Argus Cordex CXCM2 Replacement Procedure Download Page 1

 

CXCM2 Cordex Controller Replacement Procedure 

 
 
Summary 
 

This procedure describes the process of removing and replacing the CXCM2 modular controller from the 
1.8kW shelf after inhibiting the low voltage disconnect and preserving any custom settings. 
Note: Any system software changes made on site would need to be transferred, by backing up the 
configuration as shown in step 1 and 2. The replacement CXCM2 unit will ship with with the factory original 
configuration specified for your setup. 

 
Tools/Information Required 
 

• Voltmeter 
• Ethernet crossover cable 
• Philips screw driver 

 
Preparing for Removal of CXCM2 
 

1.  Save CXC configuration file if necessary (see software manual). 
 
 

 

 
 
 
 
 
 
 