background image

© 2019 ASCO Power Technologies. All Rights Reserved

For troubleshooting, call technical assistance at 1-800-237-4567 or [email protected]

3

IO-75065

12/2019

ASCO Model 277 

Surge Protective Device (SPD) with Active Tracking Filter™

Introduction

ASCO Model 277 with Active Tracking Filter technology offers high 

frequency noise filter capabilities with surge protection for loads up to 20 A 

of continuous current. The Model 277 is a DIN or flange mounted SPD/ATF 

that helps to protect industrial critical loads.

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• 

Apply appropriate personal protective equipment (PPE) and follow safe 

electrical work practices. See NFPA 70E, NOM-029-STPS or CSA Z462.

• 

This equipment must only be installed and serviced by qualified electri-

cal personnel.

• 

Turn off all power supplying this equipment before working on or inside 

equipment.

• 

Always use a properly rated voltage sensing device to confirm power is off.

• 

Replace all devices, doors and covers before turning on power to this 

equipment.

• 

This equipment must be effectively grounded per all applicable codes. 

Use an equipment-grounding conductor to connect this equipment to the 

power system ground.

• 

Do not supply more than 125VAC or 5 A AC to contacts.

• 

Confirm that the Surge Protective Device voltage rating on the module 

or nameplate label is not less than the operating voltage.

Failure to follow these instructions will result in death or serious injury.

WARNING:

 This product can expose you to chemicals including 

DINP, which is known to the State of California to cause cancer, and 

DIDP which is known to the State of California to cause birth defects 

or other reproductive harm. For more information go to: www.

P65Warnings.ca.gov.

NOTICE

LOSS OF SURGE SUPPRESSION

• 

Make certain that Surge Protective Device is disconnected from the 

circuit it is protecting before conducting high potential insulation testing.

Failure to follow these instructions can result in equipment damage.

DANGER

Installation

1.  Turn off all power supplying this equipment before working on or inside 

equipment.

2. 

Confirm that the unit has the same voltage rating and configuration as 

the power system voltage and power system voltage to which it will be 

connected.

3. 

Install the unit and cables as close as possible to the protected equip-

ment and secure.

4.  Connect the supply cables to the line side of the SPD/ATF.

5.  Complete the circuit by connecting cables from the load of the SPD/ATF 

to the protected equipment.

 

Note:

 

A dry contact connection is available.

6.  Check that all connections are secure. Remove all tools and discarded 

hardware from the unit.

7. 

Replace the barrier, cover/door and/or trim to the equipment.

8. 

Equipment may be re-energized after all the above steps are complete.

Summary of Contents for 277

Page 1: ...Surge Protective Devices Installation Operation Manual Model 277 ...

Page 2: ...used to alert you to potential personal injury hazards Obey all safety messages that follow this symbol to avoid possible injury or death DANGER DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION CAUTION indicates a hazardous situation...

Page 3: ...vice voltage rating on the module or nameplate label is not less than the operating voltage Failure to follow these instructions will result in death or serious injury WARNING This product can expose you to chemicals including DINP which is known to the State of California to cause cancer and DIDP which is known to the State of California to cause birth defects or other reproductive harm For more ...

Page 4: ... C22 2 No 269 5 17 277120NF003AN3N0 5 A 277120NF005AN3N0 10 A 277120NF010AN3N0 20 A 277120NF020AN3N0 240 V 50 60 Hz 1 phase 2 wire ground 320 V L N 3 A 277240LF003AN3N0 5 A 277240LF005AN3N0 10 A 277240LF010AN3N0 20 A 277240LF020AN3N0 Table 2 ASCO Model 277 General Specifications1 Mounting Power Connection Wiring Copper Wire Terminal Torque Operating Storage Temperature Catalog Numbers DIN rail or ...

Page 5: ...ce at 1 800 237 4567 or customercare ascopower com 5 IO 75065 12 2019 ASCO Model 277 Surge Protective Device SPD with Active Tracking Filter Figure 1 ASCO Model 277 DIN Rail Installation and Removal Figure 2 DIN Clips Note DIN Rail clips can be positioned for vertical or horizontal installation ...

Page 6: ...onal protective equipment PPE and follow safe electrical work practices See NFPA 70E CSA Z462 or NOM 029 STPS Failure to follow these instructions will result in death or serious injury Indicator Status ON The device is installed correctly and the line side has power Indicator Status OFF Check connections verify that the line voltage is at the point of connection if all is correct then replace the...

Page 7: ... Reserved For troubleshooting call technical assistance at 1 800 237 4567 or customercare ascopower com 7 IO 75065 12 2019 ASCO Model 277 Surge Protective Device SPD with Active Tracking Filter Dimensions in mm 3 83 97 2 3 06 77 7 4 06 103 1 ...

Page 8: ...7 535 6339 F 727 539 8955 E customercare ascopower com While every precaution has been taken to ensure accuracy and completeness in this literature ASCO assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions ...

Reviews: