DOES THE
BURNER LIGHT?
YES
NO
YES
YES
WAS THE
RESET SWITCH
PRESSED?
YES
NO
NO
NO
NO
YES
1)Check/replaceigniter plugs
2)Check wiring
3)Check starter
4)Check small wire
5)Check power supply PCB
6)Check control PCB
1) Check whether flame
detection electrode is
hit by the flame
2) Check the electrode
3) Check the power PCB
4) Check the control PCB
1)Check supply of gasto gas
valve
2)Check power supply PCB
3)Check control PCB
4)Check functionality of the
valve
Shutdown LED off
Restart of thefan
IS
THE AIR PRESSURE
SWITCH ACTIVATED?
ARE THE
FUMES DISCHARGED
CORRECTLY?
SAFETY
SHUTDOWN OF THE
BOILER ACTIVATED?
1) Check flue discharge
2) Check venturi & small pipes
3) Check wire for air press.switch
4) Check/replace air press. switch
5) Check/replace PCB wire
6) Check/replace power PCB
7) Check/replace control PCB