1X-F Series Quick Installation Guide 

Fire routing outputs 

EN 54-2 

OUT4 

EN 54-2 Scandinavia 

OUT4 

NEN 2535 

OUT3 (automatic) 
OUT4 (manual) 

Mains fuses and batteries 

Mains fuses 

110 VAC [1] 

T 3.15A 250V 

240 VAC 

T 2A 250V 

[1] See your installation manual for 110 VAC operation requirements. 

Batteries 

Two- and four-zone panels  12 V, 7.2 Ah 

Eight-zone panel 

12 V, 7.2 Ah or 12 V, 12 Ah 

Basic configuration 

Default configuration 

Operating mode 

01 (EN 54-2) 

Zone end-of-line 

Passive 

Zone type 

Mixed 

The configuration controls are located on the control 
panel interface. 

Configuration controls 

Button Function 

Scroll to the next configuration menu on the seven-
segment display. 

Scroll to the next configuration value for the active menu 
on the seven-segment display. 

Scroll to the previous configuration menu on the seven-
segment display. 

Scroll to the previous configuration value for the active 
menu on the seven-segment display. 

Enter 

Confirm a menu selection or a value selection entry. 

The configuration controls are also used to enter the 
user level password. The seven-segment display is 
visible when the control panel cover is removed. 

Seven-segment display 

 

LED Indications 

Mode 

Steady: Select a 

menu 

using buttons 1 and 3. 

— or — 
Flashing: Select a 

submenu 

using buttons 1 and 3. 

Value 

Steady: Select a 

value 

using buttons 2 and 4. 

Basic configuration menu 

Selected options from the basic configuration menu are 
shown below. The default password for basic 
configuration is 3333. 

 

Display Menu 

Values 

 

Basic default 
configuration 

01 to 32 

 

Sounder delay 

00 to 10 minutes  

 

Fire routing delay 

00 to 10 minutes 

 

Extended fire routing 
delay 

00 to 10 minutes 

 

Restore previous 
configuration 

 

 

Restore factory 
configuration 

 

 

Exit without saving 

 

 

Exit and save 

 

 