Argo AER608SH Technical Data & Service Manual Download Page 2

IMPORTANT!
Please read before installation

This air conditioning system meets strict safety and operating
standards.
For the installer or service person, it is important  to install or
service the system so that it operates safely and efficiently.

For safe installation and trouble-free operation, you must:

• Carefully read this instruction booklet before beginning.
• Follow each installation or repair step exactly as shown.
• Observe all local, state and national electrical  codes.
• Pay close attention to all warning and caution notices given in

this manual.

•The unit must be supplied with a dedicated electrical line.

This symbol refers to a hazard or unsafe practice which can result
in severe personal injury or death.

This symbol refers to a hazard or unsafe practice which can result
in personal injury or product or property damage.

If necessary, get help

These instructions are all you need for most installation sites and
maintenance conditions.
If you require help for a special problem, contact our sale/service
outlet or your certified dealer for additional instructions.

In case of improper installation

The manufacturer shall in no way be responsible for improper
installation or maintenance service, including failure to follow the
instructions in this document.

SPECIAL PRECAUTIONS

• During installation, connect before the refrigerant system and

then the wiring one; proceed in the reverse orden when removing
the units.

When wiring

ELECTRICAL

SHOCK  CAN  CAUSE  SEVERE

PERSONAL INJURY OR DEATH. ONLY A QUALIFIED,
EXPERIENCED ELECTRICIANS SHOULD ATTEMPT
TO WIRE THIS SYSTEM.

• Do not supply power to the unit until all wiring and tubing are

completed or reconnected and checked, to ensure the grounding.

• Highly dangerous electrical voltages are used in this system.

Carefully refer to the wiring diagram and these instructions when
wiring.
Improper connections and inadequate grounding can cause

accidental injury and death

.

Ground the unit 

following local electrical codes.

• The Yellow/Green wire cannot be used for any connection

different from the ground connection.

• Connect all wiring tightly. Loose wiring may cause overheating

at connection points and a possible fire hazard.

• Do not allow wiring to touch the refrigerant tubing, compressor,

or any moving parts of the fan.

• Do not use multi-core cable when wiring the power supply and

control lines. Use separate cables for each type of line.

When transporting

Be careful when picking up and moving the indoor and outdoor
units. Get a partner to help, and bend your knees when lifting to
reduce strain on your back. Sharp edges or thin aluminium fins on
the air conditioner can cut your fingers.

When installing...
... In a ceiling or wall

Make sure the ceiling/wall is strong enough to hold the unit-weight.
It may be necessary to build a strong wooden or metal frame to
provide added support.

... In a room

Properly insulate any tubing run inside a room to prevent
"sweating", which can cause dripping and water damage to walls
and floors.

... In moist or uneven locations

Use a raised concrete base to provide a solid level foundation for
the outdoor unit.
This prevents damage and abnormal vibrations.

... In area with strong winds

Securely anchor the outdoor unit down with bolts and a metal
frame. Provide a suitable air baffle.

... In a snowy area (for heat pump-type systems)

Install the outdoor unit on a raised platform that is higher than
drifting snow. Provide snow vents.

When connecting refrigerant tubing

• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare

and union tubes before connecting them;  screw by hand and
then tighten the nut with a torque wrench for a leak-free
connection.

• Check carefully for leaks before starting the test run.

NOTE:

Depending on the system type, liquid and gas lines may be either
narrow or wide. Therefore, to avoid confusion, the refrigerant
tubing for your particular model is specified as narrow tube for
liquid, wide tube for gas.

When servicing

• Turn the power OFF at the main power board  before opening

the unit to check or repair electrical parts and wiring.

• Keep your fingers and clothing away from any moving parts.
• Clean up the site after the work, remembering to check that no

metal scraps or bits of wiring have been left inside the unit being
serviced.

• Ventilate the room during the installation or testng the refrigeration

system; make sure that, after the installation, no gas leaks are
present, because this could produce toxic gas and dangerous
if in contact with flames or heat-sources.

WARNING

CAUTION

WARNING

2

Summary of Contents for AER608SH

Page 1: ...ECHNICAL DATA SERVICE MANUAL OUTDOOR UNIT AER608SH AER609SH AER612SH SPLIT SYSTEM AIR CONDITIONER 0 8180 261 0 05 2002 AER609SH 387007131 AER612SH 387007132 Model No Product Code No AER608SH 387007130...

Page 2: ...ing to touch the refrigerant tubing compressor or any moving parts of the fan Do not use multi core cable when wiring the power supply and control lines Use separate cables for each type of line When...

Page 3: ...er Component specifications 11 3 DIMENSIONAL DATA 12 4 REFRIGERANT FLOW DIAGRAM 13 5 PERFORMANCE DATA 15 5 1 Performance Charts 15 5 2 Cooling Capacity 18 5 3 Heating Capacity 21 6 ELECTRICAL DATA 22...

Page 4: ...RANGE Cooling Maximum Minimum 43 C D B 19 C D B 32 C D B 23 C W B 19 C D B 14 C W B 24 C D B 18 C W B 8 C D B 9 C W B Temperature Indoor Air Intake Temp Outdoor Air Intake Temp Heating Maximum Minimum...

Page 5: ...be diameter Wide tube mm in Dimensions Weight Unit dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Weight Net kg Shipping kg Shipping volume m3 DATA SUBJECT TO CH...

Page 6: ...mm in Dimensions Weight Unit dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Weight Net kg Shipping kg Shipping volume m3 DATA SUBJECT TO CHANGE WITHOUT NOTICE Re...

Page 7: ...m in Dimensions Weight Unit dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Weight Net kg Shipping kg Shipping volume m3 DATA SUBJECT TO CHANGE WITHOUT NOTICE Rem...

Page 8: ...igh Nominal output W Coil resistance Ambient temp 25 C Safety devices Type Operating temp Open C Close C Run capacitor F VAC Heat Exch Coil Coil Rows Fin pitch mm Face area m2 External Finish DATA SUB...

Page 9: ...High Nominal output W Coil resistance Ambient temp 25 C Safety devices Type Operating temp Open C Close C Run capacitor F VAC Heat Exch Coil Coil Rows Fin pitch mm Face area m2 External Finish Acryli...

Page 10: ...gh Nominal output W Coil resistance Ambient temp 25 C Safety devices Type Operating temp Open C Close C Run capacitor F VAC Heat Exch Coil Coil Rows Fin pitch mm Face area m2 External Finish 450 Therm...

Page 11: ...way Valve 20S Coil rating Coil resistance at 20 C AER612SH 4 way Valve 20S Coil rating Coil resistance at 20 C AC 220 240 V 50 Hz 6W 1402 7 SRF 01AJ504D1 Coil STF 0101Z Valve AC 220 240 V 50 Hz 6W 14...

Page 12: ...IONAL DATA 700 540 15 470 4 12 holes 116 320 294 Air intake Air discharge 255 10 170 103 57 Narrow tube service valve 6 35 1 4 Wide tube service valve 9 52 3 8 12 7 1 2 7000 9000 BTU h 12000 BTU h Uni...

Page 13: ...exchanger Heat exchanger Muffler Capillary tube Capillary tube Cooling cycle Heating cycle Strainer Indoor unit Outdoor unit Check valve Strainer Compressor 4 way valve Accumulator Wide tube service v...

Page 14: ...insulation should be a min 8 mm After a tube has been insulated never try to bend it into a narrow curve because it can cause the tube to break or crack IMPORTANT CAUTION Wide tube Thickness Min 8 mm...

Page 15: ...60 10 5 0 5 10 15 20 25 Outdoor inlet air D B C High pressure at wide tube service valve MPa 1 2 3 4 5 6 7 8 9 10 11 20 25 30 35 40 45 Outdoor inlet air D B temp C Operating current A Indoor inlet air...

Page 16: ...25 Outdoor inlet air D B C High pressure at wide tube service valve MPa 1 2 3 4 5 6 7 8 9 10 11 20 25 30 35 40 45 Outdoor inlet air D B temp C Operating current A Indoor inlet air D B C 32 27 19 1 2 3...

Page 17: ...10 15 20 25 Outdoor inlet air D B C High pressure at wide tube service valve MPa 1 2 3 4 5 6 7 8 9 10 11 20 25 30 35 40 45 Outdoor inlet air D B temp C Operating current A Indoor inlet air D B C 32 27...

Page 18: ...1 87 TC 2 65 2 50 2 42 2 30 2 16 1 99 CM 0 72 0 75 0 78 0 80 0 83 0 85 21 SHC 1 17 1 10 1 06 1 01 0 95 0 88 23 SHC 1 38 1 29 1 26 1 21 1 15 1 08 19 25 SHC 1 59 1 48 1 45 1 40 1 34 1 27 27 SHC 1 79 1 6...

Page 19: ...8 2 72 2 63 2 50 2 35 2 16 CM 0 78 0 84 0 90 0 96 1 02 1 08 21 SHC 1 27 1 19 1 15 1 10 1 03 0 96 23 SHC 1 50 1 40 1 36 1 31 1 24 1 17 19 25 SHC 1 73 1 60 1 57 1 52 1 46 1 38 27 SHC 1 94 1 81 1 78 1 73...

Page 20: ...7 3 37 3 26 3 10 2 91 2 68 CM 0 98 1 06 1 13 1 21 1 28 1 35 21 SHC 1 57 1 48 1 43 1 36 1 28 1 19 23 SHC 1 86 1 74 1 69 1 62 1 54 1 45 19 25 SHC 2 14 1 99 1 95 1 88 1 81 1 71 27 SHC 2 41 2 24 2 21 2 05...

Page 21: ...ition Indoor 20 C D B Outdoor 7 C D B 6 C W B 2 Above characteristics indicate instantaneous operation which does not take into consideration defrost operation 3 Fan speed High 4 Because this air cond...

Page 22: ...C D B 23 C W B Outdoor Air Temperature 43 C D B HEATING Indoor Unit Complete Unit Fan Motor Fan Motor Compressor performance at Rating conditions Running Amps A 0 11 0 28 3 61 4 0 Power input Kw 0 025...

Page 23: ...ir Temperature 43 C D B HEATING Indoor Unit Complete Unit Fan Motor Fan Motor Compressor performance at Rating conditions Running Amps A 0 12 0 28 4 3 4 7 Power input Kw 0 027 0 063 0 973 1 050 Full l...

Page 24: ...ir Temperature 43 C D B HEATING Indoor Unit Complete Unit Fan Motor Fan Motor Compressor performance at Rating conditions Running Amps A 0 13 0 28 6 19 6 6 Power input Kw 0 031 0 063 1 306 1 400 Full...

Page 25: ...6 2 Electric Wiring Diagram 6 3 System Wiring Diagram 25...

Page 26: ...Via Varese 90 21013 Gallarate Va Italy Tel 39 0331 755111 Fax 39 0331 776240 www argoclima it...

Reviews: