GB - 23
technical adjustments
TABLE OF PARAMETERS
CABLED AND WIRELESS VERSIONS
- Hold “
+
” down for 5 seconds. The display will alternate between the software version and
modifi cation index.
- Press “OK” to enter the settings menu.
- Press “
+
” and “
-
” to scroll through the parameters.
- Press "OK" button to select a parameter.
Par.
Description
Default
CF01
Room temperature correction (range +/-5°C)
0°C
CF11
0: Display OFF after 10s
1: Display always on
1
CF12
0: Backlight off
1: Backlight OFF after 5s of inactivity
1
WIRELESS VERSION
- Hold “
+
” down for 5 seconds. The display will alternate between the software version and
modifi cation index.
- Hold “+” down for 5 seconds again to enter the technical parameters menu; parameter “rF01”
will display
- Press “OK” to enter the settings menu.
- Press “+” and “-” to scroll through the parameters.
- Press "OK" button to select a parameter.
Par.
Description
Default
rF01
Detect device (0 - 15)
rF02
Associate zone (1 - 6)
rF03
Signal level (0 - 4)
rF04
Association (0 - 1)
TABLE OF ERRORS
Error
Cause
Solution
Err – Ebus
Zone association error: the
zone associated with the
device is already assigned
Check the installed room sensors. Associ-
ate a diff erent zone
Err – rout
Radio communications error:
the room sensor is out of
range of the receiver or aerial
Check the signal strength with parameter
“rF03”
Use an aerial.
Reposition the room sensor.
Repeat the association procedure
- - -
Err
The room sensor is damaged
Replace it