p3
1. INTRODUCTION
•
The TPIs 2T is a module of 2 logic inputs, extra narrow (7.2mm) designed
for DIN rail mounting.
•
It belongs necessarily to a local network made up of converters and/or
output modules.
The status of its 2 inputs, as well as the result of a logical «or» or «and»
between its 2 inputs can be associated with the converter or with the output
module to perform several functions (eg.: direct driving of a relay, zero reset
of alarm recording, etc.)
•
Each converter or module is fixed on the DIN rail via a 5 points footing which
allows the communication and the supply of the TPIs of the network (24Vdc
±30%).
Up to 50 TPIs can be connected on the same bus and up to 200 different
measures can be made to transit ; In this configuration the maximum scan-
ning time is 200ms.
•
The programming is performed via the µUSB connector located on the front
face, which is to be connected to a computer of the type PC equipped with
the software SlimSet.
1.1 General features
Operating temperature ......................... -25°C to +70°C
Storage temperature ............................ -40°C to +85°C
Power supply........................................ 16.8 to 31.2 Vdc
Max. power draw .................................. 0.7W
Max. internal dissipation....................... 0.5W
Galvanic partition.................................. 2.5kV-50Hz-1mn between supply,logic
.............................................................. inputs, µUSB
.............................................................. (logic inputs not insulated from each other)
Listed
Installation in ATEX / IECEx area 2
Installation in division 2 cFMus
Compliance with standards:
Directive EMC 2004/108/CE ............EN 61326-1
Directive LV 2014/35/UE ..................EN 61010-1
Standard for CSA electrical safety....CSA C22.2 14-13
..........................................................UL 508 17th ed.
ATEX 94/9/CE ..................................EN 60079-0, EN 60079-15
IECEx ...............................................IEC 60079-0, IEC 60079-15
Hazardous locations.........................CSA C22.2 213
..........................................................ANSI/ISA 12.12.01
Marking:
II 3 G Ex nA IIC T4 Gc
Class I, Div.2, Groups A, B, C, D T4
1.2 Features of the inputs
Logic input:
low level < 1.2V / high level > 2.1V / Umax 18V
NAMUR input:
Supply 8.3V ±0,5V / 15mA max
Input resistance 1kOhm
low level < 1.2mA / high level > 2.1mA
Detection of the sensor rupture: i<0.1mA
NPN or contact: Supply: 15V ±10% / 20mA max (*)
Input resistance 2.7k to the 11V (Imax : 4mA)
PNP: Supply: 15V ±10% / 20mA max (*)
Input resistance 20k to the GND (Imax : 1mA)
(*) Supply limited to 8,3V if one of the 2 inputs is configured as «namur»
• Filtering:
Programmable analog filter: allows to suppress any parasite
noises.