5-18 Indoor Unit Jumpers Configuration
Unit is shipped with jumpers set
according to the following table:
JUMPER
STATUS
JP1
open
JP2
open
5-19 Outdoor Unit Jumpers Configuration
Unit is shipped with jumpers set
according to the following table:
JUMPER
STATUS
JP1
open
JP2
closed
JP3
open
5-20 Contacts for Building Automation
5-20.1 Input Contact (J11 - green)
The status of this input affects system operation according to the following:
Contact OPEN : system does not operate (always OFF) – inputs from wireless remote controller are not processed
Contact CLOSED: system operates in the normal way according to the inputs coming from wireless remote controller
INPUT CONTACT
CONNECTOR J11 GREEN
STATUS: CLOSED
OUTPUT CONTACT
CONNECTOR J20 RED
USED TO SIGNAL
AN ALARM CONDITION
5-20.2 Output Contact (J20 - red)
This connector is directly tied to the contact (normally open) of a power relay which activates every time
the following alarm condition occur:
RAT damaged
ICT damaged
Communication error
Fault on outdoor unit
In this case when alarm happens, on poles 1 and 3 of J20 connector, 220 VAC-50Hz are available.
Max electrical load:
1A- 240VAC
19
Summary of Contents for 387005002
Page 7: ...2 DIMENSIONAL DATA FCIAS8 Units mm Wide Tube Ø 9 52 3 8 7 ...
Page 8: ...3 PERFORMANCE DATA 3 1 Air Throw Distance Chart FCIAS8 Floor Mounted Ceiling Mounted 8 ...
Page 9: ...4 ELECTRICAL DATA 4 1 Electric Wiring Diagram 9 ...
Page 24: ...7 4 OUTDOOR UNIT DOES NOT RUN AND NO FAULT IS DISPLAYED 7 5 ONLY OUTDOOR UNIT IS OFF 24 ...
Page 28: ...7 8 NOISE PROBLEM 28 ...