Arrow Pneumatics RH105 Owner'S Manual Download Page 6

D r y e r   O p e r a t i o n

6

The inlet wet compressed air enters the dryer and is directed into tower “A” through the switching
valve. The wet air passes through the desiccant bed while the activated alumina strips moisture 
leaving dry service air. A portion of this extremely dry air is passed through the fixed orifice shuttle
check valve and flows downward through tower “B” drying out the saturated desiccant and exhaust-
ing out of the purge muffler.

This “REGENERATING OPERATION” is actually two cycles: one for drying service air, and one for dry-
ing desiccant. After approximately five minutes, the switching valve redirects flow,  repeating the
cycle. These cycles are reduced to two minute cycles if the -100ºF dew point is selected. 

Required purge air is generally 15% of rated flow.

All Arrow Pneumatic Mini-Regen Dryers have less than a 2 PSIG  
Maximum Pressure Drop at standard conditions. 

Your Arrow Dryer will give you years of service if the filters and drains ahead of
the dryer are properly maintained on a manufacturers recommended schedule.

Arrow also suggest replacing the desiccant in the vessels approximately every
three (3) years.  

Operating conditions will have to be taken into consideration and the schedule
adjusted accordingly. 

NOTE: BEFORE MAINTENANCE OF DRYER ALWAYS SHUT DRYER

OFF, DISCONNECT THE ELECTRICAL SUPPLY, AND DEPRESSURIZE

THE PNEUMATIC SYSTEM TO AVOID PERSONAL INJURY

DRYER OPERATION

MAINTENANCE

Summary of Contents for RH105

Page 1: ...O W N E R S M A N U A L Form F 0071 MINI REGENERATIVE AIR DRYER power MODELS RH105 THROUGH RH125 Mini Regenerative Mini Regenerative Air Dryer Air Dryer ARROW PNEUMATICS...

Page 2: ...URE 75 PSIG MAXIMUM INLET TEMPERATURE 120 F MINIMUM INLET TEMPERATURE 32 F STANDARD 40 F PRESSURE DEW POINT OPTIONAL 100 PRESSURE DEW POINT STANDARD CYCLE TIME 5 MINUTES OPTIONAL CYCLE TIME 2 MINUTES...

Page 3: ...conditions Best results occur when dryer is located as close to point of use as practical Avoid locating dryer outside or where it is exposed to the elements Dryers are sized according to airflow not...

Page 4: ...side of cabinet After filters located after the dryer help eliminate the possibility of desiccant dusting and carry over into the air system Install Purge Muffler shipped separately inside of cabinet...

Page 5: ...eaks detected must be fixed especially those on the outlet side of the dryer Energize electrical circuit by simply pressing the on off switch to the ON position The switch indicator light will be illu...

Page 6: ...alve redirects flow repeating the cycle These cycles are reduced to two minute cycles if the 100 F dew point is selected Required purge air is generally 15 of rated flow All Arrow Pneumatic Mini Regen...

Page 7: ...126065 126065 126065 MUFFLER SQF 3 SQF 3 SQF 3 SQF 3 SQF 3 ON OFF SWITCH 57300 57300 57300 57300 57300 5 MINUTE TIMER 120V 126707 126707 126707 126707 126707 5 MINUTE TIMER 220V 126750 126750 126750 1...

Page 8: ...buse or accident This warranty will apply to equipment installed operated and maintained in accordance with the procedures and recommendations as outlined in the owners manual published by Arrow Pneum...

Reviews: