Each status and selection of this screen is explained below.
COMBUSTION AIR STATUS
Blower On: The combustion air blower has been energized.
Air On: The combustion air proving switch has been made.
BURNER AND FUEL STATUS
Spark On: The burner spark igniter has been energized.
Fuel On: The main fuel valves have been energized.
WATER CONTROL STATUS
Water On: The inlet water valve is energized.
Pump On: The transfer pump is energized.
(Not Shown) Pump Speed: This will display when the transfer pump is energized and switch between Low and High
depending on level in the lower basin.
STATUS READOUTS
Flame Signal: Strength of the flame signal in a scale of 0-100%.
Brn Output: Commanded output of the burner in a scale of 0-100%.
Fuel Actr Pos: Position of the fuel actuator in degrees.
Air Actr Pos: Position of the air actuator in degrees.
Outlet Temp: Outlet water temperature in degrees Fahrenheit.
Basin Level: Level of the lower basin corresponding with the float switches in the lower basin. Burner Status: Phase
of the burner management system.
MANUAL RUN CONTROL
When the heater is in manual run mode use the START and STOP buttons to control the heater.
RUN MODE
The Flo-Direct has two run modes: MANUAL and AUTO. This panel is used to switch between them. In MANUAL
mode the heater is started and stopped by the buttons on the panel above (manual run control). Pressing the AUTO
RUN button will switch to auto run mode and the heater will start and stop via an external input. This can be float
switches in a storage tank, a remote run control relay or a remote run bit via Ethernet connection.
NOTE:
If running the heater in MANUAL mode it will not STOP unless the STOP button is pushed. Constant
monitoring is required running in this mode.
43