Return to default
view
If the user navigates to a menu and gives no input after a period of
time de ned with this parameter, the unit will return to the default
view automatically. If time is set to 0 s, this feature is not in use.
0…3600 s
10 s
0 s
LED test
When activated, all LEDs are lit up. LEDs with multiple possible
colors blink each color.
0: -
1: Activated -
0: -
Reset latches
Resets the latched signals in the logic and the matrix. When a reset
command is given the parameter will return back to “-“
automatically.
0: -
1: Reset
-
0: -
Measurement
recorder
Enables the
Measurement recorder
tool. The Measurement recorder
is con gured in
Tools
→
Misc
→
Measurement recorder.
0: Disabled
1: Enabled
-
0: Disabled
Mimic recon gure Reload the mimic to the unit.
0: -
1:
Recon gure
-
0: -
Table. 5.4. - 78. The
General
menu indications
Name
Description
Serial number
The unique serial number identi cation of the unit.
SW version
The rmware software version of the unit.
HW conf.
The order code identi cation of the unit.
UTC time
The UTC time value which the device's clock uses.
5.5. Control functions
5.5.1. Setting group selection
All relay types support up to eight (8) separate setting groups. The Setting group selection function
block controls the availability and selection of the setting groups. By default, only Setting group 1
(SG1) is active and therefore the selection logic is idle. When more than one setting group is enabled,
the setting group selector logic take control of the setting group activations based on the logic and
conditions the user has programmed.
The following gure presents a simpli ed function block diagram of the setting group selection function.
Figure. 5.5.1. - 63. Simpli ed function block diagram of the setting group selection function.
AQ-E215
Instruction manual
Version: 2.01
93