6. CHECKING ELECTRICAL COMPONENTS
6-1 Measurement of Insulation
Resistance
The insulation is in good condition if the
resistance exceeds 2M
Ω
6-1-1. Power supply wires
Clamp the grounding terminal of the power plug
with a lead clip of the insulation resistance tester
and measure the resistance by placing a probe
on both the two power terminals. (fig.1)
Then, also measure the resistance between the
grounding and other power terminals. (fig.1)
6-1-2. Indoor Unit
Clamp a metallic part of the unit with the lead
clip of the insulation resistance tester and measure
the resistance by placing a probe on each terminal
screw where power supply lines are connected on the
terminal plate. (fig.2)
6-1-3. Outdoor Unit
Clamp an aluminium plate fin or copper tube with
the lead clip of the insulation resistance tester
and measure the resistance by placing a probe
on each terminal screw on the terminal plate. (fig.2)
Note that the ground line terminal should be skipped
for the check.
6-1-4. Measurement of Insulation
Resistance for Electrical Parts
Disconnect the lead wires of the desired electric
part from terminal plate, capacitor, etc.
Similary disconnect the connector.
Then measure the insulation resistance. (fig.3 and 4)
NOTE: Refer to electric wiring diagram
If the probe cannot enter the poles because the
hole is too narrow then use a probe with a
thinner pin.
Ground
power plug
(Local supply)
probe
Insulation
tester
Terminal plate
Copper
tube or
metallic part
Clip
Insulation
tester
Probe
Copper
tube or
metallic part
Clip
Insulation
tester
Probe
Clip
Insulation
tester
Probe
Metallic
part
From fan motor,
compressor and
other parts
Fig. 2
Fig. 3
Fig. 4
The shape of the power plug may differ from that
of the air conditioner which you are servicing.
NOTE
Fig. 1
30
Summary of Contents for Euro-Line AS28AL
Page 8: ...2 DIMENSIONAL DATA Units mm 8 ...
Page 9: ...3 ELECTRICAL DATA 3 1 Electric Wiring Diagrams 9 ...
Page 10: ...4 1 Cool Mode Operation 4 FUNCTION 10 ...
Page 11: ...4 2 Heat Mode Operation 11 ...
Page 12: ...4 3 Auto Cool Heat Mode Operation 12 ...
Page 13: ...4 4 Dry Mode Operation 13 ...
Page 15: ...2 Outdoor Coil High Pressure Protection 15 ...
Page 16: ...4 7 Protection Operations in Heat Mode 1 Outdoor Coil Deice Protection 16 ...
Page 17: ...17 ...
Page 18: ...2 Indoor Coil High Pressure Protection in Heat Mode 18 ...
Page 19: ...4 8 Sleep Function 4 9 Daily Timer Function 4 10 IFEEL Function 19 ...
Page 32: ...Via Varese 90 21013 Gallarate Va Italy Tel 39 0331 755111 Fax 39 0331 776240 www argoclima it ...