6.1.4. IEC 61850
Device models with IEC 61850 support, can have the IEC 61850 protocol enabled by the user.
IEC61850 edition1 is used by AQ-200 series IEDs. IEC 61850 in Arcteq devices support the following
services:
Dataset, pre-de ned datasets can be edited with IEC 61850 editor tool in Aqtivate.
Report control block, both buffered and un-buffered reporting is supported.
Control, ‘direct-with-normal-security’ control sequences are supported.
Disturbance recording le transfer
GOOSE
Time synchronization
Currently used 61850 setup of the device can be viewed in the IEC61850 tool (
Tools
→
IEC61850
).
For a list of available Logical Nodes in the Arcteq implementation browse the 61850 tree. See following
picture:
Figure. 6.1.4. - 160. IEC 61850 tool buttons.
The available functions in the IEC 61850 tool are:
1. Open an existing CID- le from the PC hard drive
2. Save the CID le into the aqs currently open (save the aqs le as well [
File
→
Save
] to keep the
changes)
3. Save the CID le into the hard drive for later use.
4. Exports current CID le without private tags
5. Exports dataset info into a txt le that can be viewed in table format in tools like Excel
6. Opens main con gurations window
7. Opens data set editing window
8. Send the CID con guration to the relay (requires a connection to the relay)
9. Retrieves the default CID le from the relay.