background image

11

During normal operation of zoning equipment, the amount of air passing through the air conditioning coil
or over the heat exchanger may be reduced to a point that undesirable air temperatures may develop in
the duct system (too cold or too hot). The Leaving Air Temperature (LAT) system is used to cycle the AC
compressor or heating system to prevent evaporator coil freeze-up or overheating of the heat exchanger.
Install the Sensor into the supply duct just around the corner from the Plenium and connect to the “LAT
Sensor” 
terminals (Fig. 10b). Connect the Green grounding lead to the ground terminal at the 24 VAC
terminals (Fig. 5a) along with the mechanical ground wire. Add no more than 25 ft. of wire to LAT Sensor.

NOTE:  All LAT limit controls must be used as secondary controls only.

The LAT control setting must be above/below your primary factory protection level.

LAT SYSTEM SET-UP

Set both rotary switches(Heating LAT and Cooling LAT) to the desired heating and cooling limits 

(Fig.10a).

Heating LAT settings range from 100° F to 180° F and OFF.
Cooling LAT settings range from 40° F to 56° F and OFF.

If you do not wish to use either or both, place the unused rotary switch pointer to the Off position.

You must install the sensor or place both rotary switches to the Off position.

Self Test: The Arzel Panel automatically detects an open or shorted LAT sensor and locks out the
equipment accordingly.
·  Both Red LED’S at Heating LAT flashing indicates a shorted sensor wire or probe.
·  Both Yellow LED’S at Cooling LAT flashing indicates an open sensor wire or probe.
High LAT: The temperature setting cycles the first-stage heating at set point temperature. Second-stage
heating is automatically cycled 10° lower than high temperature setting. Both stages will re-connect after
a 15° temperature drop.
Low LAT: The temperature setting cycles the first-stage cooling at set point temperature. Second-stage
cool- ing is automatically cycled 5° higher than set point temperature. Y1 will reconnect after a 4-minute
time delay if the duct temperature is above set point. Y2 will reconnect after a 4-minute time delay, if the
duct temperature is 5° above set point.

                          NOTE:  All LAT limit controls are to be used as secondary controls only.

               The LAT control setting must be above/below your primary factory protection level.

         Rev. 5/01/01

MASTER ZONE CONTROL (MZC

®

)

Moving this switch to the ON position or closing a circuit across the “Set-Back” terminals, establishing
Zone 1 as the “Master Zone” and allows automatic (occupied/ unoccupied) set-back or set-up control. The
“Master Zone Control” mode operates as a single zone system: all zone dampers open and the
equipment is cycled based on Zone 1 thermostat settings.  Master Zone operation may be initiated by
manual operation of the switch or it may be operated by a time clock or programmable thermostat with
dry contacts that close in the unoccupied mode (wired across the MZC Remote terminals).  The switch
and the remote terminal are electrically parallel. You may use either one or both (Fig. 10b).

LAT™ (Leaving Air Temperature) Limit Controls for Heating and Cooling

(Fig. 10a)

(Fig. 10b)

      U.S. and Foreign Patents & patents pending.                                                    © copyright 2004 by Arzel Zoning Technology, Inc.

 

 

Summary of Contents for AirBoss

Page 1: ...and 8 Zones Comfort Reliability and Easy Installation U S and Foreign Patents patents pending copyright 2004 by Arzel Zoning Technology Inc Rev 5 1 01 Arzel Zoning Technology Inc 4801 Commerce Parkwa...

Page 2: ...____________ Date Installed ________________________________________ Model ____________________ Serial ___________________ Address _____________________________________________ _______________________...

Page 3: ...Heating Cooling Automatic 8 Call Waiting 9 Energy Conservation Cycle ECC 9 ECC Bypass 9 Compressor Lockout TDO 1 Stage 1 and TDO 2 Stage 2 9 Fan On Heat Operation 10 Master Zone Control MZC 10 LAT Lim...

Page 4: ...all dampers during emergency or test operations by switching MPS to ON and PWR switch to OFF P 12 Master Zone Control MZC Can be set up either by a programmable thermostat manual switch or a time clo...

Page 5: ...The LAT control setting must be below above your primary factory protection level GENERAL SYSTEM OPERATION A call from any zone thermostat will call on the HVAC equipment position the solenoid air va...

Page 6: ...hermostats for each zone in a central area within the zone on an inside wall five feet from an outside wall and five feet from the floor Avoid areas near register outlets lights and other equipment th...

Page 7: ...Yellow reversing valve energized in cooling B No LED reversing valve energized in heating Fig 6a Fig 6b Damper positioning is controlled by a bank of 24VDC solenoids one per zone mounted along the to...

Page 8: ...rgency heat mode can be initiated either with the Emergency Heat switch on the panel a remote outdoor thermostat or a call for W1 in the Fossil Fuel mode The Emergency Heat Mode can also be initiated...

Page 9: ...U S and Foreign Patents patents pending copyright 2004 by Arzel Zoning Technology Inc THREE WAY PRIORITY SYSTEM PROVIDES A CHOICE OF HEATING COOLING OR AUTOMATIC PRIORITY FIG 8A In Heating Priority He...

Page 10: ...out of the HVAC system Before using the TDO switches you must disconnect the HVAC R wire to avoid short cycling the compressor FAN ON HEAT OPERATION Use the Fan On Heat switch if immediate fan operati...

Page 11: ...LED S at Cooling LAT flashing indicates an open sensor wire or probe High LAT The temperature setting cycles the first stage heating at set point temperature Second stage heating is automatically cycl...

Page 12: ...rs if the air temperature in the duct is compatible with the thermostat call Smart Slave Zone operation is indicated by the LED on its PC board If the LED is lit the damper is in the open position Do...

Page 13: ...n all the zone dampers will open This will aid in troubleshooting by allowing the operation of the HVAC system independent of the Arzel panel if you suspect a PC board failure YOU CAN BYPASS THE ZONIN...

Page 14: ...nd place template on duct Fig 13a observing direction of airflow arrow on the template Cut out required triangle Fig 13b Insert damper blade with blade facing the long side of the triangle Fig 13c Rot...

Page 15: ...each duct corner Fig 14a This will avoid the need to cut into the Pittsburgh Lock in the duct and leave sheet metal for the mounting plate screws Slide the damper into the duct at an angle to avoid cu...

Page 16: ...is available in eight colors to easily identify each zone IDENTIFYING THE ZONES Tubing is available in eight colors for easy tracing and identification of dampers To avoid zone mix ups mark all suppl...

Page 17: ...tion with the pressure tap at the bottom 2 Start a fan call for the smallest zone only Adjust the pressure switch to open the Bypass damper when air noise at the registers approaches the level you det...

Page 18: ...backup heating 8 Turn the thermostat down until the thermostat is satisfied The dampers and system will go through its Energy Conservation Cycle ECC for 3 minutes The LED lights will go out and the p...

Page 19: ...t a heating problem To correct a cooling problem To save energy costs What is the Brand name of your furnace ______________________ What is the brand name of your A C ______________________ Type of Sy...

Page 20: ...can continue in this effort please fill out this survey card and return it to us Comfort makes a house a home Comfort also makes a commercial environment more productive Your decision to install anAr...

Reviews: