installation &   

operating instructions

In-line circulating 

pumps

4

warning

A poor electrical connection can overheat and cause 
terminal and/or terminal board failures. Examine the 
wiring harness quick- connect terminals carefully for 
any signs of physical deterioration or loose fit to the 
terminals on the motor terminal board.
Care must be taken to assure connections are made 
to the proper terminals and adequate electrical clear-
ances are maintained.

warning

The control unit on the motor contains potentially 
hazardous voltage.

caution 

Wear safety glasses to inspect the equipment while 
it is running, especially if cover plates are removed.

notice

•  Voltage symbols vary among different multimeters and 

may be displayed as 

V AC

, AC, V, or a V beneath a wavy 

line. Select the correct symbol and set the multimeter to the 
voltage closest to the voltage you are measuring.

•  Read all instructions thoroughly and be familiar with the 

equipment before installing or working on it.

•  The PerfectSpeed® motor is properly packaged for  ship-

ment and storage and should be kept in a clean and dry 
indoor area.

Overview

The interface board communicates with the motor control to 
operate the motor in speed mode. The operating parameters 
are programmed in the 

eeprom

 of the motor control, not the 

PerfectSpeed® User Interface. On power up the interface board 
extracts the operating parameters from the motor control. 
Parameter categories include:
•  Motor direction
•  Motor mode of operation
•  Motor output display
•  Motor profile

PerfectSpeed® user interface box

The PerfectSpeed® operates in speed mode when connected to 
the pump. You can adjust the demand of the motor manually 
using the PerfectSpeed® User Interface. The motor information 
displayed in the User Interface is outlined in 

Table 

1

. If the 

motor encounters a problem, the User Interface displays a 
corresponding error code. These are outlined in 

Table 

1

 as well.

Table 

1

 – 

User interface display information

Control mode

Data displayed

Speed  
(speed feedback)

Spd

 – followed by the instantaneous speed in 

rpm

dE

 – followed by 

S +

 demand in 

%

Error Codes

e1

 – No communications

e2

 – Under Voltage

e4

 – Non- PerfectSpeed(r) Motor

Minimum and maximum operating parameters

The PerfectSpeed® motor operates properly within minimum 
and maximum parameters. Your settings must be within these 
ranges.

Table 

2

 – 

Armstrong

 

centrifugal pump & motor operating 

parameters

Control mode

Minimum

Maximum

Speed

300 rpm

s&h 5&6 

series

Summary of Contents for h-53

Page 1: ...nstalled on the discharge and suction side of the pump to facilitate service On larger pump sizes a check valve should be located on the discharge side of pump between the pump body and the gate valve to prevent damage due to water hammer 2 0 system cleanliness Before starting the pump the system must be thoroughly cleaned flushed and drained then replenished with clean liquid Welding slag and oth...

Page 2: ...perature or constant operation Be sure oil is visible at the top and center of window on side of bracket and maintain this level at all times Motor lubrication caution Stop motor before lubricating Do not over oil or spill oil on resilient motor rings This motor has been lubricated properly at the factory At the start of each following heating season however on motors with oil cups add 15 drops sa...

Page 3: ...tion with and adherence to the National Electrical Code nec and National Fire Protection Association nfpa standards and to local codes are required It is important to observe safety precautions to protect personnel from possible injury Person nel should be instructed for handling each of the following Insulate all connections carefully to prevent grounding or short circuits Reinstall all conduit a...

Page 4: ...rface board communicates with the motor control to operate the motor in speed mode The operating parameters are programmed in the eeprom of the motor control not the PerfectSpeed User Interface On power up the interface board extracts the operating parameters from the motor control Parameter categories include Motor direction Motor mode of operation Motor output display Motor profile PerfectSpeed ...

Page 5: ...ethods of setting the Input Demand See Table 3 for definitions of the two options Table 4 Setting input demands options set with on board potentiometer set with 0 V to 10V DC control signal AC line connections Check to see if the line voltage matches the nameplate voltage connections green verde screw ground Configuration scenarios This section provides examples of different configurations and bri...

Page 6: ...t running If the PerfectSpeed motor with User Interface isn t running perform the following checks 1 Ensure that both the PerfectSpeed motor and User Inter face have proper line voltage for intended application 2 Turn the User Interface on board potentiometer fully clock wise 100 demand and check to see if the motor runs 3 If 0V to 10V DC input is in use disconnect the external input from the User...

Page 7: ...ains definitions for acronyms and terms oc curring in the Operation Configuration and Troubleshooting Manual or in the PerfectSpeed User Interface ccw Counter clockwise direction Motor rotation is viewed from the lead end of the motor not the shaft cw Clockwise direction Motor rotation is viewed from the lead end of the motor not the shaft dE Demand The set point of the motor ecm Electronically Co...

Page 8: ...fined by the maximum operating parameters Also called motor slew rate Motor Speed Limit A user defined limit in rpm equating to 100 demand in Speed Mode of Operation Motor Power Limit A user defined limit in Watts of output power The parameter cannot be less than 25 of the value in the Motor Table Refer to Appendix A Motor Charts Motor Torque Limit A user defined limit in lb in equating to 100 dem...

Page 9: ...installation operating instructions In line circulating pumps 9 ...

Page 10: ...hester united kingdom m11 2et 44 0 8444 145 145 93 east avenue north tonawanda new york u s a 14120 6594 1 716 693 8813 23 bertrand avenue toronto ontario canada m1l 2p3 1 416 755 2291 unit 903 888 north sichuan rd hongkou district shanghai china 200085 86 0 21 5237 0909 rua josé semião rodrigues agostinho 1370 galpão 6 embu das artes sao paulo brazil 55 11 4781 5500 b i r m i n g h a m heywood wh...

Reviews: