General Installation 
Information 

1. 

What Does it Do? 

The ATS1203/ATS1204 provides zone expansion with 8 to 
32 zones to ATS Control Panels with a built-in Power 
Supply of max. 3A (total). Both the Mains Power Supply 
and the Battery are monitored. The DGP also provides for 
8 to 32 outputs occupying 2 DGP addresses when selected 
to support more then 16 outputs. 

The ATS1203/ATS1204 functionality is similar to the 
ATS1201. 

Setup of the ATS1203/ATS1204 is possible using the built-
in menu that can be accessed through Titan or the ATS 
Control Panel menu 28. 

2. 

Mains Power connection 

Use the Mains Connector Terminal for connecting the 
mains-supply. A fixed cable or a flexible mains leading to 
an earthed mains outlet can be used. In case fixed wiring is 
used, insert a dedicated circuit breaker in the power 
distribution network. In all cases, the mains connection has 
to comply with local regulations. 

 

 
 

IMPORTANT: 

Disconnect the mains power before opening 
the cabinet! 

 

Disconnect AC mains plug from AC 
Mains wall socket.      Or 

 

Disconnect the mains with the 
dedicated circuit breaker. 

3. Mounting

 

The unit is mounted with screws or bolts through the four 
mounting holes in the base. 

Ensure that the unit is mounted on a flat, solid, vertical 
surface such that the base will not flex or warp when the 
mounting screws/bolts are tightened. 

Leave a 50-mm clearance between equipment enclosures 
mounted side by side and 25 mm between the enclosure 
and the sidewall. 

The battery mounting facility inside the housing is only 
useful for steady state use of the control panel. Remove 
the battery for transport of the control panel. 

Ensure that the wire terminals are isolated. Use tie wraps 
to prevent contact with any other wires or circuits in case 
wires break. 

4. General 

installation 

guidelines 

The ATS1203/ATS1204 has been designed, assembled 
and tested to meet the requirements related to safety, 

emission and immunity with respect to environmental 
electrical and electromagnetic interference, as of current 
relevant Standards. 

If the following guidelines are followed, the system will give 
many years of reliable service. 

In addition to the following guidelines, during the 
installation of the ATS1203/ATS1204, it is essential to 
follow any country dependent installation requirements of 
local applicable standard. Only a qualified electrician or 
other suitable trained and qualified person should attempt 
to wire this system to the mains or to the public telephone 
network. 

1. 

Ensure that there is a good earth available for the 
alarm system. 

2. 

Maintain a separation between the low voltage and 
mains supply cables. Use separate points of cable 
entry to the control panel cabinet. 

3. 

If, the upper and/or lower cabinet entry cable holes 
are used to route wiring into the control panel, 
always use a proper pipe fitting system by means of 
an appropriate conduit and junction box. For this 
purpose, use only materials of suitable flammability 
class (HB or better). 

4. 

For Mains Power connection, use the mains 
connector terminal either through a permanent 
wiring or a flexible mains cable to an earthed mains 
outlet. Always use cable ties to fix mains cable, at 
the dedicated fixing point provided near the mains 
terminal connector. 

a. 

In case of permanent fixed wiring, insert an 
easily accessible, dedicated bipolar circuit 
breaker in the power distribution network. 

b. 

Never attempt to solder mains connection 
wires end where they will be wired to the 
terminal connectors. 

5. 

Avoid loops of wire inside the control panel cabinet 
and route cables so that they do not lie on top or 
underneath the printed circuit board. The use of 
cable ties is recommended and improves neatness 
of the wiring within the box. 

6. 

The battery used with this unit, must be made of 
materials of suitable flammability class (HB or 
better). 

7. 

Any circuit connected either directly to the on board 
relay’s contact or to external relay’s contact through 
the on board electronic output, must be of SELV 
(Safety extra low voltage) operating circuit. 

a. 

Mains switching relay must not be fitted 
inside the control panel cabinet 

b. 

Always place a suppression diode (e.g. a 
1N4001) across the relay coil 

c. 

Use only relay with good insulation between 
the contacts and the coil. 

8. 

The minimum clearance between equipment 
closures is 50 mm (between equipment vents). 

Summary of Contents for ATS1203

Page 1: ... 2003 GE Interlogix B V 1051411 All Rights Reserved 10 2004 ATS1203 ATS1204 8 32 Zone DGP with 3A power supply ...

Page 2: ...2 ...

Page 3: ...ut State Input No 17 Normal 113 0 Exit 32 Open 226 0 Exit 3 DGP settings 0 Exit Menu 1 DGP Address Change 0 Exit Battery Load OFF Change 0 Exit Mains Check ON Change 0 Exit Static Outputs Change 0 Exit 4 Factory Reset 0 Exit Menu Factory Default Yes No ATS1203 Vx x DGP 0 EXIT Menu ...

Page 4: ... guidelines are followed the system will give many years of reliable service In addition to the following guidelines during the installation of the ATS1203 ATS1204 it is essential to follow any country dependent installation requirements of local applicable standard Only a qualified electrician or other suitable trained and qualified person should attempt to wire this system to the mains or to the...

Page 5: ...Normally closed panel tamper contact 8 Normally closed panel tamper contact 9 Normally closed Alarm Contact 10 Normally Closed Tamper Contact 11 Interface to ATS1202 input expanders 12 External 8 Ohm siren speaker or siren 13 1K resistor must be fitted if external siren not connected 14 Clock out Interface to plug on output expansion or 4 way non clocked output expansion e g ATS1810 15 Dipswitch t...

Page 6: ...protected against variations in earth potential Shielding The shielding of all shielded cables used in the system should only be connected at ONE side to one common earthing point in a building see Fig 3 If a shielded databus cable is routed via more than one plastic device the shielding from incoming and out going cable has to be connected Explanation of fig 1 Mains power with local earth 2 Mains...

Page 7: ...xp Allows for max 32 inputs 16 outputs to be connected Shows as DGP n exp where n is the selected DGP address in menu 1 DGP status 2 DGP Addresses Allows for max 32 inputs outputs to be connected but requires DGP polling to be enabled for the DGP address and the DGP address 1 Shows as DGP n m where n is the selected DGP address and m is the address 1 in menu 1 DGP status 2 Battery Load Select if t...

Page 8: ...5 2225 2025 1675 1625 Aux 40 220 330 500 550 VdS C 60 24 Battery 2685 2500 2395 2225 2175 4 General Feature Specifications End of line resistor standard 4 7 kΩ 5 0 25 W 2 2 kΩ or 10 kΩ Standard on board output Ext siren J13 S S Electronic output Rating 1 A at 13 8 VDC Housing Dimensions ATS1203 370 x 475 x 160mm ATS1204 460 x 475 x 160mm Colour Beige Operating temperature 0 to 50 C certified 5 40 ...

Page 9: ...ur notamment en matière de sécurité électrique et d immunité aux interférences électromagnétiques Installée dans les rêgles de l art cette centrale vous donnera satisfaction de nombreuses années En plus de ces recommandations d installation il est essentiel de respecter les normes en vigueur et de ne faire effectuer les raccordements au réseau électrique et téléphonique par du personnel qualifié 1...

Page 10: ...t fermé 9 Contact d alarme normalement fermé 10 Contact d autoprotection normalement fermé 11 Connecteur vers les extensions d entrée ATS1202 12 Haut parleur de sirène externe 8 Ohm ou sirène 13 Une résistance d 1 K doit être installée si la sirène externe n est pas connectée 14 Sortie de données pour connecter des cartes de sorties ou une simple carte 4 relais 15 Dipswitch d adressage du DGP 16 C...

Page 11: ...protégé contre les différences de potentiel existant sur la terre Blindage des câbles Le blindage des câbles utilisés dans le système doit être raccordé à une seule terre commune du bâtiment et d UN SEUL côté voir la figure Si le câble du bus de données blindé passe par plusieurs modules en plastique la continuité du blindage du câble devra être assurée sur toute sa longueur Explication de figure ...

Page 12: ...ure Le menu 3 permet le paramétrage du DGP Utiliser la touche MENU pour changer un paramètre Utiliser ENTER pour accepter ce paramètre et aller à la prochaine option 1 DGP configuration choix du nombre de zones et de sorties options possibles 1 DGP Address DGP 16 zones 16 sorties Vu dans le menu 1 comme DGP n où n est le n du DGP valeur par défaut 1 DGP exp DGP 32 zones 16 sorties Vu dans le menu ...

Page 13: ...h Courant mA Capacité batterie niveau d agrément Décharge Recharge Sortie 7 2Ah 18Ah 25Ah 36Ah 50Ah Aux 490 1300 1800 1800 1800 EN 1 2 12 72 Batterie 2235 1425 925 925 925 Aux 40 220 330 500 550 EN 3 4 60 24 Batterie 2685 2500 2395 2225 2175 Aux 110 360 550 850 1000 Nfa2p ΙΙ 36 30 Batterie 2615 2350 2200 1875 1725 Aux 20 150 230 380 580 Nfa2p ΙΙΙ 72 30 Batterie 2700 2600 2500 2345 2100 Aux 150 500...

Page 14: ...ion auxiliaire sirène F1 A 20x5 F2 Batterie F3 A 20x5 Fusible secteur F630 mA 20x5 ATTENTION Avant de retirer le fusible secteur déconnecter le courant secteur au disjoncteur principal de l installation voir page 8 ...

Page 15: ... test per soddisfare gli standard correnti relativi alla sicurezza elettrica alla emissione e alla immunità alle interferenze elettriche ed elettromagnetiche ambientali Il rispetto delle seguenti indicazioni contribuirà a garantire un efficace e duraturo funzionamento delle centrali per diversi anni Oltre alle presenti indicazioni è essenziale rispettare durante l installazione delle centrali ATS ...

Page 16: ...tiera LCD ATS1105 l interruttore TERM non posizionato su ON 4 Alimentazione 12 V separata Necessaria se la stazione di inserimento RAS è distante più di 100 metri dalla centrale o dal concentratore DGP più vicino Connettere a del bus di dati 5 Il tipo di cavo preferito è il WCAT 52 2 coppie twistate 6 Cavallotto TERM montato ultimo dispositivo sul bus di dati locale 7 Messa a terra per la schermat...

Page 17: ...cette per assicurare un corretto cablaggio In ogni caso sarà necessario rispettare tutte le normative vigenti in materia 14 Messa a terra vedere figura ATTENZIONE È necessario seguire la procedura di messa a terra correttamente Messa a terra di un contenitore con più dispositivi al suo interno Ogni dispositivo progettato per il sistema ha predisposti sul circuito stampato punti di contatto per la ...

Page 18: ...o corrente ecc Per vedere tutte le informazioni entrare nel menu e premere ENTER per vedere il successivo argomento Menu 2 Stato Ingressi vedere Figura Mostra il corrente stato di tutti gli ingressi che sono stati abilitati e il valore digitale degli stati Il campo che è disponibile può essere visto nello Stato DGP Il numero degli ingressi usati è in relazione all indirizzo impostato Vedere numera...

Page 19: ...capacità max batteria Ricaricabile al piombo 2 x 25Ah 12 V nom BS129 1 Consumo circuito centrale 75 mA at 13 8 V 5 Certificato IMQ II livello con kit antirimozione ST580 3 Uscita batteria disponibile basata sul backup Tempo h Corrente mA Capacità batteria Certificaz ione Scarica Carica Uscita 7 2Ah 18Ah 25Ah 36Ah 50Ah Ausiliaria 490 1300 1800 1800 1800 EN 1 2 12 72 Batteria 2235 1425 925 925 925 A...

Page 20: ...ientali Grado di protezione IP IP30 5 Fusibili F4 Alimentazione ausiliaria e sirena F2 A 20x5 F5 Batteria F3 A 20x5 Fusibile di rete F630 mA 20x5 1 il fusibile di rete è integrato nella morsettiera di connessione per la rete 230V ATTENZIONE Prima di agire su questo fusibile rimuovere l alimentazione di rete vedere a pag 15 ...

Page 21: ...21 ...

Page 22: ...22 ...

Page 23: ...23 ...

Page 24: ...t 7 6003 DH Weert The Netherlands EU Representative Concerning EMC Safety A sample of the product has been tested by GE Interlogix Kelvinstraat 7 6003DH Weert The Netherlands Bicon Steenovenweg 5 5708HN Helmond The Netherlands Test report reference ATS1203_CE_Spec_1_3 CEQP_ATS1203_ATS1204 GEI 20031127 N1 Applied standards EN50130 4 1995 A1 1998 EN61000 6 3 2001 EN55022 1998 A1 2000 A2 2003 EN61000...

Reviews: