Event number
Event channel
Event block name
Event code
Description
3529
55
THD1
9
THD Alarm I01 OFF
3530
55
THD1
10
THD Alarm I02 ON
3531
55
THD1
11
THD Alarm I02 OFF
3532
55
THD1
12
Blocked ON
3533
55
THD1
13
Blocked OFF
The function registers its operation into the last twelve (12) time-stamped registers. The register of the
function records the ON event process data for ACTIVATED, BLOCKED, etc. The table below
presents the structure of the function's register content.
Table. 5.5.5 - 235. Register content.
Date and
time
Event
code
L1h, L2h, L3h
pretriggering current
L1h, L2h, L3h
Fault current
L1h, L2h, L3h
Prefault current
Used SG
dd.mm.yyyy
hh:mm:ss.mss
3520-3533 Descr. Start/alarm -20ms THD
of each phase.
Start/Alarm THD of
each phase.
Start -200 ms THD
of each phase.
Setting group
1...8 active.
5.5.6 Disturbance recorder (DR)
The disturbance recorder is a high-capacity (64 MB) and fully digital recorder integrated to the
protection relay. The maximum sample rate of the recorder's analog channels is 64 samples per cycle.
The recorder also supports 95 digital channels simultaneously with the twenty (20) measured analog
channels.
The recorder provides a great tool to analyze the performance of the power system during network
disturbance situations. The recorder's output is in general COMTRADE format and it is compatible with
most viewers and injection devices. The files are based on the IEEE standard C37.111-1999. Captured
recordings can be injected as playback with secondary testing tools that support the COMTRADE file
format. Playback of files might help to analyze the fault, or can be simply used for educational
purposes.
Analog and digital recording channels
Up to 20 analog recording channels and 95 digital channels are supported. The available analog
channels vary according to the device type.
Table. 5.5.6 - 236. Analog recording channels.
Signal
Description
IL1
Phase current I
L1
IL2
Phase current I
L2
IL3
Phase current I
L3
I01c
Residual current I
01
coarse*
I01f
Residual current I
01
fine*
I02c
Residual current I
02
coarse*
I02f
Residual current I
02
fine*
IL1”
Phase current I
L1
(CT card 2)
IL2”
Phase current I
L2
(CT card 2)