Installation, Operation and Maintenance Manual

IO-30100  RevT  03-18

2

ASCO 200 SERIES

 power line filters offer the original Active Tracking™ technology to guard against 

commonly occurring, but very damaging, lower energy transients and offers excellent noise reduction. 
The Model 277 & Model 275 combine rugged, high energy current diverters with the Active Tracking™ 
Filter to provide protection against the full spectrum of voltage transients and surges. 

INSTALLATION

DANGER! ONLY QUALIFIED PERSONNEL SHOULD INSTALL OR SERVICE 

THIS SYSTEM. ELECTRICAL SAFETY PRE-CAUTIONS MUST BE FOLLOWED 

WHEN INSTALLING OR SERVICING THIS EQUIPMENT. TO PREVENT RISK OF ELECTRICAL SHOCK, 

TURN OFF AND LOCK OUT ALL POWER SOURCES TO THE UNIT BEFORE MAKING ELECTRICAL 

CONNECTIONS OR SERVICING.

DANGER! SEULEMENT LE PERSONNEL QUALIFIÉ DOIT INSTALLER OU MAINTENIR CE 

SYSTÈME.  DES PRÉCAUTIONS DE SÉCURITÉ EN ÉLECTRICITÉ DOIVENT ÊTRE SUIVIS LORS DE 

L’INSTALLATION OU DE LA MAINTENANCE DE CET EQUIPEMENT.  POUR EVITER TOUT RISQUE DE 

CHOC ÉLECTRIQUE, DÉBRANCHEZ ET VEROUILLER TOUTES LES SOURCES D’ ALIMENTATION DE 

CET EQUIPEMENT AVANT DE LE BRANCHER OU LE MAINTENIR.

Proper installation is required for maximum system performance. Read the following information to 
assure a quality installation. These instructions do not replace national or local electrical codes.

Environment –

 For use indoors, in an ambient temperature of -40°C to +50°C, with a relative humidity 

0% to 95% (non-condensing).

Maximum Current Capability – 

The total current draw for all loads that a model may continuously 

handle is given in the MODEL NUMBER CONFIGURATION table found on the next page. Overloading the 
unit can permanently damage the device.

Nominal Voltage –

 The nominal operating voltage for each model is given in the MODEL NUMBER 

CONFIGURATION table found on the next page. Failure to use the unit at its rated voltage can permanently 
damage the unit or provide inadequate surge protection.

Supplemental Enclosures -

 All units provided with exposed terminal blocks must be installed inside an 

enclosure and located so as to prevent accidental contact with terminals during maintenance or servicing.

Summary Alarm Contacts (Model 277 only) –

 Summary alarm Form C (1 N.O. and 1 N.C.) relay contacts 

rated 125VAC, 5A max. are provided for remote indication of protection status. Connections may be made 
to these terminals on the unit using 18 AWG conductors.

Grounding -

 Input and output ground terminals (if provided) must be connected for proper operation. 

This grounding is not only required for safety, but also for equipment performance. Incorrect grounding 
can reduce or impede the operation of the unit.

Line Cord Units (Model 275 only) –

 Plug unit into wall outlet and turn on power switch (if provided). For 

best results, plug equipment to be protected directly into the unit (do not use extension cords or power 
strips). Keep data cables as far away from power cords as possible.

OPERATION

These products are designed for years of trouble-free operation and require little or no operator 
intervention after installation. Should the unit not appear to be functioning properly and/or the indicator 
LED (if provided) is extinguished, check all connections, and assure the voltage is correct and that the 
total current draw on the unit from all loads does not exceed the rated current. If the unit still is not 
functioning properly, call ASCO Surge Protection at 800-237-4567.

TROUBLESHOOTING

If any of the diagnostic indicators indicates a problem (i.e. red LED ON, and/or green LED OUT), check all 
connections and voltages to the unit. If all connections are reliable, and proper voltages are supplied to 
the unit, call ASCO Surge Protection, Inc at 800-237-4567.

 

Summary of Contents for 270

Page 1: ...ation Manual Model 270 Model 275 Model 277 Model 270 Islatrol E Series DC DC Voltage EMI RFI Noise Filter SPD Model 277 Islatrol IE Series AC Voltage EMI RFI Noise Filter SPD Model 275 Islatrol IC LRIC Series AC Voltage EMI RFI Noise Filter SPD ...

Page 2: ...model is given in the MODEL NUMBER CONFIGURATION table found on the next page Failure to use the unit at its rated voltage can permanently damage the unit or provide inadequate surge protection Supplemental Enclosures All units provided with exposed terminal blocks must be installed inside an enclosure and located so as to prevent accidental contact with terminals during maintenance or servicing S...

Page 3: ...F 0 3 0 G F 0 5 0 L F 1 0 0 2 7 5 1 2 0 N F 0 0 2 A N 3 N 0 2 4 0 L F 0 0 5 L C 4 8 0 L F 0 0 7 W L F 0 1 5 F 0 3 0 2 7 7 1 2 0 N F 0 0 3 A N 3 N 0 2 4 0 L F 0 0 5 X F 0 1 0 F 0 2 0 KEY 270 Islatrol E Series DC 120N 120VAC Single Phase L N G F002 2 5 Amps Max A LC Line Cord Receptacle G NEMA Type 4 metal 0 Standard F003 3 Amps Max All Modes of Protection 240L 220 230 240VAC Single Phase L N G or L...

Page 4: ...ith or without one or more yellow stripes insulated grounding conductor identical in size insulation material and thickness to the grounded and ungrounded conductors must be installed ref NEC Table 250 95 and referenced back to an acceptable building earth ground Attachment plugs receptacles etc in the vicinity of the filter must be of a grounding type with the grounding conductors serving them co...

Reviews: