Ardent Energy HF65R Installation And Operation Instruction Manual Download Page 6

Model HF65R                                                                                                        6 

FLOOR 
SHIELD 

LIP INSIDE 
FLUE COLLAR 

RADIATION SHIELD 

TRIM COLLAR 

RAIN CAP 

STORM COLLAR 

FLASHING 

CAUTION: 

UNDER NO CIRCUMSTANCES MUST ANY TYPE 

OF DAMPER OR RESTRICTION BE INSTALLED IN THE CHIM-
NEY OR CONNECTING STOVE PIPE. 
 

CHIMNEY 

 
Chimney size:  178mm (7”) dia. or 150mm x 250mm (6”X10”) 
maximum inside measure masonry chimney. 
 
Metal chimneys must be of a type suitable for wood burning ap-
pliances and masonry chimneys must be lined with an approved 
liner. 
 
ARDENT ENERGY heating units burn very efficiently, resulting in  
lower than usual flue gas temperatures. For this reason, 
outside installation of the chimney is not recommended. Due to 
the fact that it will dissipate more heat, an outside   chimney will 
cause more problems with low draft and excessive creosote ac-
cumulation. 
 
On initial operation of the heating unit a draft reading should be 
taken. (Contact your local ARDENT ENERGY dealer for further 
information on measuring draft). The draft should measure .06 
water column with the unit at normal operating temperature. If 
this reading has to be induced by a roaring fire, it is an indication 
that draft is inadequate. If the draft is more than .06 a draft  

regulator should be fitted to the connector pipe. If the draft is less 
than .06 appropriate action should be taken to improve the draft. 
 
eg.       a) insulate chimney 

b) move unit to eliminate horizontal section 
c) add to top of chimney 

 
If an existing chimney is to be used, it must be inspected carefully 
for soundness and to assure that it meets the above specifications.  
 

CHIMNEY TERMINATION 

 
Chimneys are required to extend at least 915 mm (3’) above the 
highest point where they pass through the roof of the building and 
at least 610 mm (2’) higher than any portion within ten feet. In 
some cases the chimney must be higher than minimum for enough 
draft due to unfavorable geometry of the surroundings. 

 

INSTALLATION OF OPTIONS 

 
WALL THERMOSTAT KIT (MODEL HC2) 

 
The control system consists of an electric damper control unit and 
a wall thermostat. 
 

INSTALLATION 

 
1.     Remove the 32 mm (1 1/4”) knockout at top left of rear heat 

shield. Insert arm through hole and screw the damper control 
unit into pre-drilled holes. 

 
2.     Remove left hand side shroud by unscrewing 2 screws at 

back. 

 
3.     Attach one end of ball chain to damper control arm. 
 
4.     Attach the remaining end through hole in air intake assembly. 

(There should be a slight slack in the chain) 

 
5.     Locate thermostat some distance from heater 3M — 6M 

(10’—20’) but not in another room unless direct venting is pro-
vided for hot air. 

 
6.     The thermostat should be set on an interior wall. Follow manu-

facturers instructions. 

 
7.     The heat anticipator setting should be 0.4 amps. 
 
8.     Check chain length by shutting off the manual control and 

setting the thermostat above room temperature. The draft 
damper should open to maximum. 

 
9.     Set thermostat below room temperature; the draft damper 

should close completely. Adjust chain length if required.

 

HEAT  
DEFLECTOR 

THERMOSTAT 
CONTROL 

HEAT EX-
CHANGE FINS 

HEAT SHIELD 
MOUNTING 
SCREW 

AIR INLET 
ASSEMBLY 

WATER COIL 
KNOCKOUT 

FAN 

MANUAL 
CONTROL 

FIG. 5 

HEAT DEFLECTOR 

WALL THERMOSTAT 
CONTROL 

CHECK REAR 
CLEARANCE 

7” DIA 24 GA 
STEEL CHIMNEY 

CCONNECTOR 

7” DIA LISTED 
CHIMNEY SUITABLE 
FOR WOODBURNING 
APPLIANCES 

915 mm (36”) MIN. 

FIG. 4 

Summary of Contents for HF65R

Page 1: ...Model HF65R SOLID FUEL SPACE HEATER Box 3637 Smithers BC V0J 2N0 INSTALLATION AND OPERATION INSTRUCTION MANUAL PLEASE KEEP THESE INSTRUCTIONS FOR FUTURE REFERENCE Operation Maintenance Installation...

Page 2: ...f your heater should be included with your order to assure prompt and accurate service We congratulate you on your choice of the ARDENT ENERGY heating system and may your home fires keep burning Yours...

Page 3: ...the event of an uncontrolled chimney fire shut the bypass damper and turn down the draft damper com pletely On thermostat models turn down thermo stat If chimney fire does not die down keep a watch o...

Page 4: ...temperature desired When warming up a cold room there will be an initial temperature overrun then the temperature will stabilize RELOADING 1 Have wood on hand to load firebox 2 Open bypass lever for 3...

Page 5: ...ng over the exact center of the flue of the stove and mark a spot on the ceiling to indicate the center of the chimney 3 Check that the intended location will not interfere with ceil ing joists or raf...

Page 6: ...cifications CHIMNEY TERMINATION Chimneys are required to extend at least 915 mm 3 above the highest point where they pass through the roof of the building and at least 610 mm 2 higher than any portion...

Page 7: ...he hot water coil Connection of piping to Range Boiler must be strictly followed as shown in the Diagram The 2 shut off valves must be no smaller than 3 4 inch GATE valves Make certain that the PRV Wa...

Page 8: ...OUR MODEL AND SERIAL HERE FOR EASY REFERENCE WHEN ORDERING REPLACEMENT PARTS MODEL ____________________________________________ SERIAL I ___________________________________________ DATE OF INSTALLATIO...

Page 9: ...e replaced or repaired upon return of the defective part to an au thorized Ardent Energy Ltd dealer 2 Any space heater or part thereof that is replaced or serviced during the three year warranty perio...

Reviews: