Connecting conductor bars
Important:
Aluminium conductor bars
must not be connected to
silver-plated connection
areas of the circuit-breaker. Inadmis-
sible matching of materials.
Important:
Coat contact surfaces and
comply with the specified
tightening torques (refer to
Annex).
•
Take account of DIN 43 670 and
DIN 43 671 regarding the di-
mensioning for continuous cur-
rent.
•
Maximum distance of the next
support point from the circuit-
breaker’s terminals in the directi-
on of the switch pole axis. 3 x
the pole center spacing of the
circuit-breaker (unless the next
supporting point is located in the
direction of the switch pole axis,
make sure that the circuit-brea-
ker pole is not exposed to higher
electrodynamic forces).
•
Screw-fasten conductor bar
(take account of DIN 43 679).
•
The circuit-breaker must not be
deformed by screw-fastening the
conductor bars.
Connection areas
on the circuit-breaker
on the conductor bar
Silver-plated copper
Copper or silver-plated copper
In case of aluminium:
use an intermediate layer of copper (thickness
0.1 mm) corresponding to the full size of the
connection area (reduction of rated normal
current by 13 %)
60
30
50
90
340
M12
Einschraub-
tiefe 15-22 mm
Fig. 5.2
High-voltage terminal for the HVX-F
13
M 12
Thread reach
15 – 22 mm