Ariston PRO 94 DM UK.01 Instructions For Installation And Use Manual Download Page 8

7

The following instructions are provided for qualified installers
so that they may accomplish installation, adjustment and
technical maintenance operations correctly and in
compliance with  current regulations and standards.
Important: the appliance should be disconnected from
the mains electricity supply before any adjustment,
maintenance, etc. is carried out.
 Maximum caution should
be used should it be necessary to keep the appliance
connected to the electricity supply. The cookers have the
following technical specifications:
Category: II 2H3+    Class: 1

The dimensions of the appliance are given in the figure on
page 2. For trouble-free operation of appliances installed in
housing units, the minimum distances shown in fig.4 should
be observed. Adjacent surfaces and the wall at the rear
should also be able to withstand an overheating temperature
of 65 °C. Prior to installing the cooker, 95 ÷ 155 mm high
supporting feet (provided) should be fitted into the holes to
be found in the bottom of the cooker (fig.5). These feet are
screw-adjustable and whenever necessary should be used
to make sure the cooker stands level.
Positioning
This appliance  may only be installed and operated in
permanently ventilated rooms in compliance with current
standards. The following requirements must be observed:
• The appliance must discharge combustion products into

a special hood, which must be connected to a chimney,
flue pipe or directly to the outside (fig.6).

• If it is impossible to fit a hood, the use of an electric fan

is permitted, either installed on a window or on an external
wall, which must be switched on at the same time as the
appliance.

INSTALLATION

fig.5

In a chimney stack or branched flue

Directly to the outside

(exclusively for cooking appliances)

fig.6

fig.4

Kitchen ventilation
The air flow into the room where the appliance is installed
must equal the quantity of air that is required for regular
combustion of the gas and for ventilating the same room.
Air must be taken in naturally through permanent apertures
made in the outside walls of the room or through single or
branching collective ventilation ducts in compliance with
current standards and regulations. The air must be taken
directly from the outside, from an area far from sources of
pollution. The ventilation aperture must have the following
characteristics (fig.7A):
• total free cross section of passage of at least 6 cm² for

every kW of rated heating capacity of the appliance, with
a minimum of 100 cm² (the heating capacity is indicated
on the rating plate);

• it must be made in such a way that the aperture, both on

the inside and outside of the wall, cannot be obstructed;

• it must be protected, e.g. with grates, wire mesh, etc. in

such a way that the above-mentioned free section is not
reduced;

• it must be situated as near to floor level as possible.

Detail A

Adjacent

Room to be

room

 ventilated

A

Examples of ventilation holes

Enlarging the ventilation slot

for comburant air

 between window and floor

fig. 7A

fig. 7B

The air inflow may also be obtained from an adjoining room,
provided the latter is not a bedroom or a room where there
is a risk of fire, such as warehouses, garages, fuel stores,
etc. and is ventilated in compliance with the current
standards and regulations. Air from the adjoining room to
the one to be ventilated may be made to  pass freely through
permanent apertures with a cross section at least equal to
that indicated above. These apertures may also be obtained
by increasing the gap between the door and the floor
(fig.7B). If an electric fan is used for extracting the
combustion products, the ventilation aperture must be
increased in relation to its maximum performance. The
electric fan should have a sufficient capacity to guarantee
an hourly exchange of air equal to 3 ÷ 5 times the volume
of the kitchen. Prolonged, intensive use of the appliance
may require extra ventilation, e.g. an open window or a
more efficient ventilation system by increasing the
extraction power of the electric fan if installed. Liquid
petroleum gas descends towards the floor as it is heavier
than air. Apertures in the outside walls in rooms containing
LPG cylinders should therefore be at floor level, in order to
allow any gas from leaks to be expelled.  Do not store LPG
cylinders (even when empty) in basements or rooms below
ground level; it is advisable to keep only the cylinder in use
in the room at any one time and connected far from heat
sources which could raise its temperature to above 50 °C.

Summary of Contents for PRO 94 DM UK.01

Page 1: ...PRO 94 DM X UK 01 Cooker Maxioven Instructions for installation and use...

Page 2: ...losed list When ordering this please give the code BAB followed by the appliance model The model is stamped on the plate which is visible on the front part of the oven upon opening the door SAFETY PRE...

Page 3: ...Auxiliary gas burner B Semi rapid gas burner C Rapid gas burner D Triple ring gas burner R Support Grid for Cookware M Control Knobs for Gas Burners P Ignition Pushbutton for gas burners E Ignitor for...

Page 4: ...Using the burners To obtain maximum efficiency from the burners it is advisable to only use pans with a diameter suitable for the burner being used so that the flame does not extend beyond the pan ba...

Page 5: ...e the oven When the light alternately comes on and goes out it means that the thermostat is working properly to maintain the oven temperature MAINTENANCE AND CLEANING Important The appliance should be...

Page 6: ...the glass protective cover from inside the oven unscrew the lightbulb and replace it with an identical one suitable for high temperatures 300 C and with the following characteristics Voltage 230 V Wat...

Page 7: ...e p y T e m i t g n i k o o C s e t u n i m f l e h s f o n o i t i s o P g k 5 0 s p o h C s e g a s u a S g k 1 n e k c i h c d e l l i r G g k 6 0 t i p s e h t n o l a e V g k 1 t i p s e h t n o...

Page 8: ...th current standards and regulations The air must be taken directly from the outside from an area far from sources of pollution The ventilation aperture must have the following characteristics fig 7A...

Page 9: ...d when connecting to a liquid gas supply in a cylinder fig 10 ELECTRICAL CONNECTION Adjusting the low flame Put the tap to the low flame position the burner should be lit Remove the tap knob and turn...

Page 10: ...knob all the way in You keep the knob pressed in long enough to activate the safety device The gas holes are not clogged in the area corresponding to the safety device The burner does not remain on w...

Page 11: ......

Page 12: ...viale Aristide Merloni 47 60044 Fabriano tel 0732 6611 telex 560196 fax 0732 662954 www Merloni com Mod ARISTON 06 03 195036539 00 Xerox Business Services Docutech...

Reviews: