4-2 Freeze Prevention
This function prevents freezing of the indoor heat exchange coil.
When the compressor has been running for 6 minutes or more and the temperature of the indoor heat
exchange coil falls below –0.8°C, the control circuit stops the compressor for at least 3 minutes. The
compressor does not start again until the temperature rises above 8°C or 6 minutes has elapsed.
ON
ON
ON
ON
OFF
OFF
Set speed
More than
6 minutes
6 minutes
T+1
°
C
Indoor heat exch.
coil temp.
–0.8
°
C
Compressor
Indoor fan
Room temp.
Thermo. OFF
Thermo. ON
Set temp. T
°
C
More than
6 minutes
More than
6 minutes
Set speed
16