background image

9

AUS

The following instructions are provided for qualified
installers so that they may accomplish installation,
adjustment and technical maintenance operations correctly
and in compliance with current regulations and standards.
Important: the appliance should be disconnected from
the mains electricity supply before any adjustment,
maintenance, etc. is carried out.
 Maximum caution should
be used should it be necessary to keep the appliance
connected to the electricity supply.

The dimensions of the appliance are given in the figure on
page 2. For trouble-free operation of appliances installed
in housing units, the minimum distances shown in fig.5
should be observed. Adjacent surfaces and the wall at the
rear should also be able to withstand an overheating
temperature of 65 °C.

Prior to installing the cooker, 95 ÷ 155 mm high supporting
feet (provided) should be fitted into the holes to be found
in the bottom of the cooker (fig.6). These feet are screw-
adjustable and whenever necessary should be used to
make sure the cooker stands level.

Stabilising chain"I"
Fit one end of the safety chain to either side of the cooker
and secure the other end to the wall stud or the floor.
Ensure that the cooker is stable and cannot be tilted
forward.
WARNING: servicing shall only be carried out by authorised
personnel.

Positioning
This appliance may only be installed and operated in
permanently ventilated rooms in compliance with current
standards. The following requirements must be observed:
• The appliance must discharge combustion products into

a special hood, which must be connected to a chimney,
flue pipe or directly to the outside (fig.7).

• If it is impossible to fit a hood, the use of an electric fan

is permitted, either installed on a window or on an external
wall, which must be switched on at the same time as the
appliance.

Kitchen ventilation
The air flow into the room where the appliance is installed
must equal the quantity of air that is required for regular
combustion of the gas and for ventilating the same room.
Air must be taken in naturally through permanent apertures
made in the outside walls of the room or through single or
branching collective ventilation ducts in compliance with

INSTALLATION

fig.5

fig.6

• total free cross section of passage of at least 6 cm² for

every kW of rated heating capacity of the appliance, with
a minimum of 100 cm² (the heating capacity is indicated
on the rating plate);

• it must be made in such a way that the aperture, both on

the inside and outside of the wall, cannot be obstructed;

• it must be protected, e.g. with grates, wire mesh, etc. in

such a way that the above-mentioned free section is not
reduced;

• it must be situated as near to floor level as possible.

Detail A

Adjacent

Room to be

room

 ventilated

A

Examples of ventilation holes

Enlarging the ventilation slot

for comburant air

 between window and floor

fig. 8A

fig. 8B

The air inflow may also be obtained from an adjoining room,
provided the latter is not a bedroom or a room where there
is a risk of fire, such as warehouses, garages, fuel stores,
etc. and is ventilated in compliance with the current
standards and regulations. Air from the adjoining room to
the one to be ventilated may be made to  pass freely through
permanent apertures with a cross section at least equal to
that indicated above. These apertures may also be obtained
by increasing the gap between the door and the floor
(fig.8B). If an electric fan is used for extracting the
combustion products, the ventilation aperture must be
increased in relation to its maximum performance. The
electric fan should have a sufficient capacity to guarantee
an hourly exchange of air equal to 3 ÷ 5 times the volume
of the kitchen. Prolonged, intensive use of the appliance
may require extra ventilation, e.g. an open window or a
more efficient ventilation system by increasing the
extraction power of the electric fan if installed. Liquid
petroleum gas descends towards the floor as it is heavier
than air. Apertures in the outside walls in rooms containing
LPG cylinders should therefore be at floor level, in order to
allow any gas from leaks to be expelled. Do not store LPG
cylinders (even when empty) in basements or rooms below
ground level; it is advisable to keep only the cylinder in use
in the room at any one time and connected far from heat
sources which could raise its temperature to above 50 °C.

fig.7

In a chimney stack or branched flue

Directly to the outside

(exclusively for cooking appliances)

current standards and regulations. The air must be taken
directly from the outside, from an area far from sources of
pollution. The ventilation aperture must have the following
characteristics (fig.8A):

Summary of Contents for XC 902 GH DC AUS

Page 1: ...XC 902 GH DC AUS Cooker Instructions for use and installation...

Page 2: ...hose of the mains electricity and gas supplies 8 During operation the oven glass door and adjacent parts of the appliance become hot Make sure therefore that children do not touch the appliance For gr...

Page 3: ...election I Stabilising chain 30 cm long N Splashback removable A Auxiliary gas burner B Semi rapid gas burner C Rapid gas burner D DC DR gas burner R Support Grid for Cookware M Control Knobs for Gas...

Page 4: ...he burners To obtain maximum efficiency from the burners it is advisable to only use pans with a diameter suitable for the burner being used so that the flame does not extend beyond the pan base see f...

Page 5: ...ly indicated for meats which should remain tender on the inside To grill turn the selector knob H to one of these positions grill maxigrill maxigrill fan During grilling do not set the thermostat knob...

Page 6: ...om the power supply To extend the life of your oven it must be cleaned frequently keeping in mind that The self cleaning panels if present and the enameled parts should be washed with warm water abras...

Page 7: ...nd of the set cooking time The 4 figure luminous display showing the actual time and the programming times also shows the current state of the oven by means of the following symbols Oven on Minute min...

Page 8: ...must not be too runny as this will result in prolonged cooking times In general Pastry is too dry Increase the temperature by 10 C and reduce the cooking time Pastry dropped Use less liquid or lower t...

Page 9: ...a u Q g k e r u t a r e p m e T C e m i T s e t u n i m s e k a c d n a s e i r t s a P d l u o m n i x i m n e t a e b h t i W d l u o m t u o h t i w x i m n e t a e b h t i W e s a b n a l f y r t...

Page 10: ...al free cross section of passage of at least 6 cm for every kW of rated heating capacity of the appliance with a minimum of 100 cm the heating capacity is indicated on the rating plate it must be made...

Page 11: ...necting to a liquid gas supply in a cylinder Adaptation to a different type of gas If the hob is to be converted for use with a type of gas other than that for which it was set in the factory indicate...

Page 12: ...he appliance see rating plate the supply system is efficiently earthed according to standards and laws in force the socket or double pole switch are easily accessible when the appliance is installed I...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...viale Aristide Merloni 47 60044 Fabriano tel 0732 6611 telex 560196 fax 0732 662954 www Merloni com Mod ARISTON XC 902 GH DC AUS 07 03 195039794 00 Xerox Business Services Docutech...

Reviews: