Argus Cordex CXCM2 Replacement Procedure Download Page 2

 

2

 
 
 

2.  Save CXC text file if necessary. 
 

 

 

 

 
Bypass system LVD by setting override switch 
CAUTION: If the LVD is not bypassed, the DC loads will be shut down when the wiring to the 
controller is removed.

  

Remove the DB connectors from I/O Terminal Block

 

 

3.  Standard Customer Connections on the I/O terminal block for the 1.8kW Shelf: 

P3 JUMPER SETTINGS (FOR LVD CONTROL INHIBIT FUNCTION): 
SHORT PINS 1 AND 2 IF LVD IS CONTROLLED ON K1-NC CONTACTS TO MAINTAIN OPERATION. 
SHORT PINS 2 AND 3 IF LVD IS CONTROLLED ON K1-NO CONTACTS TO MAINTAIN OPERATION

 

 

 
 

 

 
 

 
 
 

 