Instruction manual –AQ F210 Feeder Protection IED
266 (292
)
-
Current measurement inaccuracy
-
Angle measurement inaccuracy
-
Burden (50Hz/60Hz)
0.002xIn…25xIn < ±0.5% or < ±0.6mA
25xIn…375xIn < ±0.5%
< ±0.1 °
<0.1VA
Terminal block
-
Solid or stranded wire
-
Phoenix Contact FRONT 4H-6,35
Maximum wire diameter:
4 mm
2
9.1.2
A
UXILIARY VOLTAGE
Table 9.1.2-2 Power supply model A
Rated auxiliary voltage
85…265V(AC/DC)
Power consumption
< 7W
< 15W
Maximum permitted interrupt time
< 150ms with 110VDC
DC ripple
< 15 %
Terminal block
-
Solid or stranded wire
-
Phoenix Contact MSTB2,5-5,08
Maximum wire diameter:
2.5mm
2
Table 9.1.2-3 Power supply model B
Rated auxiliary voltage
18…72VDC
Power consumption
< 7W
< 15W
Maximum permitted interrupt time
< 150ms with 110VDC
DC ripple
< 15 %
Terminal block
-
Solid or stranded wire
-
Phoenix Contact MSTB2,5-5,08
Maximum wire diameter:
2.5mm
2
9.1.3
B
INARY INPUTS
Table 9.1.3-4 Isolated binary inputs with software settable threshold
Rated auxiliary voltage
5…265V(AC/DC)
Pick-up threshold
Release threshold
Software settable: 5…240V, by step of 1V
Software settable: 5…240V, by step of 1V
Scanning rate
5 ms
Pick-up delay
Software settable: 0…1800s
Polarity
Software settable: Normally On / Normally Off
Current drain
2 mA
Terminal block
-
Solid or stranded wire
-
Phoenix Contact MSTB2,5-5,08
Maximum wire diameter:
2.5mm
2