![Aritech 2000 Series Installation Manual Download Page 35](http://html.mh-extra.com/html/aritech/2000-series/2000-series_installation-manual_2971989035.webp)
2000 SERIES SENSORS INSTALLATION GUIDE Revision 3.1 June 1997
3.2.1 Standby Current
LOOP 1
STANDBY CURRENT
Device
Code
Number of
Devices
Standby
Current (A)
Total Standby
Current (A)
IONISATION
DI2052
0,00025
DI2072
0,00025
OPTICAL
DP2051
0,00025
DP2071
0,00025
HEAT
DT2053
0,00025
DT2073
0,00025
MCP
DM2000
0,00025
ZONE MONITOR
IU2051
0,0045
IND. CIRCUIT CONTROL
IU2080
0,00035
4I / 4O
IU2034
0,00025
2I / 2O
IU2032
0,00025
2I / 1O
IU2031
0,00025
4I
IU2014
0,00025
Table 2 : Device Quiescent Current
3.2.2 Alarm Current
LOOP 1
ALARM CURRENT
Number of
Devices
Alarm
Current (A)
Total Alarm
Current (A)
Define numbers of sensors that
can go into alarm at the same time
10
0.004
0.04
Table 3 : Device Alarm Current