Argus SG100-IS Quick Start Manual Download Page 3

DETECTOR LOCK

 

 

To lock the detector to the base:

 

 

1)

 

Cut off the small plastic lug

 

on the plastic locking tab on the detector base (picture 4)

 

 

2)

 

Install the detector onto the base

 

 

3)

 

Check if the detector is effectively locked!

 

 

To unlock the detector from the base:

 

 

1)

 

Insert the tip of a small screwdriver into the side hole of the mounting base (picture 5)

 

 

2)

 

Depress, with the tip of the screwdriver, the locking tab on the base

 

 

3)

 

Remove the detector from the base

 

 
 
 
 
 
 
 
 
 
 
 

TAMPER DETECTION CAPABILITY

 

 

The wireless optical smoke detector is provided with a tamper switch: in case of removal of the detector from its base, a tamper detection 
message is sent to the control panel.

 

 

TESTING

 

 

All detectors must be tested after installation and, successively, on a periodic basis.

 

 

After each test reset the fire security system from the control panel, as per your control panel instructions.

 

 

TEST 1 

-

 MAGNET TEST

 

 

Purpose: checking the alarm capability of the detector by using the built

-

in test circuitry; 

no alarming agent (aerosol) is used.

 

 

1) Hold a suitable magnet in correspondence of the indicated area (picture 6)

 

 

2) Wait a few seconds

 

 

3) If it works, the detector will switch into “

Alarm mode

” (as indicated by the LED indicator)

 

 

TEST 2 

-

 AEROSOL TEST

 

 

Purpose: checking the alarm capability of the detector by using aerosol.

 

 

Use only suitable aerosol testers supplied by approved manufacturers.

 

 

1) By following its specific instructions, apply the aerosol test device to the detector

 

 

2) Wait a few seconds

 

 

3) If it works, the detector will switch into “

Alarm mode

” (as indicated by the LED indicator)

 

 

MAINTENANCE 

-

 CLEANING

 

 

1)

 

Remove the detector from its base

 

 

2)

 

Smoke entry areas: use a small, soft bristle brush to dislodge any obvious contaminants such as insects, spider webs, hairs, etc.

 

 

3)

 

Smoke entry areas: use a small vacuum tube or dry, clean, compressed air to suck up or blow any remaining small particles away

 

 

4)

 

Wipe the exterior housing of the detector with a clean, damp, lint

-

free cloth to remove any surface film that can later attract airborne 

 

 

contaminants

 

 

5)

 

Install the detector onto its base again

 

 

6)

 

Test the detector

 

ARGUS SECURITY S.R.L.

 

-

 Via del Canneto, 14 

-

 34015 

-

 Muggia (TS) 

-

 Italy

 

www.argussecurity.it

 

Picture 4

 

Detector locking 

tab

 

Picture 5

 

Unlocking tool (screwdriver)

 

Access to detector’s lock

 

Picture 6

 

Summary of Contents for SG100-IS

Page 1: ...unctional modes battery faults and other fault types see table 1 LINKING THE DEVICE TO THE SYSTEM This detector must be linked to the fire detec tion system before installation specifically it must be linked to its translator or expander interface following the system design plan NOTE As a safety precaution linking and power up of devices should be carried out adjacent to the translator expander i...

Page 2: ... DETECTOR INSTALLATION For detector spacing placement and special applications refer to your specific national standards Mount the detector as far as possible from metal objects metal doors metal window open ings etc as well as cable conductors cables especially from computers otherwise the operating distance may greatly drop The detector must NOT be installed near electronic devices and computer ...

Page 3: ... in correspondence of the indicated area picture 6 2 Wait a few seconds 3 If it works the detector will switch into Alarm mode as indicated by the LED indicator TEST 2 AEROSOL TEST Purpose checking the alarm capability of the detector by using aerosol Use only suitable aerosol testers supplied by approved manufacturers 1 By following its specific instructions apply the aerosol test device to the d...

Page 4: ...ould be sought for special risks Sensors cannot respond correctly if barriers exist between them and the fire location and may be affected by special environmental conditions Refer to and follow national codes of practice and other internationally recognized fire engineering standards Appropriate risk assessment should be carried out initially to determine correct design criteria and updated perio...

Reviews: