Multi Variable Air Conditioners Compact Cassette Type Indoor Unit
12
(10) The installation heights of raising pipe for drainage should be lower than B. The gradient
from raising pipe towards drainage direction should be at least 1%~2%. If the raising pipe is
vertical with the unit, the raising height should be less than C, as shown in Fig.4.3.2.6.
Unit: mm
Fig.4.3.2.6
Unit: mm
model
A
B
C
AMV5-22CC
AMV5-28CC
AMV5-36CC
AMV5-45CC
AMV5-50CC
AMV5-56CC
170
1030
980
(11) During the installation, distance from soft drain pipe to the gasket is C when the bolt is
tightened. It is not allowed to apply PVC or other related glue in the joints of two ends of
drain pipe.
Fig.4.3.2.7
Unit: mm
Model
C
AMV5-22
~56
CC
10±3
4.3.3 Test of Drainage System
(1) Please test drainage system after electric work is finished.
Inject approximately 1L purified water to drain pan from air vent, ensure that not to splash the
water over the electrical components (e.g. water pump. etc.).