10
Installation
Point level switch
10
Permitted orientations
Forbidden orientations
1:
Vertical from the top
6:
In direction of solids flow
2:
Angled from the top
7:
Installation coupling too long
3:
From the side
8:
Horizontal with shaft length >300 mm (11.8 in)
4:
From the side with protective cover against falling
solids
5:
From the bottom (device must be protected
against shock-type loads)
Ambient temperature range
–20 to 60 °C (–4 to 140 °F)
Medium temperature range
–20 to 80 °C (–4 to 176 °F)
Mechanical load of optional signal lamp
The optional signal lamp must be protected against mechanical load (impact energy > 1 J).
More information is provided in the "Technical data" section (→ 24).
4.3
Installation instructions
NOTICE
The device can be damaged if handled incorrectly during installation
‣
Do not turn the housing to tighten the process connection. Once the process connection
has been tightened, the housing can be aligned so that the cable entries point downwards.
1
A0017361
3
Installation of the standard version
1
Sealing ring 60x48x3 mm (2.36x1.89x0.12 in.)
2
Open-ended wrench AF 60