Equipment Connections

Ductwork

• 

Air distribution ductwork must be designed to allow 

for the specified air flow without excessive pressure 

levels. The unit should be situated as close as 

possible to the point of use to prevent unnecessary 

long runs of ductwork.

• 

Sheetmetal ductwork is recommended for use with 

all Armcor Air Solutions equipment.

• 

Ducts should be insulated in accordance with BCA 

Section J-5.

• 

Fan inlet conditions can affect the fan performance, 

particularly where duct bends cause a non-uniform 

flow and swirl at the inlet. To reduce losses due 

to fan systems effect, adequate length of straight 

duct between any elbow and the fan inlet should be 

provided or turning vanes used in the elbow.

• 

Poor fan outlet conditions will also affect the fan 

performance. Armcor recommends a minimum of 

1000mm of straight duct directly after the fan outlet.

Filters

• 

50mm panel filters are a minimum recommendation 

for all equipment.

•  Filters 

MUST

 be fitted to the fresh air inlet. Where 

there is no provision for filters within the unit, the 

installing contractor is responsible to incorporate 

filters in the ductwork system external to the unit.

• 

It is recommended that temporary disposable filters 

are used during construction & commissioning.

• 

Where a Heat Exchanger is incorporated in the 

equipment, warranty will be void if filters are not 

fitted.

IMPORTANT: NEVER OPERATE A UNIT WITHOUT FILTERS 

FITTED TO THE FRESH AIR INTAKE.

Electrical Requirements

• 

The power requirement and voltage are detailed on 

the equipment technical specifications (available at 

armcor.com.au

) and are on the identification/serial 

number plate attached to each unit.

• 

An electrical diagram is attached to the electrical box 

on the unit.

Mains Power Supply and Fusing

• 

A single-phase power supply rated at 240v (+/- 5%) 

50Hz or a 3-phase power supply rated at 415 volts is 

required to operate the unit within manufacturer’s 

tolerance. Check the name plates for correct voltage.

• 

We recommend an isolator be mounted externally 

to the unit (not supplied) and a suitably sized 

circuit breaker mounted back at the distribution 

board to provide local isolation during service and 

maintenance periods.

• 

Main cables and control circuit wires are to be 

connected as per wiring diagram.

• 

All wiring must comply with relevant local wiring 

regulations.

• 

The unit requires a main circuit breaker capable of 

handling the full load of the unit and selected in 

accordance with SAA Wiring Rules.

• 

All wiring is to be independently colour coded.

• 

Single phase fan motors are internally protected and 

there is no need for external overloads.

  HTC – Humidity and Temperature Control Unit Installation and Operation Manual 2021                    7

Summary of Contents for HTC500

Page 1: ...Installation and Operation Manual HTC Humidity Temperature Control Unit HTC500 HTC6000 M ADE A U STRALI A N Manufactured byArmcor M ADE A U STRALI A N Manufactured byArmcor...

Page 2: ...ments Mains Power Supply and Fusing Standard Equipment Layout 8 Features 9 General Maintenance 11 General Monthly Maintenance Schedules Guide to How Frequency According to Usage is Established Three M...

Page 3: ...stems cope well with recirculated return air temperatures up to 24 C the HTC can be designed to cope with much higher air on conditions Humidity control involves reducing the temperature below dew poi...

Page 4: ...eat recovery and or air handling equipment Installing and servicing equipment can be hazardous due to electrical and mechanical components When working on equipment observe precautions in all literatu...

Page 5: ...he supply and return ducts to reduce any vibration transfer Fresh Air Inlet The location of the fresh air inlets must adhere to the Australian Standards AS 1668 2 The fresh air intake should be positi...

Page 6: ...s and guidelines Wear safety goggles work gloves work boots and protective clothing All external units are provided with substantial lifting lugs on each corner at the base frame NOTE All units should...

Page 7: ...issioning Where a Heat Exchanger is incorporated in the equipment warranty will be void if filters are not fitted IMPORTANT NEVER OPERATE A UNIT WITHOUT FILTERS FITTED TO THE FRESH AIR INTAKE Electric...

Page 8: ...Standard Equipment Layout Supply Air Fresh Air Condensor Fan Condensor Reheat EC Plug Supply Fan DX Coil Filters 8 HTC Humidity and Temperature Control Unit Installation and Operation Manual 2021...

Page 9: ...peration after the unit has stabilised Compressor Control Board TX Valve All TX valves have adjustment for super heat settings 8 11K is acceptable for R407C and R4100 gases HTC Humidity and Temperatur...

Page 10: ...ransport and for the operation of the compressor Electrical Connection Tighten all electrical connections before starting and commissioning unit Phase Failure Relay Fan Control Card Adjust pots for sp...

Page 11: ...ndensate drain if applicable for free drainage Guide to How Frequency According to Usage is Established Disposable Corrugated Filters Ordinary disposable corrugated filters should last approximately o...

Page 12: ...riginal service call costs in identifying a warranty claim Freight and travel changes for work performed or parts supplied outside of all capital cities in Australia Field wiring refrigerant pipe run...

Page 13: ...ng transport Leak test all caps and pressure connections after commissioning Starting Unit Check fans and Air Flow Turn on all circuit breakers Turn on control circuit and activate fans Turn on supply...

Page 14: ...Amps Indoor Fan Motor Amps Boost Heater Element Amps Total Unit Amps Thermostat Settings C Thermostat Operating Correctly Y N Contactors Relays Operating Correctly Y N All Terminals Checked for Tightn...

Page 15: ...Fresh Air Temperature C DB C WB 2 Air off Heat Exchanger C DB C WB 3 Air off Cooling Coil C DB C WB 4 Air off Heat Exchanger Supply Air C DB C WB Notes HTC Humidity and Temperature Control Unit Insta...

Page 16: ...u P 03 8301 9200 109 111 Northcorp Blvd Broadmeadows Vic 3047 2021 Armcor Air Solutions reserves the right to alter products and specifications without notice and does not accept responsibility for po...

Reviews: