INSTRUCTION MANUAL
Recovery and Reclaim machine
ECOcycle AuroraⅡ
IM1401
【Please read this manual before operating】
Page 1: ...INSTRUCTION MANUAL Recovery and Reclaim machine ECOcycle Aurora IM1401 Please read this manual before operating...
Page 2: ...sories Other Air Conditioning Equipment 8 HOW TO USE 9 Preparation before Operation 9 Recovery Reclaim Operation 10 Discharge Oil Method Oil separator 16 Discharge Oil Method Electrostatic filter 16 W...
Page 3: ...d smoking during the work in process Cigarette light may creates Carbon Oxy Chloride and ignite fire Use protective eye glass and hand glove when disconnecting hoses If Freon gas was touch your skin o...
Page 4: ...generator is not large enough it may lead to heating smoking or fire See the machine plate or this manual for the detailed specifications Do not setup the machine at location where gasoline thinner or...
Page 5: ...esult is unpredictable Do not use the machine for purposes other than the original intent This machine is designed to recover the specified refrigerants Do not operate under an excessive heavy load to...
Page 6: ...ation strange noise is noticed stop the unit and refer to the Page22 BEFORE REQUESTING REPAIR OR SERVICES in the manual Request for repair or service instead of disassembling for repair contact the st...
Page 7: ...de Safety cable Oil discharge port for Electrostatic lter Speci cation label Description label Dry lter Discharge valve Suction valve Auto OFF Manual switch Power Breaker COMPONENTS OF THE MACHINE Lab...
Page 8: ...ion 587 622W 50 60Hz Electric current of operation Electric current of starting 8 9 6 0A 50 60Hz 34A Operating temperature 5 35 Applicable cylinder over fill protection method Float sensor type Recove...
Page 9: ...liquid Adapter for different diameter for auto A C quick type 3 16 female x 1 4 male Y19120 Adapter to connect to the small service port 3 16 for R12 High pressure quick joint for R134a M12 Y03100A Fo...
Page 10: ...r when the vacuum reaches 0 095MPa 13 8psi 0 1MPa 14 5psi Switch off the vacuum pump Disconnect the hose between the vacuum pump and the cylinder In case of the temperature under 10 it needs warming u...
Page 11: ...side CLOSE Vapor valve System Manifold Optional Acc Eco Cycle Aurora Cylinder with over protection sensor Low pressure side High pressure side High pressure side Liquid port Safety cable Filter CLOSE...
Page 12: ...e Purge position Connect hose to liquid side of cylinder after the suction pressure gauge was reach vacuum again Set the Power switch to the OFF position 2 Evacuation of the recovery machine and the h...
Page 13: ...valve OPEN Ball valve AutoOFF 2 ON 3 OFF 7 OPEN Suction valve RECOVERY Switching valve OPEN Discharge valve OPEN SLOWLY OPEN 4 CLOSE 6 CLOSE 8 CLOSE 8 Low pressure side High pressure side CLOSE Low pr...
Page 14: ...lve Slowly open the ball valve of the suction hose which almost opened with taking 20 seconds Follow ordinal recovery reclaim procedure SLOWLY OPEN OPEN Liquid valve CLOSE Vapor valve System Manifold...
Page 15: ...rate See the instruction manual of Cooling Unit for detailed information Use an evacuated spare cylinder Use Cooling Unit CL3 optional accessory Replacement of spare cylinder Recovery Procedure of R4...
Page 16: ...ry machine and the hose of the discharge side Connect the hose of the discharge side to an evacuated cylinder to recover the refrigerant left in the recovery machine and the hose 4 Refrigerant Dischar...
Page 17: ...of machine Slowly open the valve and discharge oil to other container The oil is collecting about 2L when the tank is full CLOSE the valve after discharge oil CLOSE the cap of oil discharge port afte...
Page 18: ...e side OPEN Suction valve RECOVERY Switching valve CLOSE Discharge valve OPEN 5 At 0 2MPa 29psi Maintain 4 HOW TO USE Connect hoses as above after carry out Page11 2 Evacuation of the recovery machine...
Page 19: ...0 3063 0 5616 0 1335 4 0 3349 0 6069 0 1519 2 0 3650 0 6545 0 1714 0 0 3996 0 7044 0 1920 2 0 4298 0 7569 0 2138 4 0 4647 0 8119 0 2369 6 0 5012 0 8695 0 2612 8 0 5395 0 9300 0 2868 10 0 5796 0 9930...
Page 20: ...e inside of the cylinder is under this condition and this chart is useful for field operation When a cylinder is almost full with liquid and no vapor the pressure rises rapidly even with a slight incr...
Page 21: ...ecular sieve No need to take off filter at the bottom in the Molecular sieve pack Dry filter is installed back side of machine Replacement period amount of refrigerant 150 200 kg Fill up all of new mo...
Page 22: ...ing hose Turn ON the vacuum pump and OPEN the valve of oil discharge port CLOSE the oil discharge valve and turn OFF the vacuum pump after more than 1 hour of vacuum Take off connected hose between va...
Page 23: ...liquid valve on the cylinder The pressure in the cylinder is high Cool the cylinder or use Cooling Unit Voltage drop Connect to a 220V power source Use appropriate extension code The recovery speed i...
Page 24: ...oat switch Oil full fill bypass switch Full fill lamp Safety cable Low pressure switch Auto off Manual switch for operation Power switch Power cord Circuit breaker 15A Electrostatic filter system High...
Page 25: ...Safety relief valve Check valve Purge Recovery Purge Molecular sieve Low pressure switch Compressor Condenser Low pressure gauge High pressure gauge Electrostatic lter system Oil separator Double pip...
Page 26: ...25 ECOcycle Aurora...
Page 27: ...26 ECOcycle Aurora...
Page 28: ...Customer Memo Please ll in for your record in the future The information is helpful for inquiry and ordering parts Products Number Date Purchased Store Purchased the Unit Code No IM0345 A...