Fill in the right-hand column with the Set-Up Wizard settings that you use when programming the panel.
Record the setup date. If any settings change, record those changes and the date they were made.
Function
Options
Settings
Initial Set-Up
Setting Date
Adjusted
Setting Date
Temperature Display
F/C
Mode Priority
Automatic, Cooling, Heating, Zone Weight
Zone 1 T-Stat
Heat Pump-
Heating/Cooling
Z1 Weight
Zone 1: 10%-90%
Z2 Weight
Zone 2: 10%-90%
Z3 Weight
Zone 3: 10%-90%
Z4 Weight
Zone 4: 10%-90%
Air Handler Stage-up Threshold
30%-100%
Heat Stage Threshold
Enter Temp: 80-130
Cool Stage Threshold
Enter Temp: 20-60
Balance Point-OAT
Enter Temp: 0-50 of Back-up Heat
Resistance Lockout-OAT
Enter Temp: Lock-In or 0 to 40
H.P. LAT High Limit
Enter Temp: 100-125
AUX LAT High Temp
Enter Temp: 130-180
Cooling LAT Low Temp
Enter Temp: 34-46
Type of Back-up
Electric/Fossil Fuel
Back-up Controls Fan
True-False
Dehumidifier Call Voltage
0 VAC/24 VAC
Secondary Purge Time
Enter Sec: 0-180
Dehumidification Cycle Time
Enter Min: 5-10-15
Cooling Low Ambient Lockout
Enter Temp: 20-60
Rev Valve Energized
Cooling/Heating
Use balance point for electric
True-False
Demo mode enable
True-False
Setup Worksheet