INSTALLATION 

 
1. Position the detector centrally on its mounting base. 
 
2. Rotate clockwise applying gentle pressure. The detector will       
  drop into its mechanical holding location. 
 
3. Push the detector to win the force of the contacts. 
 
4. Continue to rotate clockwise a few degrees until the detector is 
  firmly held on the detector base. 
 
5. When the detector is firmly held verify the alignment between 
  the detector and the raised marks on the base (picture 5). 
 
6. After installing all detectors, apply power to the fire security 
  system. 
 
7. Test the detectors as described in the paragraph headed 
  “TESTING”.

 

Picture 3 - Wiring used 
when the alarm current 
is limited by the resistor 
on the mounting base. 

1.  Position the detector. 

2.  Rotate. 

3.  Push. 

4.  Rotate. 

CAUTION 

Dust  covers  help  to  protect  the  devices  during 
shipping  and  when  first  installed.  They  are  not 
intended  to  provide  complete  protection  against 
contamination,  therefore,  sensors  should  be 
removed before construction, major re-decoration 
or  other  dust  producing  work  is  started.  DUST 
COVERS  MUST  BE  REMOVED  BEFORE  THE 
SYSTEM CAN BE MADE OPERATIONAL. 

MAINTENANCE 

 
Before starting any maintenance work, isolate and disable the system in order to avoid accidental and unwanted fault conditions. 
Remove the sensor from its mounting base to allow inspection in good light at ground level. Inspect the smoke entry ports around the 
sensor and use a small, soft bristle brush to dislodge any evident contaminants such as insects, spider webs, hairs, etc. Use a small 
vacuum tube or clean, dry and compressed air to suck up or blow away any remaining small particles from the smoke entry screen 
area. Wipe the exterior housing of the sensor with a clean, damp, lint free cloth to remove any surface film that can later attract 
airborne contaminants. After all sensors have been inspected, repositioned on their mounting bases and power has been re-applied, 
check correct operation as described under the “TESTING” paragraph. 

TESTING 

 
Sensors should be tested after installation and during periodic maintenance visits (it is recommended each device should be tested at 
least once per year). When the system has been reset, allow, after each test, at least one minute for power stabilisation before the 
next test. Detectors can be tested as follows: 

Magnet test 

Position the magnet (model TMD-01, optional) next to the sensor between the two raised 
marks on the base (picture 5). 
The magnet test verifies the function of all electronic circuits of the sensor and its com-
munication with the control panel.  
The sensor should trigger an alarm condition on the control panel and turn the red LED 
on. 

 

Aerosol (simulated smoke) test 

Use a test aerosol from an approved manufacturer in accordance with their application 
instructions. This is important to prevent contamination or possible damage. 
The red LED alarm indicator on the detector should illuminate (normally within 60 sec-
onds, but may vary) and  trigger an alarm condition on the control panel. 

 
If testing fails after installation or maintenance then replace the sensor and return 
it for servicing. 

ANTI-TAMPER MECHANICAL BLOCK FEATURE 

 
The sensor may be blocked onto its base by remov-
ing the small plastic element on the base’s detector 
blocking tongue by using a suitable tool (e.g. a 
small screwdriver) inserted through the access hole 
on the side of the mounting base (picture 4). 
To remove the sensor from the base, if mechani-
cally blocked, insert a suitable tool through the 
access hole on the side of the mounting base 
(picture 4). 

TAMPER DETECTION 

 
Each detector’s mounting base has two “–” marked terminals. These are electrically identical, but they are connected to each other 
only when a detector is correctly fitted onto the base; this feature is used in combination with an appropriate “end of line” (EOL) 
component, designated by the control panel manufacturer, in order to indicate a fault condition if a detector is removed from its 
base. To enable the function to operate correctly it is important that incoming and outgoing negative wires are separated in the  
above said way 

Picture 4 - The anti-tamper block and its handling. 

Picture 5 - The correctly installed detector. 

Magnet 
test position 
(model TMD-01). 

Alignment between base and detector. 

ARGUS SECURITY S.R.L.

 - Via Archimede 42, 20041, Agrate Brianza, Milano, Italy 

www.argussecurity.it 

[email protected] 

L20-S1000-0001 (v1.0) 

LINE IN 

POSITIVE (+) 

LINE IN 

NEGATIVE (-) 

LINE OUT 

POSITIVE (+) 

LINE OUT 

NEGATIVE (-) 

REMOTE INDICATOR 

END OF LINE RESISTOR 

WIRING - BASE WITH RESISTOR AND BASE WITH RESITOR AND SCHOTTKY DIODE 

 
This configuration is to be used when the alarm current depends only on the value of the resistor fitted on the base (picture 3). 

 
  