17 - OUTDOOR/INDOOR UNIT REFRIGERANT CIRCUIT ADDRESS

Indoor units that are part of a multisplit system must be properly configured to be able to communicate with the 
outdoor unit over different channels (Indoor A, Indoor B, etc...) of the communication bus.

Each indoor unit address must correspond to the physical connection of the indoor unit to the outdoor unit refrigerant 
circuit, i.e.:

Refrigerant Circuit A <--> Indoor Unit Address A

Refrigerant Circuit B <--> Indoor Unit Address B

...

There are three methods to set the address of an indoor unit:

(1) 

Dip-switch setting:

 the address is set by mean of a dip-switch located on the indoor unit pcb.

(2) 

Remote controller procedure

: the address is set by mean of a special setting on the remote controller.

(3) 

Automatic addressing procedure:

 the address is automatically set on every indoor unit of the system by mean of 

an  automatic procedure.

Check that the setting of switch SW2 (PCB) corresponds to the figure:

(1) ADDRESS SETTING THROUGH DIP-SWITCHES (UP TO 4 INDOOR UNITS)

Disconnect the power

SW2    

(PCB factory state)

1=off
2=off

INDOOR UNIT 

A

INDOOR UNIT 

D

SW2 

1=on
2=on

PCB

INDOOR UNIT 

B

SW2 

1=on
2=off

PCB

INDOOR UNIT 

C

SW2

1=off
2=on

PCB

Summary of Contents for ADIAS19DC

Page 1: ...ALLATIONS ANLEITUNGEN INSTRUCCIONES DE INSTALACIÓN INSTRUÇÕES DE INSTALAÇÃO DE ES PT ADIAS19DC ADIBS13DC ADICS13DC Split air conditioner system Condizionatore d aria split system Climatiseurs split Zweirohrsystem Klimaanlage Acondicionador de aire Split System Sistema de ar condicionado de Unidades Separadas ...

Page 2: ...s and maintenance conditions If you require help for a special problem contact our sale service outlet or your certified dealer for additional instructions In case of improper installation The manufacturer shall in no way be responsible for improper installation or maintenance service including failure to follow the instructions in this document SPECIAL PRECAUTIONS During installation connect befo...

Page 3: ...k Sharp edges or thin aluminium fins on the air conditioner can cut your fingers When installing In a ceiling Make sure the ceiling is strong enough to hold the unit weight It may be necessary to build a strong wooden or metal frame to provide added supporte In a room Properly insulate any tubing run inside a room to prevent sweating which can cause dripping and water damage to walls and floors Wh...

Page 4: ...E SELECTION DO Select an appropriate position from which every corner of the room can be uniformily cooled Select a sufficiently strong location to support the weight of the unit Select a location where tubing and drain hose have the shortest run to the outside Allow access for operation and maintenance as well as unrestricted air flow around the unit AVOID Direct sunlight Nearby heat sources that...

Page 5: ...D B Room temperature 10 C D B 6 C W B Heating Maximum conditions Outdoor temperature 24 C D B 18 C W B Room temperature 27 C D B Heating Minimum conditions Outdoor temperature 15 C D B Room temperature 5 C D B Deoxidized annealed copper tube for refrigerant tubing connecting the units of the system it has to be insulated with foamed polyethylene min thickness 8mm For tubing dimensions tubing lengt...

Page 6: ...EIGHT kg ADIA 30 ADIB 35 AWIC 35 B C A E E D RECEIVER WIRE LENGTH 5 m 105 70 REAR VIEW FRONT VIEW TOP VIEW FRESH AIR INTAKE PORT CONVOGLIATORE ARIA ACCESSORIO SU RICHIESTA REFRIGERANT TUBING SIDE Ø 18 CONDENSATE DRAIN PIPING REFRIGERANT TUBING JOINT REFRIGERANT TUBING JOINT WIDE TUBE NARROW TUBE O D 6 35mm 1 4 O D 9 52mm 3 8 ADIA O D 12 7mm 1 2 ADIB C ...

Page 7: ...eiling C Use rawl plug suitable to the ceiling consistence and four M10 threaded bars of suitable lenght not supplied 300 D Mark on the ceiling the holes for the hanging rods verify the distance of the centres E Drill a 65 80 mm diameter hole for the passage of refrigeration pipework condensate pipework and electrical cable Insert a PVC pipe in the wall ADIB CS13 900 ADIAS19 ...

Page 8: ... a large volume of water draining back into the unit when it is switched off I Convoy the condensate to the outside with a positive slope from a trap at the end if necessary J Predispose the terminals of the wire to connect to the terminal strip and connect them See electric wiring to connect Secure inter unit wire using the supplied clamp Loose wiring may cause the terminal to overheat or result ...

Page 9: ...986 ADIB CS13 782 ADIAS19 988 ADIB CS13 10 DUCT FOR FRESH AIR There is a duct connection port for drawing in fresh air The supplementary fan motor for outside air intake has to be supplied separately and controlled by a bipolar ON OFF switch with safety fuses Fresh air flow must be about 10 of the total air flow to avoid operating problems and noise Open the knock out hole fix a Ø 120 mm flange on...

Page 10: ...all with two screws and hang the remote control unit 12 INFRARED RECEIVER INSTALLATION A Slot a screwdriver by the 2 slits on the cover sides and separate the cover from the base Do not lay the receiver cable near any power lines and do not put it into any raceways or metal tubes together with other power lines Install the receiver far from electromagnetic interferences Always provide for an earth...

Page 11: ...rm occurs the poles of the terminal block will have a voltage of 220V 50Hz Max electric load 3A 240V C D End of installation C 14 DEFAULT SETTING RESET To operate the unit again with the default setting it is necessary to set the remote control as follows Filter ON Night Mode High Power Mode OFF Operation mode AUTO Flap AUTO Set point 10 C At this point press contemporary the FAN and IFEEL keys of...

Page 12: ...e solved by increasing the fan speed as follows A B Open the cover of the electrical junction box Take out JP2 With the contact JP2 open the external static pressure will increase to about 7 mm Check static pressure and air flow rate on the fan performance graph L Low fan speed M Middle fan speed H High fan speed HH Very high fan speed H Standard supplied unit Available fan speeds Low Middle High ...

Page 13: ...are three methods to set the address of an indoor unit 1 Dip switch setting the address is set by mean of a dip switch located on the indoor unit pcb 2 Remote controller procedure the address is set by mean of a special setting on the remote controller 3 Automatic addressing procedure the address is automatically set on every indoor unit of the system by mean of an automatic procedure Check that t...

Page 14: ... than 7 seconds and release them pointing the remote controller to the indoor unit receiver Be sure to send the signal to only one indoor unit and that there is no other indoor unit that could receive the same signal If the signal is received the indoor unit will emit 5 consecutive beeps NOTE for electrical connections refrigerant circuit connection and check consult the Installation Instruction o...

Page 15: ... following LED combination to confirm that the automatic addressing procedure has been activated OPERATION GREEN TIMER BLUE STANDBY RED From this moment until the end of the procedure the indoor units will not receive anymore the signals from the remote controllers infrared receiver is disabled Execution of automatic addressing procedure Once the procedure has been activated the system will run au...

Page 16: ...in the remote control unit Switch on the indoor unit At this point the system starts operating with the new address Set SW1 PCB as shown in the table 1 FACTORY STATE 1 OFF 2 OFF 3 OFF 4 OFF 5 ON 6 ON SW1 1 OFF 2 OFF 2 1 ON 2 OFF 3 OFF 4 OFF 5 ON 6 ON SW1 1 ON 2 OFF 3 1 OFF 2 ON 3 OFF 4 OFF 5 ON 6 ON SW1 1 OFF 2 ON 4 1 ON 2 ON 3 OFF 4 OFF 5 ON 6 ON SW1 1 ON 2 ON REMOTE CONTROLLER PCB INDOOR UNIT ...

Page 17: ...CTION Use a tripolar electric shielded wire 0 5mm2 max length 15m The wires have not to be lighter than Mod H05VVC4V5 K according to CEI 20 20 CENELEC HD21 CONNECTING THE REMOTE CONTROLLER TO THE 5 POLES TERMINAL BLOCK INSIDE THE ELECTRICAL PANEL AS FOLLOWS Remove the bridge wire between the terminals 2 and 4 Connect the terminal 1 to the bottom terminal of remote control terminal block pole Conne...

Page 18: ...RRÓN CASTANHO G Y GREEN YELLOW VERDE GIALLO VERT JAUNE GRÜN GELB VERDE AMARILLO VERDE AMARELO GRY GREY GRIGIO GRIS GRAU GRIS CINZENTO ORG ORANGE ARANCIONE ORANGE ORANGE NARANJA COR DE LARANJA PNK PINK ROSA ROSE ROSA ROSA COR DE ROSA RED RED ROSSO ROUGE ROT ROJO ENCARNADO VLT VIOLET VIOLA VIOLET VIOLETT VIOLETA VIOLETA WHT WHITE BIANCO BLANC WEISS BLANCO BRANCO YEL YELLOW GIALLO JAUNE GELB AMARILLO...

Page 19: ...S A C Printed in italy Via Alfeno Varo 35 25020 Alfianello BS Italy Tel 39 0331 755111 Fax 39 0331 755501 www argoclima com ...

Reviews: