Application Description
KNX-IMPZ2 2 Channel Impulse Counter
Page 4
2.2 Parameter - 2 Independent Counter
Parameter - 2 Independent Counter - KNX-IMPZ2
Parameter
Setting
Description
Sending Values Cyclically
• send nothing
• 1 .. 120 Minutes
Measured values will be sent in the preset cycle time. If cyclical
sending is disabled, measured values will only be sent if changes
in measured values occur. A minimum interval of 10 seconds is
maintained in order to restrict bus load.
Count per Unit
0 .. 99
Impulse value must be set to the counter. The value to be set can
be calculated from the impulse value of the counter.
See
4 Notes “
Settings the Pulse Rating”
Exponent
Exponent of ten
of
10^-10 .. 10^10
The value to be set can be calculated from the parameter value
"Counts per Unit" and the display unit.
See
4 Notes “
Settings the Pulse Rating”
Preset Counter Value
( 0 - no changes )
0 .. 4.294.967.295
If there is a difference between the value displayed in the
cyclometer register and the object value 0/1 “Count of channel 1/
Channel 2", the counter can be synchronized. All impulses
already counted will be entered.
Example: A consumption of 12.553 cbm and 1 imp/l equal a
correction value of 12553.