUE POSITION