Armstrong Air RP16AC Series Installation And Maintenance Instructions Manual Download Page 18

Page 18  of  22

507635-05

Issue 2245

Diagnostic LEDs

The defrost board uses two LEDs for diagnostics. The 

LEDs flash a specific sequence according to the condition 

as shown in Table 4.

Defrost Board Diagnostic LEDs

Green LED 

(DS2)

Red LED 

(DS1)

Condition

OFF

OFF

No Power to Control

Simultaneous Slow FLASH

Normal Operation /  

Power to Control

Alternating Slow FLASH

5-min Anti-Short-Cycle Delay

ON

Slow FLASH

Low Pressure Switch Ignored 

(Low Ambient)

Fault & Lockout Codes

OFF

Slow FLASH

Low Pressure Switch Fault

OFF

ON

Low Pressure Switch Lockout

Slow FLASH

OFF

High Pressure Switch Fault

ON

OFF

High Pressure Switch Lockout

Table 4. Defrost Control (CMC1) Diagnostic LEDs

System Performance

This equipment is a self-contained, factory optimized 

refrigerant system, and should not require adjustments to 

system charge when properly installed. If unit performance 

is questioned, perform the following checks.

Ensure unit is installed per manufacturer’s instructions and 

that line voltage and air flow is correct. Refer to Table 5 

through Table 7 for proper performance value. The indoor 

metering device varies by model. 

If the measured performance value varies from table value 

allowance, check internal seals, service panels and duct 

work for air leaks, as well as restrictions and blower speed 

settings. If unit performance remains questionable, remove 

system charge, evacuate to 500 microns, and weigh in 

refrigerant to nameplate charge. It is critical that the exact 

charge is re-installed. Failure to comply will compromise 

system performance. 

If unit performance is still questionable, check for 

refrigerant-related problems, such as blocked coil or 

circuits, malfunctioning metering device or other system 

components.

Maintenance

Before performing maintenance operations on the 

system, shut off all electrical power to the unit. Turn off 

accessory heater power switch if applicable. Electrical 

shock could cause personal injury or death.

WARNING

Periodic inspection and maintenance normally consists of 

changing or cleaning the filters and cleaning the evaporator 

coil. On occasion, other components may also require 

cleaning.

Filters

Filters are not supplied with the unit. Inspect once a month. 

Replace disposable or clean permanent type as necessary. 

Do not replace permanent type with disposable.

Motors

Indoor and outdoor fan and vent motors are permanently 

lubricated and require no maintenance.

Some models may be equipped with a permanent magnet, 

constant torque indoor blower motor. These motors remain 

energized and are controlled by 24V signals. For high 

static applications, use tap 3 for cooling speed and tap 5 

for heating speed. Refer to the heater installation label for 

limitations to blower tap selection on heating speeds.

Evaporator Coil

Dirt and debris should not be allowed to accumulate on 

the evaporator coil surface or other parts in the air circuit. 

Cleaning should be as often as necessary to keep coil 

clean. Use a brush, vacuum cleaner attachment, or other 

suitable means. If water is used to clean the coil, be sure 

the power to unit is shut off prior to cleaning. 

Care should 

be used when cleaning the coil so that the coil fins are 

not damaged.

Do not permit the hot condenser air discharge to be 

obstructed by overhanging structures or shrubs.

Condenser Coil

Clean condenser coil annually with water and inspect 

monthly during the cooling season.

Condenser coil may need to be cleaned at startup in 

case oil from the manufacturing process is found on the 

condenser coil.

Summary of Contents for RP16AC Series

Page 1: ...tates the Canadian Electrical Code Part 1 CSA 22 1 latest edition in Canada and any state or provincial laws or local ordinances Local authorities having jurisdiction should be consulted before instal...

Page 2: ...T POWER ENTRY 5 86 3 07 6 20 17 07 13 44 13 44 14 32 6 20 40 89 21 63 13 21 TYPICAL DRAIN LOCATION CONDENSATE DRAIN 3 4 NPT SIDE VIEWS 11 49 2 33 47 66 1 98 16 77 2 48 14 02 47 66 POWER ENTRY POWER EN...

Page 3: ...POWER ENTRY 14 32 4 20 3 76 6 20 17 07 18 19 18 19 6 20 44 89 21 63 13 21 TYPICAL DRAIN LOCATION CONDENSATE DRAIN 3 4 NPT SIDE VIEWS TOP VIEW POWER ENTRY POWER ENTRY RETURN AIR 2 11 19 49 2 39 2 33 1...

Page 4: ...x 5 5 8 in 140 x 31 mm Opening for Power Entry Through Unit Base 3 x 13 in 76 x 330 mm 44 3 8 1127 44 3 8 1127 16 7 8 429 13 7 8 352 2 1 8 54 11 1 2 287 SUPPLY OPENING RETURN OPENING 8 203 14 356 18 4...

Page 5: ...Unit Base 5 1 2 x 5 5 8 in 140 x 31 mm Opening for Power Entry Through Unit Base 3 x 13 in 76 x 330 mm 52 7 8 1343 44 3 8 1127 19 1 2 380 11 1 2 287 19 1 2 380 2 1 8 54 11 1 2 287 SUPPLY OPENING RETU...

Page 6: ...ements NOTE CLIPLOCK CORNER DETAIL CURB PROFILE 1 1 2 1 3 4 1 11 5 8 2 1 8 14 1 3 1 2 13 1 2 44 3 8 Bottom Curb Assembly Opening for Power Entry thru base 11 5 8 5 1 2 5 3 4 3 5 8 1 3 8 17 1 4 13 7 8...

Page 7: ...ements NOTE CLIPLOCK CORNER DETAIL CURB PROFILE 1 1 2 1 3 4 1 19 5 8 11 5 8 2 1 8 19 3 8 11 5 8 14 23 1 8 1 5 1 2 5 3 4 3 1 2 3 1 2 13 1 2 6 7 8 52 7 8 44 3 8 Insulated Panels Opening for Power Line E...

Page 8: ...89 2 1 8 54 Built In Rain Diverter Not Shown Front Flange 8 203 NOTE Minimum Height 4 102 Built In Drip Edge Unit Base Rail Unit Base Rail Clips 4 Sides and Back Flange 6 152 Unit Base Rail Clips 4 Su...

Page 9: ...designed to be located outdoors with sufficient clearance for free entrance to the air inlet and discharge air openings The location must also allow for adequate service access The unit must be insta...

Page 10: ...with a forklift The lengths of the forks of the forklift must be a minimum of 42 inches The unit operating conditions including airflow cooling operation ignition input rate temperature rise and vent...

Page 11: ...by the installer Refer to the unit rating plate for maximum over current protection and minimum circuit ampacity as well as operating voltage The power supply must be sized and protected according to...

Page 12: ...be discarded 2 Install the duct system to the unit For downflow duct systems 1 Remove the duct covers on side of the unit Keep the screws and the covers as they will be re installed later 2 Remove th...

Page 13: ...te drain line must be properly trapped routed to a suitable drain and primed prior to unit commissioning NOTE Install drain lines and trap so they do not block service access to the unit See Figure 4...

Page 14: ...11 full times plus one fast or half flash At times the light may appear to flicker or glow This takes place when the control is communicating with the motor between cycles This is normal operation Rea...

Page 15: ...ssor and outdoor fan Second stage heating is initiated when the thermostat energizes Y2 or when the outdoor ambient temperature is below the lock in temperature see Second Stage Lock In section The re...

Page 16: ...dition NOTE Within a single room thermostat demand if 5 strikes occur the board will lockout the unit Control board 24 volt power R must be cycled OFF or the TEST pins on board must be shorted between...

Page 17: ...brate another defrost cycle will be initiated after 45 minutes of heating mode compressor run time Once the control board is calibrated it initiates a demand defrost cycle when the difference between...

Page 18: ...rcuits malfunctioning metering device or other system components Maintenance Before performing maintenance operations on the system shut off all electrical power to the unit Turn off accessory heater...

Page 19: ...18 342 366 392 419 446 475 504 60 258 277 298 319 341 365 391 415 442 470 499 Table 5 Cooling Performance AC Models 80 DB 67 WB Deg Return Air Air Temperature Entering Evaporator Coil Degree F COOLING...

Page 20: ...82 90 102 108 118 129 36 27 32 38 46 50 56 71 79 91 96 106 115 48 34 38 43 50 54 61 76 84 97 103 113 124 60 36 41 46 55 58 65 80 87 99 104 113 123 24 Liquid 309 304 300 299 299 301 310 317 330 336 34...

Page 21: ...507635 05 Page 21 of 22 Issue 2245 Wiring Diagrams Figure 8 AC Wiring Diagram...

Page 22: ...Page 22 of 22 507635 05 Issue 2245 Figure 9 HP Wiring Diagram...

Reviews: