Manual explosion-safe window air conditioning system AR-054 

Issue December 2017 

3 / 7 

If these instructions are not followed the explosion safety of the equipment cannot be guaranteed. The equipment could 

then endanger the life of the user and could cause the ignition of an explosive atmosphere. Consequently, Artidor as 

the manufacturer will waive any responsibility. 

 

2.

 

Description 

The window air conditioning system consists of a combined outdoor unit and indoor unit with remote control. In function 

the system refrigerates air. The air conditioning system provides a continuous flow of cold fluid which decreases the 

temperature of the heat exchanger, which in its turn absorbs the energy of the air, resulting in a room air temperature 

decrease. The remote control enables the user to operate the indoor unit. 

 

The part of the air conditioning system situated on the outside consists of a sheet steel enclosure and contains a heat 

exchanger, a hermetically sealed compressor, one pressure regulated valve for controlling the refrigerant and NTC 

temperature sensors. The sheet steel enclosure is partly part of the protection degree against ignition applied. 

 

The part of the air conditioning system situated on the inside consists of a heat exchanger and NTC temperature 

sensors all covered by a non-metallic hood. The electronically driven fan provides air flow on both sides of the system. 

 

The infra-red remote control contains electronics (PCB) with a display and membrane pushbuttons all housed in a non-

metallic housing containing two (2) 1,5 V DC AAA dry cell batteries. 

 

The ambient temperature allowed for the apparatus is -20 °C to +45 °C. 

 

3. 

Characteristics 

The characteristics can be summarized as follows: 

 

Equipped with a H07 RN-F 3 x 1,5 mm² connection cable, length 5 meter 

 

Manufactured on the basis of European Directive 2014/34/EU (ATEX 114); 

 

Suitable for use in gas hazardous areas classified as zone 2; 

 

Explosion safety category and protection against ignition applied: II 3 G Ex ic nAC h IIC T3 Gc; 

 

Protection degree against ingress of water and dust IP54; 

 

4.

 

CE - Marking 

The modification of the equipment to explosion-safe does not affect the conformity to the European Directives as 

declared by the original equipment manufacturer in the original Declaration of Conformity. 

With regard to explosion safety the air conditioning unit has been designed and manufactured on the basis of the 

essential health and safety requirements of European Directive 2014/34/EU (ATEX 114) relating to Group II Category 

3 G. Harmonized European construction standards have been applied fulfilling the essential requirements of the 

directive. Please refer to paragraph 6 “Technical Data” and the Declaration of Conformity in the back of this user 

manual for the applicable directives. 

 

 

Summary of Contents for AR-054 series

Page 1: ...User manual Explosion safe window air conditioning system Type series AR 054 II 3 G Ex ic nAC h IIC T3 Gc ...

Page 2: ...it when it is damaged During installation of the air conditioning unit national safety regulations must be observed Only use the air conditioning unit under the environmental conditions for which it is specified Deviating environmental conditions can contribute to damage to the equipment and may lead to possible danger to the life of the user Do not use the air conditioning unit at temperatures de...

Page 3: ...l covered by a non metallic hood The electronically driven fan provides air flow on both sides of the system The infra red remote control contains electronics PCB with a display and membrane pushbuttons all housed in a non metallic housing containing two 2 1 5 V DC AAA dry cell batteries The ambient temperature allowed for the apparatus is 20 C to 45 C 3 Characteristics The characteristics can be ...

Page 4: ...N 60079 11 2012 EN 60079 15 2010 EN 80079 36 2016 and EN 80079 37 2016 Certification document Unit assessment certificate Ambient temperature 20 C to 45 C Sealed against moisture and dust IP54 according to EN 60529 Material housing inside part Sheet steel frame and non metallic cover Material housing outside part Sheet steel plating Connection H07 RN F 3 x 1 5 mm connection cable length 5 meter Ea...

Page 5: ...g The unit contains no components that need direct access in normal operation The following warning is marked The air conditioning unit is modified to explosion safe meeting ATEX requirements II 3 G No serviceable parts inside Refer to qualified personnel as substitution of parts may impair the suitability for use in hazardous areas The housing may only be opened under non hazardous safe condition...

Page 6: ...ive for repair If the housing is opened care must be taken of the following The housing must not be opened unless power is switched off prior to repair The housing must not be opened unless the area has been known to be non hazardous If opened the AR 054 air conditioning unit shall be dismantled in a logical sequence 12 Removal re use For processing regarding disposal or reuse of the product and i...

Page 7: ...Manual explosion safe window air conditioning system AR 054 Issue December 2017 7 7 This document can be subject to change without notice ...

Reviews: